8
Temco DV5200, DV6400 Series
77531
Electrical Services
Optional fan kits are equipped with a 120V, 60Hz
blower, less than 12 amps.
If electrical supply 120V is being roughed in to provide
for future installation of an optional blower kit, an
approved surface mount, steel electrical box, cover and
strain relief bushing must be installed in the fireplace
(supplied by others).
NOTE: All electric connections are to be made in
accordance with CSA Standard C22.1 - Canadian
Electrical Code part 1 or with the National Electrical
Code, ANSI/NFPA 70 (latest addition) and/or in accor-
dance with local codes.
General Venting
When locating the vent termination, the minimum vent
clearances must be observed. (Page 9, Fig. 10)
NOTE: Local codes may require different clearances.
It is recommended that the termination not be located
within 24" (305mm) of garden sheds, fences, decks,
utility buildings or other obstructions.
Do not locate termination cap where excessive snow or
ice build up may occur. Be sure to check vent termina-
tion area after snow falls and clear to prevent acciden-
tal blockage of venting system. When using snow
blowers, make sure snow is not directed towards vent
termination area.
This appliance has a "special vent system". Check with
local codes or in the absence of same, with CSA
B149.1 installation codes in Canada, or the current
National Fuel Gas Code ANSI Z223.1/NFPA 54 in the
USA, regarding special vent termination clearances.
These fireplaces are certified for use with four types of
venting systems
1. Temco 4” x 7” dia. flex vent.
2. Temco TDV series 4” x 7” dia. rigid vent.
3. Simpson Dura-Vent GS series 4” x 6
⁵⁄₈
” dia. vent.
4. Security Secure Vent series 4” x 6
⁵⁄₈
” dia. vent.
Review general venting information in this manual, and
information packed with the venting prior to starting the
installation of the fireplace.
•
Termination shall not be recessed into a wall or
siding.
•
Horizontal sections must maintain a minimum 1/4”
rise per linear foot of horizontal run.
•
Combustible clearances from any horizontal vent
pipe area must be 2” (51mm) from top of vent, and
1” (25mm) from sides and bottom.
•
Clearance to combustibles from vertical pipe sur-
face is 1” (25mm).
3" (76mm)
Min.
Gas Supply Inlet
To
Equipment Inlet
Nipple
Cap
Tee Fitting
T172
Fig. 9 Sediment trap.
1/2” Gas Supply
1/2” NPT x 1/2” Flare
Shut-off Valve
1/2” Flex Line
(from valve)
FP297a
Fig. 8 Typical gas supply installation.
IMPORTANT: Always check for gas leaks with a
soap and water solution. Do not use open flame
for leak testing.
Sediment Trap
A sediment trap shall be installed as close to the inlet
of the equipment as practicable at the time of equip-
ment installation. The sediment trap shall be either a
tee fitting with a capped nipple in the bottom outlet as
shown below or other device recognized as an effec-
tive sediment trap.
Thermostatic Fan Kit - Optional
(Part # GDVTFK)
For installation of the optional fan, please refer to the
instructions included in the fan kit.