![Telect 009-8005-1404 Installation Manual Download Page 14](http://html.mh-extra.com/html/telect/009-8005-1404/009-8005-1404_installation-manual_1080084014.webp)
Dual 200A 4/5 TPA/GMT Fuse Alarm Panel
with Bay Alarms
Installation Guide
14
© Telect, Inc. All rights reserved. 126152-5 5.3.17
509.926.6000 :: www.telect.com
1.6 Schematic Drawing
C
ACTIVATE
NOTE 1: NC & NO Alarm switches are shown in
normal operating state (without failures or alarms).
NOTE 2: Layout of rear-access terminals in this schematic does not
represent the physical arrangement on the rear of the panel.
NOTE 3: Operational power for the monitoring and activation of all fuse,
bay, and power alarms is obtained from combining Input A and
Input B sources. Either Input A or Input B is individually sufficient
for complete operation of all alarm circuits.
NO
NC
C
PWR
ALARM
FUSE
ALARM
BAY ALARMS
CONTACTS ACTIVATE
NO
NO
NC
C
NC
NC NO
C
C
A
A
R
R
REMOVEABLE ALARM CARD
BATT
RTN
RTN
BATT
1
2
3
4
1
2
3
4
1
2
19
20
1
2
19
20
1
2
19
20
1
2
19
20
1
2
3
4
1
2
3
4
TPA OUTPUT
BATT A
INPUT A
TPA OUTPUT
RTN A
GMT OUTPUT
BATT A
GMT OUTPUT
RTN A
GMT OUTPUT
RTN B
GMT OUTPUT
BATT B
TPA OUTPUT
RTN B
TPA OUTPUT
BATT B
INPUT B
POWER ON A
POWER ON B
TPA/GMT FUSE ALARM
CR
MJ
MN
TPA FUSE
HOLDER
LEDS
TPA FUSE
HOLDER
LEDS
C GND
CRITICAL
MAJOR
MINOR
BAY
ALARM
GMT Amp Size Color Code
¼ Violet (VIO)
½ Red (RED)
¾ Brown (BRN)
1 Gray (GRY)
1 1/3 White (WHT)
1 ½ White/Yellow (WHT/YEL)
2 Orange (ORN)
3 Blue (BLU)
4 White/Brown (WHT/BRN)
5 Green (GRN)
7 ½ Black/White (BLK/WHT
10 Red/White (RED/WHT)
12 Yellow/Green (YEL/GRN)
15 Red/Blue (RED/BLU)
CRITICAL BAY
BREAKER
MINOR BAY
MAJOR BAY
NC
NO
RTN
ACTIVATE
C
ALARM
NO
NC
RTN
ACTIVATE
C
ALARM
NO
NC
C
ALARM
AUDIBLE
ALARM
NO
NC
NC
NO
C
C
VISUAL
ALARM
POWER
NO
RTN
NC