x.2.2.2.1.5.2.3.0
S51HYSTInt
read-write
S51 hysteresis value x1000 in Integer format
Integer32
x.2.2.2.1.5.3.1.0
S52MAXInt
read-write
S52 maximum value x1000 in Integer format
Integer32
x.2.2.2.1.5.3.2.0
S52MINInt
read-write
S52 minimum value x1000 in Integer format
Integer32
x.2.2.2.1.5.3.3.0
S52HYSTInt
read-write
S52 hysteresis value x1000 in Integer format
Integer32
setup -> io -> sensorsSetup -> sensor6setup
OID
Name
Access
Description
Syntax
x.2.2.2.1.6.1.0
S6description
read-write
Sensor 6 description
DisplayString
x.2.2.2.1.6.2.1.0
S61MAXInt
read-write
S61 maximum value x1000 in Integer format
Integer32
x.2.2.2.1.6.2.2.0
S61MINInt
read-write
S61 minimum value x1000 in Integer format
Integer32
x.2.2.2.1.6.2.3.0
S61HYSTInt
read-write
S61 hysteresis value x1000 in Integer format
Integer32
x.2.2.2.1.6.3.1.0
S62MAXInt
read-write
S62 maximum value x1000 in Integer format
Integer32
x.2.2.2.1.6.3.2.0
S62MINInt
read-write
S62 minimum value x1000 in Integer format
Integer32
x.2.2.2.1.6.3.3.0
S62HYSTInt
read-write
S62 hysteresis value x1000 in Integer format
Integer32
setup -> io -> sensorsSetup -> sensor7setup
OID
Name
Access
Description
Syntax
x.2.2.2.1.7.1.0
S7description
read-write
Sensor 7 description
DisplayString
x.2.2.2.1.7.2.1.0
S71MAXInt
read-write
S71 maximum value x1000 in Integer format
Integer32
x.2.2.2.1.7.2.2.0
S71MINInt
read-write
S71 minimum value x1000 in Integer format
Integer32
x.2.2.2.1.7.2.3.0
S71HYSTInt
read-write
S71 hysteresis value x1000 in Integer format
Integer32
x.2.2.2.1.7.3.1.0
S72MAXInt
read-write
S72 maximum value x1000 in Integer format
Integer32
x.2.2.2.1.7.3.2.0
S72MINInt
read-write
S72 minimum value x1000 in Integer format
Integer32
x.2.2.2.1.7.3.3.0
S72HYSTInt
read-write
S72 hysteresis value x1000 in Integer format
Integer32
setup -> io -> sensorsSetup -> sensor8setup
OID
Name
Access
Description
Syntax
x.2.2.2.1.8.1.0
S8description
read-write
Sensor 8 description
DisplayString
x.2.2.2.1.8.2.1.0
S81MAXx10Int
read-write
S81 maximum value x1000 in Integer format
Integer32
x.2.2.2.1.8.2.2.0
S81MINx10Int
read-write
S81 minimum value x1000 in Integer format
Integer32
x.2.2.2.1.8.2.3.0
S81HYSTx10Int
read-write
S81 hysteresis value x1000 in Integer format
Integer32
x.2.2.2.1.8.3.1.0
S82MAXx10Int
read-write
S82 maximum value x1000 in Integer format
Integer32
x.2.2.2.1.8.3.2.0
S82MINx10Int
read-write
S82 minimum value x1000 in Integer format
Integer32
x.2.2.2.1.8.3.3.0
S82HYSTx10Int
read-write
S82 hysteresis value x1000 in Integer format
Integer32
setup -> io -> analogSetup -> analog1setup
OID
Name
Access
Description
Syntax
x.2.2.2.2.1.1.0
voltage1description
read-write
Voltage 1 description
DisplayString
x.2.2.2.2.1.2.0
voltage1max
read-write
Voltage 1 maximum
Integer32
x.2.2.2.2.1.3.0
voltage1min
read-write
Voltage 1 minimum
Integer32
x.2.2.2.2.1.4.0
voltage1hyst
read-write
Voltage 1 hysteresis
Integer32
setup -> io -> analogSetup -> analog2setup
OID
Name
Access
Description
Syntax
x.2.2.2.2.2.1.0
voltage2description
read-write
Voltage 2 description
DisplayString
x.2.2.2.2.2.2.0
voltage2max
read-write
Voltage 2 maximum
Integer32
x.2.2.2.2.2.3.0
voltage2min
read-write
Voltage 2 minimum
Integer32
x.2.2.2.2.2.4.0
voltage2hyst
read-write
Voltage 2 hysteresis
Integer32
setup -> io -> digitalSetup
OID
Name
Access
Description
Syntax
x.2.2.2.3.1.0
digitalInput1description
read-write
Digital Input 1 description"
DisplayString
x.1.2.2.3.2.0
digitalInput2description
read-write
Digital Input 2 description
DisplayString