Alarms
When an alarm is generated , the display will show an alarm icon, the code and the description of the alarm in the language selected.
If the navigation keys in the pages are pressed, the scrolling message showing the alarm indications will disappear momentarily, to
reappear again after 30 seconds.
Alarms are automatically resetted as soon as the alarm conditions that have generated them disappear.
In the case of one or more alarms, the behaviour of the DCRL depends on the
properties
settings of the active alarms.
Alarm description
ALARM
DESCRIPTION
A01
Undercompensation
In automatic mode, all the available steps are connected but the cosphi is
still more inductive than the setpoint.
A02
Overcompensation
In automatic mode, all the steps are disconnected but the cosphi is still
more capacitive than the setpoint.
A03
Current too low
The current flowing in the current inputs is lower than minimum measuring
range.
This condition can occour normally if the plant has no load.
A04
Current too high
The current flowing in the current inputs is lower than minimum measuring
range.
A05
Voltage too low
The measured voltage is lower than the threshold set with P.42.
A06
Voltage too high
The measured voltage is higher than the threshold set with P.41.
A07
Capacitor current overload
The calculated capacitor current overload is higher than threshold set with
P.32 and P.33. After the alarm conditions have disappeared, the alarm
message remains shown for the following 5 min or until the user presses a
key on the front.
A08
Temperature too high
The panel temperature is higher than threshold set with P.39.
A09
No-Voltage release
A no-voltage release has occoured on the line voltage inputs, lasting more
than 8ms.
A10
Voltage THD too high
The THD of the plant voltage is higher than the threshold set with P.43.
A11
Current THD too high
The THD of the plant current is higher than the threshold set with P.44.
A12
Maintenance requested
The maintenance interval set with P.45 has elapsed. To reset the alarm
use the command C.01 (see Command menu).
A13
Step failure
The residual power of one or more steps is lower than minimum threshold
set with P.40.