Telegroup PCRL Series User Manual Download Page 13

 

 

 

 

13 

P.01

 - The value of the primary current transformer. Example: with CT 800/5 set 800. If set to OFF, after the power-up the device will 

prompt you to set the CT and allow direct access to this parameter. 

P.02

 - Value of the secondary of the current transformers. Example: with CT 800/5 set 5. 

P.03

 – It defines on which phase the  device reads the current signal. The wiring of current inputs must match the value set for this 

parameter. Supports  all possible combinations of parameter P.05. 

P.04

 

Reading 

the 

connection 

polarity 

of 

the 

CT.  

AUT

 = Polarity is automatically detected at power up. Can only be used when working with only one CT and when the system has no 

generator 

device. 

Dir

 = Automatic detection disabled. Direct connection. 

Inv

 = Automatic detection disabled. Reverse wiring (crossover). 

P.05

 - Defines on which and on how many phases the device reads the  voltage signal. The wiring of voltage inputs must match the 

setting for this parameter. Supports  all possible combinations of parameter P.03. 

P.06

 - Value in kvar of the smallest step installed (equivalent to the step weight 1). Rated power of the capacitor bank provided at  the 

rated voltage specified in P.07 and referred to the total of the three capacitors for three-phase applications. 

P.07

 - Rated plate capacitor, which is delivered in specified power P.06. If the capacitors are used to a voltage different (lower) than 

nominal, the resulting power is automatically recalculated by the device. 

P.08

  - Working frequency of the system: 

Aut

 

automatic 

selection 

between 

50 

and 

60 

Hz 

at 

power 

on. 

50Hz

 

fixed 

to 

50 

Hz. 

60Hz

 

fixed 

to 

60 

Hz. 

Var

 = variable, measured continuously and adjusted. 

P.09

 -  Minimum time that must elapse between the disconnection of one step and the subsequent reconnection both in  MAN or AUT 

mode. During this time the number of the step on the main page is blinking. 

P.10

 - Connection sensitivity. This parameter sets the speed of reaction of the controller. With small values of P.10 the regulation is fast 

(more  accurate    around  the  setpoint  but  with  more  step  swithchings).  With  high  values  instead  we‟ll  have  slower  reactions  of  the 

regulation, with fewer switchings of the steps. The delay time of the reaction is inversely proportional to the request of steps to reach the 
setpoint: 

 

waiting 

time 

(sensitivity 

number 

of 

steps 

required). 

Example

: setting the sensitivity to 60s, if you request the insertion of one step of weight 1 are expected 60s (60/1 = 60). If instead 

serve a total of 4 steps will be expected 15s (60/4 = 15). 

P11 ... P18 

- Function of output relays 1 ... 8: 

OFF

 = Not used . 

1 .. 32

 = Weight of the step. This relay drives  a bank of cpacitors which power is n times (n = 1…32) the smallest power defined 

with parameter P.06.  

ON

 = Always on. 

NOA 

= Alarm normally de-energized. The relay is energized when any alarm with the 

Global alarm

 property  arises.  

NCA

 = Alarm normally energized. The relay is de-energized when any alarm with the 

Global alarm

 property arises. 

FAN

 = The relay controls the cooling fan.  

MAN = 

Relay is energized when device is in MAN mode. 

AUT = 

Relay is energized when device is in AUT mode. 

A01 ... A13

 = The relay is energized when the alarm specified is active. 

P.19

 

Setpoint 

(target 

value) 

of 

the 

cosphi. 

Used 

for 

standard 

applications. 

P.20

 - Language of scrolling alarm messages. 

 
 

 

 

   

 

 

 

 

 

 
 

 

 

 
 

 

 

 

 
 

 

Summary of Contents for PCRL Series

Page 1: ...Via L Da VINCI 100 50028 Tavarnelle V P FIRENZE Tel 39 055 80 71 267 118 Fax 39 055 80 71 338 E mail info telegroup it www telegroup it 1 USESER MANUAL PCRL AUTOMATIC POWER FACTOR CORRECTION SYSTEM...

Page 2: ...operation will be due to faulty connections and in particular or to a faulty positioning of the current transformer Therefore we kindly request that you observe the instructions in this manual and ri...

Page 3: ...rent specifications and power to break the circuit above the presumed short circuit current When the LCC is not known at the point of installation it may be approximated by the LCC of the transformer...

Page 4: ...f Automatic PFC System during the normal operation please be sure before open the General MCCB that all Capacitor Banks are switched off following the instruction please check MAN Mode C T must be pos...

Page 5: ...present Fix PFC System for the compensation of Transformer the C T must be installed after the Fix PFC System The figure show the connection of Automatic PFC System in case of presence of MV LV Trans...

Page 6: ...emperature sensor Advanced function current measurement capacitor overload week Power Factor storing od mx value PCRL is able to recognize se sense of current of C T In case of co generation plants is...

Page 7: ...dications Operating modes Measures Keypad lock Expandability IR programming port Parameter setting through PC Parameter setting through tablets or Smarphones Setting of parameters setup from front pan...

Page 8: ...t in temperature sensor Tool less panel mount Front keyboard MODE Key Used to select among available measurements Used also to access programming menus and keys Used to set values and to select steps...

Page 9: ...the reconnection time etc The controller displays the imminent connection or disconnection of the steps with the flashing of their identification number left The flashing can last in cases in which th...

Page 10: ...unter of the step Step hours H Hour meter of the step insertion These measures are shown only if the Step trimming function is enabled P 25 ON and the advanced password is enabled and entered Keypad l...

Page 11: ...Note the parameters shown in the table with a shaded background are essential to the operation of the system thus they represent the minimum programming required for operation BASE MENU COD DESCRIPTI...

Page 12: ...3 P 12 Step 2 function Usr P 13 Step 3 function Usr P 14 Step 4 function Usr P 15 Step 5 function Usr P 16 Step 6 function Usr P 17 Step 7 function Usr P 19 Cos phi setpoint Usr 0 95 IND 0 50 Ind 0 50...

Page 13: ...50 and 60 Hz at power on 50Hz fixed to 50 Hz 60Hz fixed to 60 Hz Var variable measured continuously and adjusted P 09 Minimum time that must elapse between the disconnection of one step and the subse...

Page 14: ...0 50 IND 0 50 CAP P 30 Disconnection sensitivity Usr sec OFF OFF 1 600 P 31 Step disconnection passing in MAN Usr OFF OFF Disabled ON Enabled P 32 Capacitor current overload alarm threshold Adv 125 OF...

Page 15: ...ands menu P 22 With P 21 enabled this is the value to specify for activating user level access See Password access chapter P 23 As for P 22 with reference to Advanced level access P 24 Number of phase...

Page 16: ...hold for generation of alarm A08 Panel temperature too high P 40 Percentage threshold of the residual power of the steps compared with the original power programmed in general menu Below this threshol...

Page 17: ...s no load A04 Current too high The current flowing in the current inputs is lower than minimum measuring range A05 Voltage too low The measured voltage is lower than the threshold set with P 42 A06 Vo...

Page 18: ...18...

Page 19: ...19...

Page 20: ...20...

Page 21: ...21...

Page 22: ...22 TELEGROUP S r l Via L Da Vinci 100 50028 Tavarnelle Val di Pesa Loc Sambuca FIRENZE ITALY Phone 39 055 80 71 267 118 Fax 39 055 80 71 338 www telegroup it...

Reviews: