![Test Instrument Solutions SafetyPAT Operating Manual Download Page 19](http://html1.mh-extra.com/html/test-instrument-solutions/safetypat/safetypat_operating-manual_1091886019.webp)
1
8
Mains Socket Test
Good Show LN
√
LE
√
NE
√
Ground Show LN
√
LE× NE×
NE (NG) Show LN× LE
√
NE×
Batteries
LR6 AA 1.5V x 8
Low Voltage < 9V
Class
Ⅰ
Class
Ⅱ
Cord
Earth Continuity
<0.5ohms
N/A
<0.5ohm
Insulation
Resistance
>1.0Mohms
>2.0 Mohms
>1.0 Mohms
Remark
:
Earth Continuity Resistance 0.5
Ω
as PASS
Insulation Resistance class I 1.0M
Ω
,class II 2.0M
Ω
as PASS