Alarms 

 

When an alarm is generated , the display will show an alarm icon, the code and the description of the alarm in the language selected.

 

 

If the navigation keys in the pages are pressed, the scrolling message showing the alarm indications will disappear momentarily, to 
reappear again after 30 seconds.

 

 

Alarms are automatically resetted as soon as the alarm conditions that have generated them disappear.

 

 

In the case of one or more alarms, the behaviour of the DCRL depends on the 

properties

 settings of the active alarms.

 

 

 

 
Alarm description 

 

 

ALARM 

DESCRIPTION 

A01 

Undercompensation 

In automatic mode, all the available steps are connected but the cosphi is 
still more inductive than the setpoint. 

 

A02 

Overcompensation 

In  automatic  mode,  all  the  steps  are  disconnected  but  the  cosphi  is  still 

more capacitive than the setpoint.

 

A03 

Current too low 

The current flowing in the current inputs is lower than minimum measuring 

range.

 

This condition can occour normally if the plant has no load.

 

A04 

Current too high 

The current flowing in the current inputs is lower than minimum measuring 

range.

 

A05 

Voltage too low 

The measured voltage is lower than the threshold set with P.42.

 

A06 

Voltage too high 

The measured voltage is higher than the threshold set with P.41.

 

A07 

Capacitor current  overload 

The calculated capacitor current overload is higher than threshold set with 

P.32  and  P.33.  After  the  alarm  conditions  have  disappeared,  the  alarm 

message remains shown for the following 5 min or until the user presses a 

key on the front.

 

A08 

Temperature too high 

The panel temperature is higher than threshold set with P.39.

 

A09 

No-Voltage release 

A no-voltage release has occoured on the line voltage inputs, lasting more 
than 8ms.

 

A10 

Voltage THD too high 
 

The THD of the plant voltage is higher than the threshold set with P.43.

 

A11 

Current THD too high 

The THD of the plant current is higher than the threshold set with P.44.

 

 

 

 

A12 

Maintenance requested 

The  maintenance  interval  set  with  P.45  has  elapsed.  To  reset  the  alarm 
use the command C.01 (see Command menu).

 

A13 

Step failure 

The residual power of one or more steps is lower than minimum threshold 

set with P.40.

 

 

Summary of Contents for PCRL Series

Page 1: ...Via L Da VINCI 100 50028 Tavarnelle V P FIRENZE Tel 39 055 80 71 267 118 Fax 39 055 80 71 338 E mail info telegroup it www telegroup it 1 USESER MANUAL PCRL AUTOMATIC POWER FACTOR CORRECTION SYSTEM...

Page 2: ...operation will be due to faulty connections and in particular or to a faulty positioning of the current transformer Therefore we kindly request that you observe the instructions in this manual and ri...

Page 3: ...rent specifications and power to break the circuit above the presumed short circuit current When the LCC is not known at the point of installation it may be approximated by the LCC of the transformer...

Page 4: ...f Automatic PFC System during the normal operation please be sure before open the General MCCB that all Capacitor Banks are switched off following the instruction please check MAN Mode C T must be pos...

Page 5: ...present Fix PFC System for the compensation of Transformer the C T must be installed after the Fix PFC System The figure show the connection of Automatic PFC System in case of presence of MV LV Trans...

Page 6: ...emperature sensor Advanced function current measurement capacitor overload week Power Factor storing od mx value PCRL is able to recognize se sense of current of C T In case of co generation plants is...

Page 7: ...dications Operating modes Measures Keypad lock Expandability IR programming port Parameter setting through PC Parameter setting through tablets or Smarphones Setting of parameters setup from front pan...

Page 8: ...t in temperature sensor Tool less panel mount Front keyboard MODE Key Used to select among available measurements Used also to access programming menus and keys Used to set values and to select steps...

Page 9: ...the reconnection time etc The controller displays the imminent connection or disconnection of the steps with the flashing of their identification number left The flashing can last in cases in which th...

Page 10: ...unter of the step Step hours H Hour meter of the step insertion These measures are shown only if the Step trimming function is enabled P 25 ON and the advanced password is enabled and entered Keypad l...

Page 11: ...Note the parameters shown in the table with a shaded background are essential to the operation of the system thus they represent the minimum programming required for operation BASE MENU COD DESCRIPTI...

Page 12: ...3 P 12 Step 2 function Usr P 13 Step 3 function Usr P 14 Step 4 function Usr P 15 Step 5 function Usr P 16 Step 6 function Usr P 17 Step 7 function Usr P 19 Cos phi setpoint Usr 0 95 IND 0 50 Ind 0 50...

Page 13: ...50 and 60 Hz at power on 50Hz fixed to 50 Hz 60Hz fixed to 60 Hz Var variable measured continuously and adjusted P 09 Minimum time that must elapse between the disconnection of one step and the subse...

Page 14: ...0 50 IND 0 50 CAP P 30 Disconnection sensitivity Usr sec OFF OFF 1 600 P 31 Step disconnection passing in MAN Usr OFF OFF Disabled ON Enabled P 32 Capacitor current overload alarm threshold Adv 125 OF...

Page 15: ...ands menu P 22 With P 21 enabled this is the value to specify for activating user level access See Password access chapter P 23 As for P 22 with reference to Advanced level access P 24 Number of phase...

Page 16: ...hold for generation of alarm A08 Panel temperature too high P 40 Percentage threshold of the residual power of the steps compared with the original power programmed in general menu Below this threshol...

Page 17: ...s no load A04 Current too high The current flowing in the current inputs is lower than minimum measuring range A05 Voltage too low The measured voltage is lower than the threshold set with P 42 A06 Vo...

Page 18: ...18...

Page 19: ...19...

Page 20: ...20...

Page 21: ...21...

Page 22: ...22 TELEGROUP S r l Via L Da Vinci 100 50028 Tavarnelle Val di Pesa Loc Sambuca FIRENZE ITALY Phone 39 055 80 71 267 118 Fax 39 055 80 71 338 www telegroup it...

Reviews: