Parameter table
Below are listed all the programming parameters in tabular form. For each parameter are indicated the possible setting range and factory
default, as well as a brief explanation of the function of the parameter. The description of the parameter shown on the display can in
some cases be different from what is reported in the table because of the reduced number of characters available. The parameter code
can be used however as a reference.
Note: the parameters shown in the table with a shaded background are
essential
to the operation of the system, thus they represent the
minimum programming required for operation.
BASE MENU
COD
DESCRIPTION
ACC
UoM
DEF
RANGE
P.01
CT primary
Usr
A
OFF
OFF / 1...10.000
P.02
CT secondary
Usr
A
5
1 / 5
P.03
CT read phase
Usr
L3
L1
L2
L3
P.04
CT wiring polarity
Usr
Aut
Aut
Dir
Inv
P.05
Voltage read phase
Usr
L2-L3
L1-L2
L2-L3
L3-L1
L1-N
L2-N
L3-N
P.06
Smallest step power
Usr
Kvar
…
0.10 ... 10000
P.07
Rated capacitor voltage
Usr
V
….
50 ... 50000
P.08
Nominal frequency
Usr
Hz
Aut
Aut
50Hz
60Hz
Var
P.09
Reconnection time
Adv
sec
60
1 … 30000
P.10
Sensitivity
Usr
sec
60
1 … 1000