Warning: The mounting of the water heater should be performed by
an authorized person. Please contact our authorized dealers who are
powered by the authorized gas administration (EGO, İGDAŞ,
BOTAŞ, İZGAZ, etc). Do not try to operate your device by yourself.
The waste gas pipe should not be mounted to the general pipe or the
ventilation space of the building. The waste gas pipe should have an
outlet to outside buildig and there should be at least 500 mm space
from the open part of the exhaust outside the building. The open
edge of the air inlet pipe should be at least 100 away from the wall
where it is mounted.
In order to prevent the backflow of the condensed water or the rain
water to the heater, the part of the waste gas pipe remaining outside
the environment should be placed as to make a horizontal angle of 3
degrees.
Avoid the strong wind blowing as much as possible regarding the
waste gas pipe. Backflow may lead the device to get out of function.
The environment where the water heater is mounted should be free
from blocking, preventing parts and projections during the repair and
maintenance; there should be sufficient space around the device for
repair and maintenance.
Flammable and explosive substances must definitely be kept away
from the water heater.
The waste gas pipe can be extended when necessary however the
total pipe length should not exceed 2 m. The extension pipe should
be supplied by TERMOMEX. More than 2 brackets should not be
used for extension (including original bracket), the pipes should be
appropriately fixed.
4. THE MOUNTING OF YOUR WATER HEATER
4.1. Mounting Conditions and Safety Warnings