78
5–6 Ramp and Dwell
Example 1: Temperature cycling chamber
A chamber is used to test the temperature cycling effect on personal computers. An external
cycle timer is used to control the event input for switching the set point. The products under test
are required to stay at 60°C for 1 hour and -10°C for 30 minutes. The transition interval between
the high and low temperatures is required to be 5 minutes. Make the following setup:
EIFN=SP.P2
A1FN=TIMR
OUT1=REVR, relay output
OUT2=COOL, 4–20mA output
SPMD=MINR
IN1U=°C
DP1=1-DP
The circuit diagram and its temperature profile are shown below: