Symptom
Possible cause
Remedy
Fault code is shown as 14 on LCD
display and alarm is continuously
sounding.
The UPS shut down
automatically because
short circuit occurs on the
UPS output.
Check output wiring and if
connected devices are in
short circuit status.
Fault code is shown as 01, 02, 03,
11, 12, 13 and 41 on LCD display
and alarm is continuously
sounding.
A UPS internal fault has
occurred. There are two
possible results:
1. The load is still supplied,
but directly from AC power
via bypass.
2. The load is no longer
supplied by power.
Contact your dealer
Battery backup time is shorter
than nominal value.
Batteries are not fully
charged
Charge the batteries for at
least 5 hours and then
check capacity. If the
problem still persists,
consult your dealer.
Batteries defect
Contact your dealer to
replace the battery.
Fault code is shown as 2A on LCD
display and alarm is continuously
sounding.
The short circuit occurs on
the charger output.
Check if battery wiring of
connected external pack is
in short circuit status.
Fault code is shown as 45 on LCD
display. At the same time, alarm is
continuously sounding.
The charger does not have
output and battery voltage
is less than 10V/PC.
Contact your dealer.
5. Storage and Maintenance
Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years
at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this
case, please contact your dealer.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry
location. During storage, recharge the battery in accordance with the following table:
Storage Temperature
Recharge Frequency
Charging Duration
-25°C - 40°C
Every 3 months
1-2 hours
40°C - 45°C
Every 2 months
1-2 hours
Be sure to deliver the spent battery to a recycling facility or ship it to your
dealer in the replacement battery packing material.
Summary of Contents for Prime Plus 1101 SRT
Page 15: ...15 USER MANUAL PRIME PLUS 1 1 1 3 kVA NLINE UPS 12 3 3 1 3 4 2 Tapes Tapes...
Page 16: ...16 www tescom ups gr USER MANUAL PRIME PLUS 1 1 1 3 kVA NLINE UPS 13 4 4 1 2 T 3 4 6 1 2...
Page 32: ...32 www tescom ups gr USER MANUAL PRIME PLUS 1 1 1 3 kVA NLINE UPS l UPS 2 2 2 EEPROM 2...
Page 69: ...7 183 46 Volou 7 18 346 Moschato Greece 30 210 9590080 www tescom ups gr info tescom ups gr...