Installation and setup
This device must be installed by qualified personnel.
This device must not be installed directly outdoors.
The installation consists of mounting the device, connecting to an IP network, connecting inputs and
outputs, providing power and configuring via a web browser.
6.1.
Mounting
TCW210-TH should be mounted in a clean and dry location on a not flammable surface. Ventilation
is recommended for installations where the ambient air temperature is expected to be high.
Maintain spacing between adjacent equipment. Allow 50 mm of space on all sides, as shown in
Appendix A, this provides ventilation and electrical isolation.
6.2.
Connection
Attention! Disconnect power supply before wiring.
The correct wiring procedure is as follows:
•
Make sure power is turned off;
•
Apply all sensors;
•
Apply power.
Make sure that cables are properly attached. Not proper wiring and configuration can cause
permanent damage to TCW210-TH or the equipment to which it is connected or both.
Connector 1
Ethernet - RJ45
Connector 4
Pin1
–
not connected (most left)
Connector 2
Power - 2.1x5.5mm connector,
central positive
Pin2
–
not connected
Connector 3
Pin1
–
GND (most left)
Pin3
–
not connected
Pin2
–
GND
Pin4
–
Line B-
Pin3
–
1-Wire Data
Pin5
–
Line A+
Pin4
–
1-Wire GND
Pin6
–
not connected
Pin5
–
+VDD
Pin7
–
+VDD
Pin6
–
+VDD (most right)
Pin8
–
GND
6.2.1.
Power supply
TCW210-TH is designed to be supplied by adapter SYS1421-0612-W2E or similar, intended for
use in the conditions of overvoltage category II, and prior assessed for compliance with safety