3.3 Exclusion of safety edge in the last 5 cm of the closure
In case of uneven floors, it could be necessary deactivating the safety edge in the last part of the closure (not
more than 5 cm to comply with the standards) in order to avoid any accidental activation of the safety edge.
This procedure must be performed by qualified installer only, who will take charge of its correct application.
WARNING: this procedure can be used only for doors which require more than 10 seconds each manoeuvre. The
exclusion of the safety edge is applied only if the closure starts from the upper limit switch and it is not stopped.
Open the door
completely
by means of
a memorized transmitter. The buzzer emits
a long beep when the upper limit switch is
reached. Put on the floor, exactely under the
door, a sturdy object not more than 5 cm high.
Close the door (in
hold-to-run
mode), with
no interruption
. The door will stop at the
obstacle and the control unit will make a
long beep. Open the door
completely
and
remove the object. Close the door to verify the
correct application of the procedure.
hold-to-run
DEACTIVATION
Press P1 button
ten times
and keep it
pressed for
5 seconds
. The buzzer emits
3 beeps.
WITHIN 30 SEC. FROM POWER-ON
( 5 s)
keep it
pressed
( 5 s)
keep it
pressed
Press P1 button
eleven times
and keep it
pressed for
5 seconds
. The buzzer emits 5
beeps.
10x
11x
WITHIN 30 SEC. FROM POWER-ON
P1
P1
max. 5 cm
X