14
ADVANCED MENU
COD
DESCRIPTION
ACC
UoM
DEF
RANGE
P.21
Password enable
Adv
OFF
OFF
ON
P.22
User password
Usr
001
0-999
P.23
Advanced password
Adv
002
0-999
P.24
Wiring type
Usr
3PH
3PH three-phase
1PH single-phase
P.25
Step trimming
Usr
OFF
ON Enabled
OFF Disabled
P.26
Setpoint cle
Usr
0.00
0 – 0.10
P.27
Setpoint clearance -
Usr
0.00
0 – 0.10
P.28
Step insertion mode
Usr
STD
STD Standard
Lin Linear
P.29
Cogeneration cos
setpoint
Usr
OFF
OFF /
0.50 IND – 0.50 CAP
P.30
Disconnection
sensitivity
Usr
sec
OFF
OFF / 1 – 600
P.31
Step disconnection passing in MAN
Usr
OFF
OFF Disabled
ON Enabled
P.32
Capacitor current overload alarm threshold
Adv
%
125
OFF / 100...150
P.33
Capacitor overload immediate disconnection
threshold
Adv
%
150
OFF / 100.. 200
P.34
VT primary
Usr
V
OFF
OFF / 50-50000
P.35
VT secondary
Usr
V
100
50-500
P.36
Temperature UoM
Usr
°C
°C °Celsius
°F °Fahrenheit
P.37
Fan start temperature
Adv
°
35
0…212
P.38
Fan stop temperature
Adv
°
55
0…212
P.39
Temperature alarm threshold
Adv
°
50
0…212
P.40
Step failure alarm threshold
Adv
%
OFF
OFF / 25…100
P.41
Maximum voltage alarm threshold
Adv
%
120
OFF / 90...150