TEMA TELECOMUNICAZIONI SRL
Doorphone AA-550
MAS-AA550-REV07EN
Page 39 of 67
9.2. Access to programming and reset address and password
To program the device, it is sufficient to use a standard browser such as Explorer, Firefox, Chrome or other. The
default address of the device is
192.168.0.10
with a mask of
255.255.255.0
, and the user / password with which to
connect are
master
/
master
. Make sure you have access to this network segment from your computer
Once logged in, it is possbile to change the administrative password for the maximum safety of your device, see
par. 10.2.
The use is very simple and intuitive, it is always visible on the left the menu for selecting the functions to be
programmed, while on the right is shown the configuration window that is currently active. Any change will be
confirmed by pressing the "Apply" or "Save" buttons. Closing the browser or changing the page without selecting
those buttons will make lost any change.
Any changes does not require a restart of the device (except for the IP address change and update the software).
In case it is necessary to program a device for which are not known network address or password, it is possible
restore the default by closing the appropriate jumper inside the device:
Just keep the bridge closed for at least 5 seconds. In this phase the LED inside the card turns on and starts
flashing after this time. After the flashing is possible to reopen the jumper and reboot the device (the restoration
was carried out properly). No configuration parameter is lost, except the network address and the password.
To restore the device to factory state, proceed with the software reset (see par. 10.1).