background image

 

12

 

2.2  Calibration Notes :- 

 

1. 

When using a standard Fume Cupboard with Vertical Sliding sashes  open the sash 
to the normal max safe working height for the Low Air sample. 

 

2. 

For the Higher Air sample close the sash to approx 50% of the opening used for the 
Lower Air sample. If the Higher air sample value is too close to the Lower Air sample 
the alarm will detect this and ask you to repeat with a higher value.( The min 
difference between the Low & High air samples is set to 0.3 m/sec )To do this close 
the sash a little more and repeat the sample. Avoid closing the sash below 150mm.

 

 

3. 

The face velocity readings on the open sash may vary at different points on the 
measuring grid by up to 0.1m/sec. This is quite acceptable in terms of the fume 
cupboard performance so long as no individual point is below the designated Low Air 
alarm point .The figure entered for the calibration point can be taken as the average 
value of all the measuring grid readings or could be taken as the individual lowest 
point on the grid. For most fume cupboards this low point is on the bottom row in the 
centre and is a convenient position to measure and for future reference when 
checking the alarm during annual maintenance.

 

 

4. 

Take time when measuring the face velocities for the calibration procedure to allow 
for the velocities across the open sash to stabilise. If the velocities are changing or 
are turbulent during the sampling period the alarm will detect this and ask you to 
repeat the sample.

 

 

5. 

When using a Fume Cupboard with Horizontal Sliding sashes  open the sashes to the 
normal max safe working opening for the Low Air sample.

 

 

6. 

When calibrating or re-calibrating the alarm it is important to ensure that the ‘Vent kit’ 
is connected to the SM6 sensor on the fume cupboard. If the vent kit is not connected 
the sensor will not ‘see’ a change in the airflow during the calibration procedure and 
will show “Sensor Difference too low  - Check sensor”.

 

This only applies during the 

calibration mode. If in normal running after successful calibration the vent kit 
becomes disconnected the air flow across the sensor will fall and the alarm will go 
into the AIR FAIL condition.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for AFA1000 / 1 - Mk2

Page 1: ...Digital display 3 Relay inputs 3 Relay outputs Com port Used for alarm indication and monitoring on Fume Cupboards Model AFA1000 2 Mk2 Digital display 3 Relay inputs 3 Relay outputs 3 Pushbuttons Com...

Page 2: ...Passwords in the Main Menu or alternatively use a Laptop connected to the Com port and the Upload Download software provided Velocity Bar Graph or Alarm Time Line Velocity display m sec or fpm Control...

Page 3: ...R2 R3 SENSOR SOCKET 0 10V ECON OUTPUT 15V DC POWER SUPPLY INPUT 0 10V AUX OUTPUT s w Sash Proximity switch OUTPUT RELAYS COMMS PORT RELAY INPUTS INPUT 1 INPUT 2 INPUT 3 Bn Bk Bl Sash Micro switch REF...

Page 4: ...representing events that have occurred during the past hour The alternative to the event time line is a dynamic bar graph representing the face velocity The display shows a Horn icon with line through...

Page 5: ...the calibration and configuration menu or to select options or values External Connections the alarm unit will have the following connection points Input 1 volt free relay input configurable for norma...

Page 6: ...a Fan stop start button for the fume cupboard extract fan or as Night Set back Override Pushbutton 2 This button can be configured to act as a Lights ON OFF or UV Lights On OFF for the fume cupboard o...

Page 7: ...e configuration of the alarm NOTE If you enter the Calibration or Configure Menu by accident press the buttons at the same time to escape back to the Main Menu The menus and sub menus are in plain lan...

Page 8: ...ime the Low air alarm resets automatically High airflow If configured High Air toggles on off with display Audible alarm sounds can be muted via Enter pushbutton Audible alarm Mute When the audible al...

Page 9: ...ctivated Night Set Back Icon is displayed Red LED on Flashing Reduced Low air alarm if configured Audible alarm muted Mute Icon shown on display External alarm When input configured as External alarm...

Page 10: ...isables Night setback operation in Override On condition Note In the On condition the unit ignores any Night Set back input signals and remains in this condition until Off is selected Pushbutton 2 Pum...

Page 11: ...setup press ENTER to continue and in the Main Menu use the buttons on the alarm facia select SETUP and then press the ENTER button 7 In the Setup Menu select CALIBRATION and press the ENTER button 8...

Page 12: ...individual lowest point on the grid For most fume cupboards this low point is on the bottom row in the centre and is a convenient position to measure and for future reference when checking the alarm...

Page 13: ...ensor Hole for Vent Tube SM6 Sensor Dimensions Rear view SM6 Sensor Panel Cutout Dimensions Front view NOT TO SCALE 2 x Holes for self tapping fixing screw 4mm Fixing Hole provided on SM6 sensor Panel...

Page 14: ...ng position using a flexible tube With a single skin side wall it is possible to fix the sensor on the outside of the fume cupboard and connect directly to the inner chamber in the ideal position This...

Page 15: ...SM6 Airflow Sensor R1 R2 R3 SENSOR SOCKET 0 10V ECON OUTPUT 15V DC POWER SUPPLY INPUT 0 10V AUX OUTPUT s w Sash Proximity switch OUTPUT RELAYS COMMS PORT RELAY INPUTS INPUT 1 INPUT 2 INPUT 3 Bn Bk Bl...

Page 16: ...oximity switch Optional SM6 Airflow Sensor R1 R2 R3 SENSOR SOCKET 0 10V ECON OUTPUT 15V DC POWER SUPPLY INPUT 0 10V AUX OUTPUT s w Sash Proximity switch OUTPUT RELAYS COMMS PORT RELAY INPUTS INPUT 1 I...

Page 17: ...F all other warranties and is subject to the conditions and LIMITATIONS stated herein NO OTHER EXPRESS OR IMPLIED WARRANTY OF FITNESS FOR PARTICULAR PURPOSE OR MERCHANTABILITY IS MADE THE EXCLUSIVE RE...

Reviews: