Chapter 2 – Installation
Page 2-4
TestEquity 1016H-2 Temperature/Humidity Chamber
Connection to the Power Source
2
CAUTION:
This chamber should be connected to the AC power source by a qualified
electrician who is familiar with industrial plant wiring.
The Main Disconnect Switch on the front panel removes primary power to the entire chamber.
All branch circuits on the load side of the Main Disconnect Switch are individually fused.
However, your local electrical code may require a separate disconnect switch within sight of the
chamber.
Power Source Connection
1.
Turn the Disconnect Switch to the OFF position.
2.
Remove the lower door retaining screw located on the right side. Open the lower door.
3.
Remove the chamber’s right side panel.
4.
Mount the input wire through the hole on the rear of the chamber, using an appropriate strain
relief bushing. Approximately 54-inches of additional wire length will be needed need to
reach to the terminals on the electrical subpanel. The wires will need to pass through the
Input Access Hole. This hole is in the corner of the partition which separates the compressor
compartment from the electrical compartment. Three tie points are provided on the side of
the chamber to secure the input wiring with provided tie-wraps.
Three Phase Input
1.
Locate the Disconnect Switch.
2.
Connect the “Hot” input wires to terminals L1, L2 and L3 on the Main Disconnect Switch.
3.
Connect the Ground wire (NOT A NEUTRAL) to the Ground terminal.
4.
Put the chamber side panel back on and close the lower door.
NOTE:
The Disconnect Switch and the Disconnect Knob must both be in the off position before
closing the door. Failure to do this will result in damage to the Disconnect Switch and the
Disconnect Knob.
Single Phase Input
1.
Locate the Disconnect Switch.
2.
Connect the “Hot” input wires to terminals L1 and L2 on the Main Disconnect Switch.
3.
Connect the Ground wire (NOT A NEUTRAL) to the Ground terminal.
4.
Put the chamber side panel back on and close the lower door.
NOTE:
The Disconnect Switch and the Disconnect Knob must both be in the off position before
closing the door. Failure to do this will result in damage to the Disconnect Switch and the
Disconnect Knob.