- 7 -
5.4
Ionizer (Optional Accessory)
5.4.1.1
Description
An optional accessory is the Ionizer. This is a small device that
creates both negative and positive ions into the airstream.
These ions attract and stick to airborne pollutants and harmful
particles. This creates larger clusters in the air which allow
them to be trapped by filters more efficiently. The transfer of
ions between the air and the pollutants in the air also help to
render them inert.
The ionizer is supplied with a cover assembly. This cover is used
to help protect the ionizing brushes from any debris or
cleaning solution falling through the top panel.
5.4.1.2
Installation Instructions
To install the ionizer, first attach the ionizer to the cover
assembly with the provided nuts and bolts. Ensure the brushes
are facing away from the back of the cover assembly, and not
to over tighten the nuts.
Then, remove the lower and upper access panels. Align the
cover assembly with the holes on the outside of the electrical
cover, and mount using the provided Philips head screws.
Attach the ionizer quick connect to the 2-pin quick connect to
the unit quick connect below the electrical cover. Ensure they
have a firm and properly sealed connection, and that the locks
have fully engaged.
5.4.1.3
Maintenance Interval
It is recommended that every six (6) months the ionizer being
inspected for dust or dirt buildup on the brushes or indicator
light.
If there is dust or dirt, it should be removed with compressed
air or small alcohol towelette. Let the alcohol dry before
turning on the unit.
Cleaning sprays should not be used.
If there is any moisture on the brushes when the unit is turned
on, it may cause failure of the ionizer.
5.4.1.4
Replacement Instructions
To replace the Ionizer, first remove the lower and upper access
panel.
Disconnect the quick connect. Undo the nut and bolt holding
the ionizer to cover and remove the device out of the upper
access.
Align the new ionizer with the mounting holes on the cover
assembly with the brushes facing out. Secure the ionizer to the
cover with the nuts and bolts. Attach the ionizer quick connect
to the 2-pin quick connect to the unit quick connect below the
electrical cover. Ensure they have a firm and properly sealed
connection, and that the locks have fully engaged.