3.3 Exclusion of safety edge in the last 5 cm of the closure 

In case of uneven floors, it could be necessary deactivating the safety edge in the last part of the closure (not 
more than 5 cm to comply with the standards) in order to avoid any accidental activation of the safety edge.
This procedure must be performed by qualified installer only, who will take charge of its correct application.

WARNING: this procedure can be used only for doors which require more than 10 seconds each manoeuvre. The 
exclusion of the safety edge is applied only if the closure starts from the upper limit switch and it is not stopped.

Open the door 

completely 

by means of 

a memorized transmitter. The buzzer emits 
a long beep when the upper limit switch is 
reached. Put on the floor, exactely under the 
door, a sturdy object not more than 5 cm high.
Close the door (in 

hold-to-run

 mode), with 

no interruption

. The door will stop at the 

obstacle and the control unit will make a 
long beep. Open the door 

completely 

and 

remove the object. Close the door to verify the 
correct application of the procedure.

hold-to-run

DEACTIVATION

Press P1 button 

ten times

 and keep it 

pressed for 

5 seconds

. The buzzer emits 

3 beeps.

WITHIN 30 SEC. FROM POWER-ON

(       5 s)

keep it 

pressed

(       5 s)

keep it 

pressed

Press P1 button 

eleven times

 and keep it 

pressed for 

5 seconds

. The buzzer emits 5 

beeps.

10x

11x

WITHIN 30 SEC. FROM POWER-ON

P1

P1

max. 5 cm

X

Summary of Contents for TVNRG868A01

Page 1: ...Product TVNRG868A01 Doc TEMP Date 07 09 2018 Control system for garage doors Installer s instruction manual...

Page 2: ...emorization 4 2 Double channel memorization 4 3 Single channel Courtesy light ON OFF 4 4 Four channels memorization 4 5 Remote memorization of the first transmitter 4 6 Remote memorization of further...

Page 3: ...n with shock sensor TVSSH868A01 and BST25S and integrated speaker CONNECTIONS FUNCTIONING Wired inputs for safety edge both resistive 8K2 and infrared Wired inputs for command push button and emergenc...

Page 4: ...and transmitter 4 Safety edge wireless transmitter 1 4 2 3 6 8 1 4 2 3 1 NRG control unit 2 Tubular motor 240Vac 3 Hand transmitter 4 Safety edge wireless transmitter 5 Alarm wireless sensor 6 Wireles...

Page 5: ...5 2 1 MOUNTING THE PRODUCT BOX DIMENSIONS OPENING THE COVER 85 mm 145 mm 290 mm 80 mm 95 mm 120 mm MOUNTING SIDE...

Page 6: ...BK2 1 2 BOTTOM SLAT TRANSMITTER SLAVE Powered by led dip switches B1 B2 3 4 5 6 BK2 2 x 3 6V Lithium batteries 2 x 1 5V Type AA batteries 1 B K 2 2 3 4 5 6 B K 2 G re e n B ro w n W h it e 1 2 1 B K 2...

Page 7: ...n 17 Infrared 8K2 safety edge input green 18 Infrared 8K2 safety edge input white 19 Push button common COM 20 Push button step by step N O 21 Emergency STOP push button N C 22 Emergency STOP push but...

Page 8: ...2V 24V N O COM N C 0V 12V 24V 12 13 14 15 16 17 18 19 20 21 22 23 12 13 14 15 16 17 18 19 20 21 22 23 RX FTC010 TX FTC010 REFLEX COM N C 12Vdc 15Vdc 12 13 14 15 16 17 18 19 20 21 22 23 8K2 If no wired...

Page 9: ...TER for 2 seconds L1 and L2 led will flash 2 Push the button of the bottom slat transmitter SLAVE for 2 seconds Its led will flash In case of correct memorization L1 will costantly flash Step 4 functi...

Page 10: ...for 3s or wait time out time of 90s from the last button pression The buzzer makes one beep P2 P1 keep pressed 3 s ON 1 2 3 ON 1 2 3 ON This function is possible ONLY within 30 seconds from the power...

Page 11: ...it is not stopped Open the door completely by means of a memorized transmitter The buzzer emits a long beep when the upper limit switch is reached Put on the floor exactely under the door a sturdy ob...

Page 12: ...emorize Memorization of two buttons of any transmitter in one step with function OPEN STOP CLOSE STOP Press P1 twice and keep it pressed The buzzer emits a continuous sound Press any button of the pai...

Page 13: ...s 5 s continuous sound intermittent sound continuous sound memorized new memorized OPEN CLOSE STOP LIGHT ON LIGHT OFF 4 5 Remote memorization of the first transmitter OPEN STOP CLOSE STOP Press P1 six...

Page 14: ...itches see at side Sending any opening or closing door command will stop the alarm Warning optional speaker must be connected O N 2 1 Press P1 eight times and keep it pressed The buzzer emits a contin...

Page 15: ...is successfully completed the buzzer emits a continuous sound continuous sound keep it pressed intermittent sound P2 button to delete 4x Press 3 times P3 button of a memorized transmitter and keep it...

Page 16: ...ed P3 memorized P3 memorized P3 memorized keep it pressed 2 s The procedure can be executed only within 30 seconds from power on ON This procedure configures the time of activation of the courtesy lig...

Page 17: ...tivates or deactivates the motor torque control The control unit will costantly check the level of current required by the motor during the movement in order to detect any anomaly in the normal operat...

Page 18: ...fety devices have to be in conformity with EN12978 The installation of the control unit has to be done by fixing the box vertically with the cable glands downwards The product is in conformity with th...

Page 19: ...plug check all the pins The radio card master must be paired with the bottom slat transmitter slave Bottom slat transmitter checks Check type polarity and charge level of the batteries Check functiona...

Page 20: ...closure starting from the upper limit switch in order to be effective The door can be operated but the safety systems don t activate Check the motor direction If wrong swap brown and black motor wires...

Reviews: