Telect, Inc. • USA +1.509.926.6000 • 52.33.3836.37.52
www.telect.com • © 2010 Telect, Inc., All Rights Reserved, 118677-4 A0
Page 7
(
∞Ω
)
between Terminals C and NO on the rear of the demarcation panel. Also, the
corresponding ALARM CUTOFF LEDs should be OFF.
If a breaker trips with its corresponding
ALARM CUTOFF
switch in the
NORMAL (up)
position, expect continuity (0
Ω
) between Terminals C and NO. Thereafter, if the
corresponding
ALARM CUTOFF
is switched to
SERVICE (down)
, expect the corresponding
ALARM
CUTOFF LED to light with an open circuit (
∞Ω
) again obtained between
corresponding Terminals C and NO.
19. Wire-wrap alarm pins with solid #26 to #22 AWG.
20. Make sure the output devices — devices fed from the outputs of this demarcation panel —
are off.
21. Switch on each circuit breaker, one at a time, and check the voltage and polarity at the output
terminals and equipment ends. Verify the normal operating conditions outlined in the preced-
ing Note.
This procedure is complete.