13
3.1 - Activation/Deactivation of the Memory of the last value of the Load
Activated:
commanding the load with a short pulse, it will turn-on with the same values it had before the last
OFF command.
Deactivated:
commanding the load with a short pulse, it will turn-on always at 100%.
1- Adjust the minimum desired level of the load.
2- Press
P2 + P3
and hold them down.
The buzzer makes fast beeps.
To reset the level to the default value, press
again
P2 + P3
and hold them down.
The buzzer makes 3 slow beeps.
3.2 - To set the minimum level for the Load
3.3 - Fine adjustment for load identification (see load setting at page 3)
Press P1+P3 once
and hold them down
Press P2+P3 once
and hold them down
Press P4
to select the output
Press P4
to select the output
Press P1+P2+P3 once
and hold them down
Press P4
to select the output
1- Select the output using
P4
2- Press
P1 + P3
and hold them down.
- Fast beeps: the function is
activated
.
- 3 slow beeps: the function is
deactivated
.
This function allows to set the minimum level for dimming the load, only in case of
resistive loads
(DIP2 = ON).
This function modifies the settings of the control unit in the automatic identification of the load type.
It’s allowed only if the dip-switch 2, 3 and 4 are OFF (configuration corresponding to automatic
identification).
1- Select the output using
P4
2- Press
P1 + P2 + P3
and hold them down.
- Fast beeps: the function is
activated
.
- 3 slow beeps: the function is
deactivated
.
NOTE
: after a power failure, the dimmer will turn on the loads at the same status before it.
ON
1 2 3 4
ON
1 2 3 4