5–7 Remote Set Point
An on-line multiple zone oven is used to dry paint. Since heat demand varies at different positions in the production line,
multiple zones with individual controls should be used to ensure a consistent temperature profile. If you order a TEC-
2500 with a retransmission unit for the master controller, and retransmit its set point to input 2 on the rest of the slave
controllers, each zone will be synchronized with the same temperature. Here is an example:
Set the following parameters in the setup menu:
For the master unit
For the slave units
FUNC=FULL
FUNC=FULL
COMM=1–5V
IN2=1–5V
AOLO=0°C
IN2L=0°C
AOHI=300°C
IN2H=300°C
PVMD=PV1
PVMD=PV1
SPMD=SP1.2
SPMD=PV2
Note:
AOHI and IN2H should be set with values higher than the set point range used.
Summary of Contents for TEC-2500
Page 2: ...NOTES...
Page 4: ...NOTES...
Page 10: ...6...
Page 11: ...7 1 5 Menu Overview...
Page 13: ...9 1 7 Parameter Description...
Page 14: ...10...
Page 16: ...12...
Page 17: ...13...
Page 18: ...14...
Page 19: ...15...
Page 20: ...16 NOTES...
Page 25: ...21 2 9 CT Heater Current Input Wiring...
Page 27: ...23 2 11 Output 1 Wiring Continued...
Page 29: ...25...
Page 31: ...27 2 14 Alarm 2 Wiring...
Page 32: ...28 2 15 RS 485...
Page 34: ...30 2 17 Analog Retransmission...
Page 35: ...31 2 18 Programming Port See figure 1 3 in section 1 3 to find the programming port location...
Page 36: ...32 NOTES...
Page 94: ...90 NOTES...
Page 96: ...92...
Page 97: ...93...
Page 98: ...94 NOTES...
Page 101: ...97 A 1 Menu Existence Conditions...
Page 102: ...98...
Page 103: ...99...
Page 104: ...100 A 2 Factory Menu Description...
Page 105: ...101 A 5 Memo Use the following table as a master copy for your settings page 1 of 2...
Page 106: ...102...