background image

37 of 48

© 2011  

D 406 - 12/11

Use the SWITCHOVR setting in the Adjust Menu to select the 
proper operation of the O/B terminal.

Rc1 Y1

406

O/B

R

Y

B

Backup Delay

 -----------------------------------

 -----------------------------------

To allow the heat pump to operate at full output for some 
adjustable amount of time before the backup heat source is 
allowed to come on, a backup delay is used. Use the BKUP 
DLY setting in the Adjust Menu to set an appropriate backup 
delay time. When OVR is selected, the backup source will 
not be called upon for heat unless the MODE is set to BKUP 
or the heat pump is locked out on high return temperature or 
outdoor temperature. This ensures that the heat pump is being 
used to its full potential during heating.

HP Return Water Temperature Limit

 -------------

 -------------

At certain return water temperatures, it may not be economi-
cal to keep the heat pump operating due to low coefficient of 
performance (COP). This will occur in heating when the return 
water temperature is too high, and in cooling when the return 
water temperature is too low. These values will differ from 
one heat pump to another. Use the HP RETURN MAX and HP 
RETURN MIN

 settings in the Adjust Menu to set the heat pump 

return water temperature limits for heating and cooling.

DHW Operation

Section F

A DHW Call is required in order for the control to provide heat 
to a DHW tank. Once the control registers a DHW Call, it will 
display the DHW icon in the “Calls” box of the status field. 
This can be done in one of three ways:

DHW Calls

 

---------------------------------------

 

---------------------------------------

DHW Tank Aquastat

If a DHW aquastat (mechanical switch) is used to apply a DHW 
Call, the tank is heated to the aquastat temperature setting. 
A dry contact is applied across the DHW Call terminals on 
the House Control. 

Use the DHW XCHG setting in the Adjust Menu to set the 
boiler target required to satisfy this type of DHW call.

DHW Tank Sensor

A DHW tank sensor provides superior temperature control 
of the tank compared to an aquastat. The House Control 
automatically detects whether a DHW sensor is installed. 

Status Field

Cooling

During cool weather, cooling of the rooms is typically no longer 
required. The control shuts down the heat pump when the 
outdoor temperature falls below an adjustable temperature to 
prevent energy waste from unnecessary heat pump operation 
during cooling. Use the Y COOLING CWSD setting in the Adjust 
Menu to set the low outdoor air temperature limit for cooling.

Note: 

the CWSD icon is displayed in status field of the display 

when the outdoor temperature falls below either the BALNCE 
PT or Y COOLING CWSD settings in the Adjust Menu.

Status Field

B = Heat pump normally operates in cool mode. Energize 
B to operate the heat pump in heat mode

Outdoor Air Temperature Limit

 ------------------

 ------------------

Heating - For AIR Source Heat Pumps Only

At low outdoor air temperatures, it may not be economical to 
keep an air source heat pump operating during heating due to 
low COP. These values will differ from one air source heat pump 
to another. Use the BALNCE PT setting in the Adjust Menu to 
set the low outdoor air temperature limit for heating.

Heat Pump Differential

 ---------------------------

 ---------------------------

The differential operates by closing the Y1 contact when 
the tank water temperature is 1/2 of the differential below 
the tank target. As the tank temperature reaches 1/2 of 
the differential above the tank target, the Y1 contact is 
opened, turning the heat pump off.

+1/2 Differential

- 1/2 Differential

Tank Target

H.P. On

H.P. Off

DHW Mode

 --------------------------------------

 --------------------------------------

The control has five different settings available for DHW Mode 
that affect pump operation. The required DHW Mode setting 
will depend on the piping arrangement of the DHW tank and 
whether or not priority for the DHW tank is necessary. DHW 
Priority stops or limits the delivery of heat to the building heating 
system while the DHW tank calls for heat. This allows for quick 
DHW tank temperature recovery.

The upper limit of the DHW temperature is set by the DHW 
OCC setting in the Adjust Menu. The DHW tank differential 
is fixed to 6°F (3°C).

When using a DHW Tank Sensor, the boiler target is set 
to the DHW OCC setting plus 40°F (22°C).

tekmarNet

®

 Setpoint Control with Sensor

A DHW Call is provided through the tekmarNet

®

 system. This 

can be done through the tN4 Boil Expansion terminals with 
a tekmarNet

®

 setpoint device such as a Setpoint Control 161 

or 162.

When using a tekmarNet

®

 Setpoint Control, the boiler 

target is set to the devices Exchange Supply setting.

Summary of Contents for tekmarNet 2 House Control 406

Page 1: ...rts CSA C US Certified for use in USA and Canada Introduction The tN2 House Control 406 is designed to operate the equipment in a 2 pipe single tank hydronic heating and cooling system It operates two...

Page 2: ...tended for use as a primary limit control Other controls that are intended and certified as safety limits must be placed into the control circuit Do not attempt to service the control Refer to qualifi...

Page 3: ...llow proper wiring practices building and electrical codes for your jurisdiction Each cable must be pulled from the equipment to the electrical junction box It is recommended to label each cable for e...

Page 4: ...ix System P DHW Pump Transfer Pum Variable Speed Pump Boil System Pump Figure 1 Connect Ground Wires Figure 2 Connect Neutral Wires for Power Source 1 Pull two conductor 18 AWG LVT cable up to 500 fee...

Page 5: ...ly tucked inside the electrical box Using 2 of the 4 holes in the back of the enclosure securely fasten it to the junction box extension ring with 2 10 screws as shown in Figure 7 Install The Enclosur...

Page 6: ...add additional Boil or Mix water temperature zones to the system install a tekmarNet Wiring Center Connect the Boil Mix terminals tN4 and C on the 406 to the corresponding tN4 and C Expansion termina...

Page 7: ...heat pump Connect the Rc2 and Y2 terminals on the 406 to the R and Y2 terminals on the heat pump Connect the Rc1 and O B terminal on the 406 to the R and O or B terminal on the heat pump Wiring the A...

Page 8: ...vided in the enclosure The other side of the terminal block is used to connect wires from the control A good quality test meter capable of measuring up to 5 000 k 1 k 1000 is required to measure the s...

Page 9: ...peed setting Step 7 The mix system pump turns on for 10 seconds Step 8 The tank system pump turns on for 10 seconds Step 9 The O B contacts are closed for 10 seconds Step 10 The HP loop pump turns on...

Page 10: ...easure between 103 5 V ac and 126 5 V ac Testing the Boiler Modulating Output This test applies for modulating boilers only Active the User Test sequence and pause at Step 18 by pressing the Item butt...

Page 11: ...Menu An electric element in the system storage tank is switched on through an isolation relay with the backup relay on the 406 to provide backup heat to maintain the Tank Sensor S4 at its target temp...

Page 12: ...Com Boil HPRt Out Com Zone 1 H8009B Zone 2 Zone 3 Zone 4 tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Rc1 Y1 O B Sensors No Power No Power Call Call Mix DHW tN4 tN4 C C Mod dc mA Boil Mix Tank Rc2 Y2 Setpoint DHW...

Page 13: ...nter 314 An electric boiler supplies backup heat using the Backup relay and the Transfer Pump P7 By setting HP LOOP to ON the HP Loop Pump P2 will operate whenever there is a call on the tank or mix b...

Page 14: ...N 3 4 6 5 7 2 1 8 O C Y R O C Y R Transfer 314 Menu House Control 406 Item Tank Com Boil HPRt Out Com Zone 1 H8009B Zone 2 Zone 3 Zone 4 tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Rc1 Y1 O B Sensors No Power No...

Page 15: ...pump starts adding heat to the storage tank use the backup delay setting in the adjust menu This ensures the heat pump is being used to its full potential before backup is allowed Placing the Transfer...

Page 16: ...ack red black black black 313 Menu House Control 406 Item Tank Com Boil HPRt Out Com Zone 1 H8009B Zone 2 Zone 3 Zone 4 tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Rc1 Y1 O B Sensors No Power No Power Call Call M...

Page 17: ...sed to its full potential before backup is allowed A non condensing boiler may be used since P1 provides boiler return protection preventing flue gas condensation Tank zones can have fan coils air han...

Page 18: ...lack black black Variable Speed 314 T T Menu House Control 406 Item Tank Com Boil HPRt Out Com Zone 1 H8009B Zone 2 Zone 3 Zone 4 tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Rc1 Y1 O B Sensors No Power No Power C...

Page 19: ...or heating or mix the water temperature up above the dewpoint for floor cooling Expansion Tank Mechanical A406 5 S1 S2 S5 P3 tekmarNet 2 Thermostats tekmarNet 2 Thermostats P2 Z1 Z2 Z3 Z4 P5 Z9 Z10 Z1...

Page 20: ...black black 3 4 6 5 7 2 1 8 314 313 Menu House Control 406 Item Tank Com Boil HPRt Out Com Zone 1 H8009B Zone 2 Zone 3 Zone 4 tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Rc1 Y1 O B Sensors No Power No Power Call...

Page 21: ...CONDS Units of measurement for current number WARNING Displays if an error exists on the system Symbols Display User Interface Aux Setpoint Xfr Var Item Field Displays the name of the selected item Nu...

Page 22: ...sing the up or down button This will permit setting changes to the control Programming and Settings The 406 settings can be found in the Adjust menu When changing the items value the setting is saved...

Page 23: ...re the control is currently trying to maintain at the tank sensor The tank target is calculated based on the outdoor design and tank design settings is displayed when no heat is required for tank zone...

Page 24: ...ith TANK links zones 1 4 to the tank loop BOIL links zones 1 4 to the boiler loop MIX links zones 1 4 to the mixing loop Note This item is only available when either mix or boil water temperatures hav...

