cleaned, place the new
heater gasket onto the
tank mating surface. Coat
the mating surface with a
high temperature gasket
sealant.
10.
Set new heater into tank.
Aligning the bolt pattern
of the heater and tank
flanges.
11.
Replace the 4 heater
mounting bolts. Alternate to the opposite bolt while
tightening.
12.
Reconnect the power cable to the heater terminals. Be
certain to tighten the power cord junction box connector.
Replace the junction box cover and the lift-off cover panel.
D.
When complete, restart the unit.
5.3 PVT
TM
VALVE SERVICE
Remove heater
Figure 5.2D