Dual 200A 4/5 TPA/GMT Fuse Alarm Panel
with Bay Alarms
Installation Guide
12
© Telect, Inc. All rights reserved. 126152-5 5.3.17
509.926.6000 :: www.telect.com
35. If desired, connect the remote external audio/visual alarm indicator wires (solid or tinned wires,
#26 to #20 AWG) to the
PWR ALARM
and
FUSE ALARM
terminals.
36. Test the
CRIT
(critical),
MAJ
(major),
MIN
(minor) external alarms on the rear of the panel.
Without any alarm conditions:
•
Expect the
CRIT
,
MAJ
and
MIN
LEDs to be off
•
Expect continuity (0
Ω
) between
C
and
NC
of each set of terminals
•
Expect an open circuit (
∞Ω
) between
C
and
NO
of each set of terminals
37. Jumper
A
(activate) terminal to corresponding
R
(return) terminal of
CRIT
,
MAJ
and
MIN
.
When each pair of
A
and
R
terminals are jumpered:
•
Expect
CRIT
and
MAJ
LEDs to turn red and
MIN
to turn amber
•
Expect an open circuit (
∞Ω
) between
C
and
NC
of each set of terminals when the relays are activated
•
Expect continuity (0
Ω
) between Terminals
C
and
NO
when relays are activated
38. Connect
A
and
R
pairs to appropriate, corresponding
“dry” contacts of equipment relays powered by this
breaker panel.
39. Connect wiring (#26 to #20 AWG) to external alarm
switch contacts (Terminals
NO
,
NC
and
C
) of
CRIT
,
MAJ
and
MIN
.
40. Carefully re-install the rear cover.
41. Record TPA and GMT output destinations on the
pull-out designation card below front panel LEDs,
shown in Figure 13.
42. Turn on equipment loads one at a time to verify
proper operation of loads.
Figure 13
– Designation Card