- 2 - 

2

 

Product Overview  

The Air Medic unit is designed to enhance the air filtration of your primary HVAC system. It does not have the ability to heat or cool 
and  provides  filtration  and  sterilization  only.  This  unit  is  not  a  substitute  for  other  virus  spread  measures  such  as  frequent  hand 
sanitization, face masks or 6ft (2m) physical distancing.  

2.1

 

Model Number 

For the full model numbers available and product selection options please visit our website at 

www.temspec.com

. 

3

 

Operation  

The Air Medic Unit has a few different control options depending on the configuration chosen.  For all units, the Air Medic must be 
plugged into a standard 120V receptacle with ground pin. 

3.1

 

On/Off switch 

If the on/ off switch is chosen it will control the power to the 
unit once plugged in

. The switch will light up when in the “on” 

position to indicate power to the unit. 

If no switch is selected all devices will have power as soon as 
the unit plugged in. 

3.2

 

Filter Clogged Indicator Light 

An optional filter clogged indicator light is available. This light 
is  connected  to  the  differential  pressure  switched.  This 
pressure  switch  measures  the  air  pressure  around  the  HEPA 
filter and when it is too high the indicator light will come on to 
warn the user it should be changed.  

This is only a warning indicator. The unit will continue to work 
with it on, but the airflow will be decreased due to the dirty 
filter.  

3.3

 

Fan Control 

The fan control is available in either variable speed or constant 
speed configurations. The speed of the fan directly relates to 
the amount of airflow. 

3.3.1

 

Variable Speed

Variable  speed  motor  control  allows  the  user  to  directly 
control the fan speed from the face of the unit. Turning the dial 
clockwise increases the speed, and counterclockwise slows the 
fan down. Turning the dial all the way  counterclockwise you 
will hear a click, which will turn the fan off, as well as the UVC 
light and Ionizer (if applicable). 

3.3.2

 

Constant Speed

Constant speed control allows the unit to run at a single speed 
when it is turned on, with no outside adjustment.  

Inside of the electrical chamber, there is a speed board which 
will  allow  the  user  to  turn  up  or  down  the  fan  speed  to  the 
desired set point. The speed board is controlled by turning the 
dial clockwise to increase and  counterclockwise to decrease. 
The  adjustment  can  be  done  with  a  small  slot  terminal 
screwdriver.  

Summary of Contents for Air Medic TIF-06

Page 1: ...IOM 2020 0 2360 Millrace Court Tel 905 670 3595 Mississauga Ontario Fax 905 670 3592 Canada L5N 1W2 Web Temspec com Air Medic Air Filtration Sterilization Unit TIF 06 Installation Operation Maintenance Manual ...

Page 2: ...nel 3 4 4 Motor Access Panel 4 5 Air Medic Component Installation Maintenance and Replacement Instructions 4 5 1 Filters 4 5 1 1 Prefilter 4 5 1 2 HEPA Filter 5 5 1 3 Activated Carbon Filter Optional Accessory 5 5 2 Casters Optional Accessory 6 5 3 UVC Light Optional Accessory 6 5 4 Ionizer Optional Accessory 7 5 5 Fan Assembly 8 5 6 Differential Pressure Switch Optional Accessory 8 6 Warranty Inf...

Page 3: ...e hot and could cause serious burns if not handled properly Please wait until the lamp has cooled to room temperature to remove from the unit WARNING UV Light Hazard Harmful to skin and eyes Can cause temporary or permanent loss of vision Never look at the lamp while illuminated To prevent exposure to ultraviolet light be sure the power is disconnected before servicing CAUTION Ionizer generates hi...

Page 4: ... switched This pressure switch measures the air pressure around the HEPA filter and when it is too high the indicator light will come on to warn the user it should be changed This is only a warning indicator The unit will continue to work with it on but the airflow will be decreased due to the dirty filter 3 3 Fan Control The fan control is available in either variable speed or constant speed conf...

Page 5: ...el is equipped with two cam latches that turn to lock in place to secure the panel and the optional lock mentioned above To open the lower access panel unlock the cam lock turn the cam latches to the unlocked position and then pull up and out When replacing the panel align the panel with the width of the unit and slide it down onto the hook at the bottom Make sure not to damage the power cable 4 3...

Page 6: ...initial dust and dirt particles before they can get inside of the Air Medic similar to your HVAC equipment 5 1 1 2 Replacement Frequency The replacement frequency for the Prefilters can be found in Table 1 5 1 1 3 Replacement Instructions To replace the Prefilters when they are dirty they need to be removed To remove the Prefilters the lower access panel must be removed Lift out of the lower guide...

Page 7: ...d then tighten the wingnuts 5 1 3 Activated Carbon Filter Optional Accessory 5 1 3 1 Description An optional accessory for the Air Medic is two 1 inch Activated Carbon Filters These filters make use of Activated Carbon to adsorb airborne particles to help with allergens and odours 5 1 3 2 Installation Instructions The Activated Carbon filters are installed on the intakes behind the Prefilters To i...

Page 8: ...on the fan assemblies 5 3 1 2 Installation Instructions First remove the lower and upper access panel and then remove the HEPA filter Take the light ballast and align the tabs with the holes on the right fan bulkhead closest to the wall of the unit and screw them down with the provided Philips head screws Take supplied UVC mount assembly and align it with the four holes two on each bulkhead and wi...

Page 9: ...ews Attach the ionizer quick connect to the 2 pin quick connect to the unit quick connect below the electrical cover Ensure they have a firm and properly sealed connection and that the locks have fully engaged 5 4 1 3 Maintenance Interval It is recommended that every six 6 months the ionizer being inspected for dust or dirt buildup on the brushes or indicator light If there is dust or dirt it shou...

Page 10: ...l pressure switch This switch measures the pressure around the HEPA filter with the use of 1 4 tubing to let the operator know when the HEPA needs to be replaced When the pressure differential around the HEPA rises above the recommended level the switch will close and it will light the amber indicator light on the unit face 5 6 1 2 Maintenance Interval The switch is fully sealed and does not need ...

Page 11: ...vated Carbon Filter 16 x 18 x 1 MERV 7 FPC 16118 1 year UVC Light 16 Watt EUL 01516 1 year Table 2 Unit Specifications TIF 06 TIF 08 Performance 450 CFM 600 CFM Purge Mode 450 CFM 800 CFM Purge Mode Electrical 120 VAC 2 6 FLA 6ft 2m Power cord 120 VAC 3 4 FLA 6ft 2m Power cord Fan Motor 250mm Backward Inclined Impeller fan with ECM 20 100 fan modulation 600C FM 1 2 TSP 285 s 300pa 280mm Backward I...

Page 12: ...EMC 09004 CONSTANT SPEED FAN CONTROLLER EMC 09003 DOOR INTERLOCK SWITCH ESX 08000 DIFFERENTIAL PRESSURE SWITCH ESD 22000 CASTER WHEELS LOCKING WCX 51608 CASTER WHEELS WCX 51608 LIFT HANDLE VHX 01004 KEYED CAM LOCK NXL 01008 FAN BFE 025017 3 4IN FAN SCREW NSL 00306 IONIZER NUT NNX 21024A UVC THUMB NUT NNT 00202 CAM LOCK NXL 01010 3 4IN SCREW NSH 10206 1 2IN SCREW NSL 00304 CASTER LOCK WASHER NWX 21...

Reviews: