Warranty Information 

All Air Medic units carry a parts only warranty for a period of 1 year from date of shipment.  
 
For all Warranty and Part Sales queries please visit Temspec.com or call 888-836-7732. 
 

Table 1: Component Replacement Frequency 

 

Size 

Part No. 

Change Frequency 

Prefilter 

16” x 18” x 1” 

MERV 8 

FPY 16118 

3-6 months 

H.E.P.A 95 

Filter 

18

” x 

20

” x 6” 

MERV 16 

FPH 18620 

2 years or when 

indicator is lit 

Activated 

Carbon 

Filter 

16” x 18” x 1” 

MERV 7 

FPC 16118 

1 year 

UVC Light 

16 Watt 

EUL 01516 

1 year 

 

 

Table 2: Unit Specifications 

 

TIF- 06 

TIF-08 

Performance 

450 CFM 

600 CFM Purge 

Mode 

450 CFM 

800 CFM Purge 

Mode 

Electrical 

120 VAC 

2.6 FLA 

6ft, 2m Power cord 

120 VAC 

3.4 FLA 

6ft, 2m Power cord 

Fan & Motor 

250mm Backward 

Inclined Impeller 

fan with ECM 

20 

 100% fan 

modulation 

600C FM @ 1.2

” 

TSP 

285/s @ 300pa 

280mm Backward 

Inclined Impeller fan 

with ECM 

20-100% fan 

modulation 

800 CFM @ 1.2

” TSP

 

375/s @ 300pa 

Physical Data 

36”H x 

20

” W

 x 22

” 

915mm x 510mm x 

560mm 

Weight: 95lbs, 43kg 

52

”H x 

20

” W

 x 26

” 

1320mm x 510mm x 

660mm 

Weight: 95lbs, 43kg

 

 

 

 

Summary of Contents for Air Medic TIF-06

Page 1: ...IOM 2020 0 2360 Millrace Court Tel 905 670 3595 Mississauga Ontario Fax 905 670 3592 Canada L5N 1W2 Web Temspec com Air Medic Air Filtration Sterilization Unit TIF 06 Installation Operation Maintenance Manual ...

Page 2: ...nel 3 4 4 Motor Access Panel 4 5 Air Medic Component Installation Maintenance and Replacement Instructions 4 5 1 Filters 4 5 1 1 Prefilter 4 5 1 2 HEPA Filter 5 5 1 3 Activated Carbon Filter Optional Accessory 5 5 2 Casters Optional Accessory 6 5 3 UVC Light Optional Accessory 6 5 4 Ionizer Optional Accessory 7 5 5 Fan Assembly 8 5 6 Differential Pressure Switch Optional Accessory 8 6 Warranty Inf...

Page 3: ...e hot and could cause serious burns if not handled properly Please wait until the lamp has cooled to room temperature to remove from the unit WARNING UV Light Hazard Harmful to skin and eyes Can cause temporary or permanent loss of vision Never look at the lamp while illuminated To prevent exposure to ultraviolet light be sure the power is disconnected before servicing CAUTION Ionizer generates hi...

Page 4: ... switched This pressure switch measures the air pressure around the HEPA filter and when it is too high the indicator light will come on to warn the user it should be changed This is only a warning indicator The unit will continue to work with it on but the airflow will be decreased due to the dirty filter 3 3 Fan Control The fan control is available in either variable speed or constant speed conf...

Page 5: ...el is equipped with two cam latches that turn to lock in place to secure the panel and the optional lock mentioned above To open the lower access panel unlock the cam lock turn the cam latches to the unlocked position and then pull up and out When replacing the panel align the panel with the width of the unit and slide it down onto the hook at the bottom Make sure not to damage the power cable 4 3...

Page 6: ...initial dust and dirt particles before they can get inside of the Air Medic similar to your HVAC equipment 5 1 1 2 Replacement Frequency The replacement frequency for the Prefilters can be found in Table 1 5 1 1 3 Replacement Instructions To replace the Prefilters when they are dirty they need to be removed To remove the Prefilters the lower access panel must be removed Lift out of the lower guide...

Page 7: ...d then tighten the wingnuts 5 1 3 Activated Carbon Filter Optional Accessory 5 1 3 1 Description An optional accessory for the Air Medic is two 1 inch Activated Carbon Filters These filters make use of Activated Carbon to adsorb airborne particles to help with allergens and odours 5 1 3 2 Installation Instructions The Activated Carbon filters are installed on the intakes behind the Prefilters To i...

Page 8: ...on the fan assemblies 5 3 1 2 Installation Instructions First remove the lower and upper access panel and then remove the HEPA filter Take the light ballast and align the tabs with the holes on the right fan bulkhead closest to the wall of the unit and screw them down with the provided Philips head screws Take supplied UVC mount assembly and align it with the four holes two on each bulkhead and wi...

Page 9: ...ews Attach the ionizer quick connect to the 2 pin quick connect to the unit quick connect below the electrical cover Ensure they have a firm and properly sealed connection and that the locks have fully engaged 5 4 1 3 Maintenance Interval It is recommended that every six 6 months the ionizer being inspected for dust or dirt buildup on the brushes or indicator light If there is dust or dirt it shou...

Page 10: ...l pressure switch This switch measures the pressure around the HEPA filter with the use of 1 4 tubing to let the operator know when the HEPA needs to be replaced When the pressure differential around the HEPA rises above the recommended level the switch will close and it will light the amber indicator light on the unit face 5 6 1 2 Maintenance Interval The switch is fully sealed and does not need ...

Page 11: ...vated Carbon Filter 16 x 18 x 1 MERV 7 FPC 16118 1 year UVC Light 16 Watt EUL 01516 1 year Table 2 Unit Specifications TIF 06 TIF 08 Performance 450 CFM 600 CFM Purge Mode 450 CFM 800 CFM Purge Mode Electrical 120 VAC 2 6 FLA 6ft 2m Power cord 120 VAC 3 4 FLA 6ft 2m Power cord Fan Motor 250mm Backward Inclined Impeller fan with ECM 20 100 fan modulation 600C FM 1 2 TSP 285 s 300pa 280mm Backward I...

Page 12: ...EMC 09004 CONSTANT SPEED FAN CONTROLLER EMC 09003 DOOR INTERLOCK SWITCH ESX 08000 DIFFERENTIAL PRESSURE SWITCH ESD 22000 CASTER WHEELS LOCKING WCX 51608 CASTER WHEELS WCX 51608 LIFT HANDLE VHX 01004 KEYED CAM LOCK NXL 01008 FAN BFE 025017 3 4IN FAN SCREW NSL 00306 IONIZER NUT NNX 21024A UVC THUMB NUT NNT 00202 CAM LOCK NXL 01010 3 4IN SCREW NSH 10206 1 2IN SCREW NSL 00304 CASTER LOCK WASHER NWX 21...

Reviews: