background image

SI-125 Power Amplifier Manual 

 

Unit Description 

The various amplifier parts are: 

 

Figure 1: SI-125 Front View 

A.

 

VU METER:

 The 30 dB digital VU meter shows 0 dB when the amplifier is operating at 

its rated output. Exceeding the rated output will cause the output to be clipped, which will 
be indicated by the illumination of the CLIP light. 

B.

 

HIGH TEMPERATURE Light:

 If the internal temperature of the amplifier exceeds its 

normal operating limit, the High Temperature light will illuminate and the output level 
will begin to be reduced. The amplifier will continue to operate at a reduced output level 
until the temperature returns to an acceptable level. If the High Temperature light 
illuminates, see the Troubleshooting section. 

C.

 

CURRENT OVERLOAD Light:

 If the current output of the amplifier exceeds its 

maximum power output, the Current Overload light will illuminate and the output level 
will begin to be reduced. The amplifier will continue to operate with the current limiting 
circuit reducing the output power. If the Current Overload light illuminates, see the 
Troubleshooting section. 

D.

 

GAIN Control:

 The gain of the amplifier can be adjusted using this potentiometer. The 

potentiometer is concealed behind a snap-on cover. The cover can be snapped off when 
the level needs to be adjusted but should be replaced to prevent unintended tampering. 
The amplifier gain is set by both this control and the sensitivity Input Level switch on the 
back of the amplifier. 

E.

 

POWER Switch:

 Turns the amplifier on and off. The switch will illuminate when the 

amplifier is turned on. 

 

Figure 2: SI-125 Rear View 

Summary of Contents for SI-125

Page 1: ... from overloading The amplifier also has circuitry to protect it from overheating The SI 125 Power Amplifier can have optional modules installed for additional functionality The PA AM Power Amplifier Attenuator Module allows the amplifier to support a 25 V input signal The PA MM Power Amplifier Monitor Module activates a relay under normal amplifier operation The PA PM Power Amplifier Paging Modul...

Page 2: ...ee the Troubleshooting section C CURRENT OVERLOAD Light If the current output of the amplifier exceeds its maximum power output the Current Overload light will illuminate and the output level will begin to be reduced The amplifier will continue to operate with the current limiting circuit reducing the output power If the Current Overload light illuminates see the Troubleshooting section D GAIN Con...

Page 3: ...overs the slot Please note that the accessory modules are not user installable They must be factory installed and ordered with the amplifier Do not remove any modules or the cover plate J INPUT LEVEL Switch The Input Level switch selects the range of the input level This switch works in conjunction with the GAIN Control on the front of the amplifier The Input Level switch should be set to match th...

Page 4: ...urn on either when there is excessive signal level on the input or when there is hard clipping present on the output The CLIP light will not turn on when the output level is clipped due to current overload Installation Before installing an SI 125 Power Amplifier carefully inspect the device for any damage that may have occurred during shipping The shipping package should contain only the Power Amp...

Page 5: ...own in Figure 5 Figure 5 Input Connections To reduce the incidence of ground loop hum oscillation or interference from other audio sources 1 Use a shielded cable for input wiring The shield must be grounded at one end of the cable only not both 2 Regardless of what type of input signal is supplied to the amplifier balanced or single ended the GND terminal should not be connected to the common term...

Page 6: ...pplications there is often a privacy switch in the room When this switch is activated it grounds one side of the room speaker line through a transformer Make sure that all these privacy switches are not in the Privacy position when measuring line impedance to ground These switches do not adversely affect the operation of the amplifier When measuring load impedance on a Telecor installation disconn...

Page 7: ...registers a signal when no signal should be present The amplifier may be oscillating possibly at a very high frequency This may be caused by running input and output wires close together grounding the input or incorrect grounding of the shield The Current Overload light illuminates or flashes This indicates that the amplifier is being overloaded Check the total speaker load on the amplifier Also c...

Page 8: ...ls on input and output Mas Con connectors are used with optional modules Controls Power Switch Illuminated GAIN Control Low Cut Switch Input Level Switch 1 V 100 mV Indicators Clip High Temperature VU Meter and Current Overload Protection Foldback current limiting Over temperature protection Primary circuit fused at 3 5 A Temperature Range 10 C to 35 C 14 F to 95 F Power Consumption AC 120 V 60 Hz...

Page 9: ...ansportation labor charges indemnity etc are not covered by this warranty and no responsibility for same will be assumed by us Our liability does not extend to consequential damage AUTHORIZED REPAIR STATION All participating Distributors and Dealers are authorized to accept Telecor products for return to us for repair or replacement or customers may return goods to us directly providing that retur...

Reviews: