27
R24 WAITING DC BUS
Warning Rectifier is waiting DC BUS to raise for startup
R25 BATTERY FAILURE
Warning Battery test failed
R26 BATT TEMP SENSOR
Warning Battery temperature sensor is defected or not connected
R27 BATT TEMP HIGH
Warning Battery ambient temperature is high
R29 PFC RESET
Warning Rectifier module power on
R30 PLEASE WAIT
Warning Rectifier waits as adjusted startup delay
R31 RECTIFIER START
Warning Rectifier is in soft start stage
Panel module alarm codes
L01 TH1 TEMP HIGH
Warning TH1 temperature is high
L02 TH2 TEMP HIGH
Warning TH2 temperature is high
L03 TH1 TEMP LOW
Warning TH1 temperature is low
L04 TH2 TEMP LOW
Warning TH2 temperature is low
L05 FAN MAINT
Warning FAN maintenance time
L06 BATTERY MAINT
Warning Battery maintenance time
L07 OPT MAINTENANCE
Warning Optional maintenance time
L08 TH1 SENSOR FAIL
Warning TH1 temperature sensor failure
L09 TH2 SENSOR FAIL
Warning TH2 temperature sensor failure
L10 ENTER FAULT RESET
Warning UPS is waiting fault reset for startup
L11 BATT CB OPEN
Warning External interactive battery switch is off
L12 GENERAL MAINT
Warning General maintenance time
L13 PFC CAN COMM ERR
Warning PFC module CAN communication timeout
L14 INV CAN COMM ERR
Warning INV module CAN communication timeout
Inverter module alarm codes
INV CODE = 0XXX
Current inverter modüle status code
A00 INV FAULT = XXXX
Hata
XXXX fault occured at the inverter module
CALL SERVICE !
A01 O/P OVERCURRENT
Alarm
IGBT saturation alarm on inverter module
A02 OVERTEMP SHUT
Alarm
Overtemperature at inverter power module
A03 BATT HIGH
Alarm
Inverter module measured battery voltage high
A04 OUTPUT V.LOW
Alarm
Inverter output voltage is low
A05 OUTPUT V.HIGH
Alarm
Inverter output voltage is high
A06 OVERLOAD SHUT
Alarm
Overload at UPS output
A07 SHORT CIRCUIT
Alarm
Short circuit at UPS output
A08 ON MAINTENANCE
Alarm
Maintenance by-pass switch on
A09 MANUAL BYPASS
Alarm
Load is transferred to by-pass from front panel
A10 BATTERY LOW SHUT
Alarm
Inverter measured battery voltage is low (shutdown level)
A11 REPO STOP
Alarm
External REPO input signal sensed
A12 DC BALANCE BAD
Alarm
Before inverter start fitler capacitors dont discharged
A13 PEAK CURRENT
Alarm
Very high current at the UPS output
A14 INV NOT START
Alarm
Inverter module start failed
A17 BYPASS FAILURE
Warning By-pass input voltage failure
A18 BYPASS VOLT
Warning By-pass input voltage out of tolerance
A19 BYP FREQ.TOLER
Warning By-pass input frequency out og tolerance
A20 OVERLOAD
Warning Currently the load exceeded 100% capacity
A21 OVERTEMP
Warning Currently inverter power modul heatsink temperature is high
A22 OUTPUT OFF
Warning There is no UPS output voltage
A23 ON BYPASS
Warning Load is on bypass
A24 REVERSE CURRENT
Warning Regenerative backfeed to UPS output
A25 INV RESET
Warning Inverter module power on
A26 BATTERY LOW
Warning Batteries are going to full discharge
A27 GENERATOR MODE
Warning Generator set is running
A28 O/P PHASE LOSS
Warning Anyone of the UPS output phases there is no voltage
A29 SYNCHRON BAD
Warning Inverter is not synchron to by-pass input
A30 SHORT CIRCUIT
Warning Short circuit occured at the UPS output currenty normal
A31 OUTPUT SWITCH
Warning Output switch of the UPS is off
Summary of Contents for DS300 Series
Page 1: ...DS300 SERIES DSP Controlled UPS 100 120 160 kVA 3 Phase In 3 Phase Out USER MANUAL...
Page 2: ......
Page 53: ......
Page 54: ...AGKK10632 09 2021...