TTM 01-G Manual / October 2018
9
ALM: Alarm Output
The alarm output is a type “A” (normally open) dry contact type. Additionally, it is a high voltage isolated contact
capable of switching up to 300 V at 100 mA.
Note:
The “Normally-Open” (NO) descriptor refers to the de-energized state of the relay.
The TTM 01-G operates with the alarm relays energized during normal operation, and de-energized in the alarm
state. It follows that, in the event of all power to the TTM 01-G being lost, the alarm relay defaults to the “alarm”
state (open contact). The “+” and “-” symbols are included for reference purposes only, as the alarm contacts are
not polarized.
The “ALM” output is a synchronization fail alarm. This alarm is active (contact open) when the unit is not
synchronized and is not in the holdover state.
OPT: Optional Output
The TTM 01-G has a slot for one I/O card, to allow a variety of user interfaces. Each card is limited to one
additional port with at least 3 kV isolation from the rest of the system to avoid current loops. Refer to Table 5
for the list of orderable options.