44
3–12 Heater Break Alarm
A current transformer (Part Number TEC99999) should be installed to detect
the heater current if a heater break alarm is required. The CT signal is sent to
input 2, and the PV2 will indicate the heater current in 0.1amp resolution. The
range of the current transformer is 0 to 50.0amp. For more detailed descriptions
about heater current monitoring, please see section 3-25.
Example:
A furnace uses two 2KW heaters connected in parallel to warm up the process.
The line voltage is 220V and the rating current for each heater is 9.09A. If we
want to detect any one heater break, set A1SP=13.0A, A1HY=0.1,
A1FN=PV2.L, A1MD=NORM, then:
Heater break alarm 1
Setup: IN2=CT
A1FN=PV2.L
A1MD=NORM
A1HY=0.1
Adjust: A1SP
Trigger level: A1SP±A1HY
Heater break alarm 2
Setup: IN2=CT
A2FN=PV2.L
A2MD=NORM
A2HY=0.1
Adjust: A2SP
Trigger level: A2SP±A2HY
Limitations:
1. Linear output can't use heater
break alarm.
2. CYC1 should use 1 second or
longer to detect heater current
reliably.
Summary of Contents for TEC-2500
Page 2: ...NOTES...
Page 4: ...NOTES...
Page 10: ...6...
Page 11: ...7 1 5 Menu Overview...
Page 13: ...9 1 7 Parameter Description...
Page 14: ...10...
Page 16: ...12...
Page 17: ...13...
Page 18: ...14...
Page 19: ...15...
Page 20: ...16 NOTES...
Page 25: ...21 2 9 CT Heater Current Input Wiring...
Page 27: ...23 2 11 Output 1 Wiring Continued...
Page 29: ...25...
Page 31: ...27 2 14 Alarm 2 Wiring...
Page 32: ...28 2 15 RS 485...
Page 34: ...30 2 17 Analog Retransmission...
Page 35: ...31 2 18 Programming Port See figure 1 3 in section 1 3 to find the programming port location...
Page 36: ...32 NOTES...
Page 94: ...90 NOTES...
Page 96: ...92...
Page 97: ...93...
Page 98: ...94 NOTES...
Page 101: ...97 A 1 Menu Existence Conditions...
Page 102: ...98...
Page 103: ...99...
Page 104: ...100 A 2 Factory Menu Description...
Page 105: ...101 A 5 Memo Use the following table as a master copy for your settings page 1 of 2...
Page 106: ...102...