Ensure that hot air is being removed from the generator room with a flexible duct connection.
The cooling air flow required can be provided by calculating the dimensions of the air inlet and outlet louvers.
Windows area of the room should not be less than the area of radiator matrix. If possible, the air inlet and outlet
area should be %150 of the radiator matrix.
In order for the protection of air channels, stationary or moving shutter systems can be built within these windows.
For an automatic generator set; an automatically moving shutter system which is designed to open automatically
when the engine starts, is the best solution for this purpose. However, manually opened moving shutters can be
acceptable in some manual mode generator set applications.
The layout drawing below, is just showing a typical generator set installation.
It is for guidance purpose only. Every generator set installation case or design
must be studied carefully and individually.