Page 25: ...SECTION D The outdoor air temperature used in the heating curves that determine the tank mix and boiler target temperatures Typically set to the temperature of the coldest day of the year 70 to 200 F...

Page 26: ...g device does not provide boiler protection when Boiler Type is set to EMS1 or EMS2 10 to 230 seconds Default 30 seconds Access Installer Set to BOILER MOTOR SPEED SECTION G Time in seconds from full...

Page 27: ...HOVER SECTION E O Close O B contacts to operate heat pump in cool mode B Close O B contacts to operate heat pump in heat mode 2 to 20 F 1 to 11 C Default 4 F Access Installer Set to HEAT PUMP DIFFEREN...

Page 28: ...CTION E Minimum compressor off time for the heat pump 10 to 180 minutes OVR Default 60 minutes Access Installer Set to BACKUP DELAY SECTION E The time that heat pump s have to run at full output befor...

Page 29: ...only available when HP TYPE 2STG or ROT 0 to 9999 Hours Default 0 hr Access User RUN TIME BOILER The total on time of the backup relay since the item was last reset Press and hold the Up and Down butt...

Page 30: ...Hours Default 0 hr Access Installer RUN TIME MIX SYSTEM PUMP The total running time of the Mix System Pump since this item was last reset Press and hold the Up and Down buttons while viewing to reset...

Page 31: ...ble items When set to USER all thermostats are locked and the number of thermostat settings available are reduced OFF SEL Default Off Access Installer FACTORY DEFAULTS Loads the factory default settin...

Page 32: ...ATERTEMP setting in the Adjust Menu to configure the proper water temperatures for the application The following table references application drawings with different water temperatures selected Applic...

Page 33: ...so used to give a boiler enable to allow the modulating boiler to go through the ignition sequence The Backup relay may not be required on all modulating boilers EMS1 The Mod dc mA output uses 0 10 V...

Page 34: ...ots of glass and high solar gains by extracting heat away from the slab before it is able to heat the room Floor is displayed in the Mode status field while doing floor cooling Enable Floor Cooling Fo...

Page 35: ...utdoor design These two parameters set the upper point for each heating curve Adjust the BOIL DSGN MIX DSGN and TANK DSGN settings in the Adjust Menu Boiler and Tank Minimum The BOIL MIN and TANK MIN...

Page 36: ...naturally recover better since there are longer periods of time between the heat pump transferring heat to or from the ground source GEO Source Staging Longer times between cycles Stage 2 ON Y2 Stage...

Page 37: ...ontrol shuts down the heat pump when the outdoor temperature falls below an adjustable temperature to prevent energy waste from unnecessary heat pump operation during cooling Use the Y COOLING CWSD se...

Page 38: ...Adjust Menu to adjust the preheat tank target The heat pump will target a water temperature 20 F 11 C higher than the preheat tank target at the return sensor The heat pump target is limited by the H...

Page 39: ...here are four items that determine the boiler target temperature 1 2 Differential 1 2 Differential Boiler Target Boiler On Boiler Off Boiler Differential Both on off and modulating boilers are operate...

Page 40: ...ings for House Control 406 with Common Modulating Boilers Modulating Boiler Operation The 406 can operate a single hot water modulating boiler using the Mod dc mA output and the Backup contact Not all...

Page 41: ...setting Note Setpoint operation has no priority Boiler System Pump Setpoint Pump Setpoint ON ON or OFF Zone Pump ON or OFF Setpoint Operation The control can operate to satisfy the requirements of a...

Page 42: ...g set to On The control is not in Warm Weather Shut Down Xfr The House Control 406 operates six different pump outputs on the back side of the enclosure The Pumps box in the status field indicates whi...

Page 43: ...supply sensor As a result the control operates the variable speed pump at a fixed output as long as there is a Mix Call Locate and repair the problem as described in the Test the Sensor Wiring sectio...

Page 44: ...me once the sensor problem is corrected The error message self clears once the error condition is corrected DOMESTIC HOT WATER CALL ERROR A DHW sensor and a DHW call have been applied at the same time...

Page 45: ...cking for the flashing Warning symbol Once the error on the device is corrected the error message will clear DEVICE ERROR AT ADDRESS M 01 to M 24 Each tekmarNet device thermostat setpoint control time...

Page 46: ...tem in AWAY During AWAY the thermostats operate at a lower temperature Locate a User Switch and set to Normal to resume heating MODE setting The mode of the 406 can be set to Auto Cool Heat Backup or...

Page 47: ...TANK DSGN TANK MIN MIX DSGN BOIL DSGN BOIL MIN BOIL MOTR MIN MOD MOD DELAY WWSD OCC WWSD UNOCC INTERLOCK COOL SETP Item Setting DEW POINT COOL MIN SWITCHOVER HP DIFF HP2 DELAY HP LOOP HP RETURN MAX H...

Page 48: ...sponsibility and obligation Pur chaser shall indemnify and hold tekmar harmless from and against any and all claims liabilities and damages of any kind or nature which arise out of or are related to a...

Reviews: