background image

© 2011

D 406 - 12/11

34 of 48

Interlock Delay

 ----------------------------------

 ----------------------------------

The interlock delay is the minimum time between heat/cool 
switchovers while in the AUTO mode. Use the INTERLOCK 
setting in the Adjust Menu to select an interlock time between 
10 minutes and 180 minutes.

Switchover

 --------------------------------------

 --------------------------------------

Switchover is determined by polling the thermostats on the 
Tank and Mix bus. When enough thermostats are calling for 
the opposite mode and the interlock delay has elapsed, a 
switchover will occur. This ensures that the system actually 
requires the new tank mode before switching over. Switchover 
includes purging and preheat or precool.

Purging

Once Switchover begins, the heat pump is forced off. All zones 
that are off remain off and all zones that become satisfied and 
turn off also remain off. The remaining zones are allowed to 
continue calling for 30 minutes or until the tank temperature 
changes by 15°F (8°C). This allows the tank to be purged 
before the heat pump is allowed to switch modes and reverse 
the water temperature of the tank. While this is happening, 

With Humidity Sensor

In areas where there is a potential for condensation to form 
on the cooling surface, floor cooling requires at least one 
humidity sensor on the network. The humidity sensor measures 
relative humidity. Knowing the relative humidity and the room 
temperature, the House Control 406 is able to calculate the 
dewpoint temperature. Keeping the surface temperature of 
the slab above dewpoint while doing floor cooling will prevent 
condensation from forming.
For best results, multiple humidity sensors may be used. 
The House Control 406 will choose the zone with the highest 
dewpoint to calculate the floor cooling target.
Set the DEW POINT item in the Adjust Menu to ON for floor 
cooling with a humidity sensor on the network.

Status Field

Floor Cooling

------------------------------------

------------------------------------

Floor cooling is a form of radiant base load cooling. It reduces 
the sensible cooling load, and care must be taken to avoid 
removing moisture from the air causing condensation (latent 
cooling). It works well in zones with lots of glass and high solar 
gains by extracting heat away from the slab before it is able to 
heat the room. ‘Floor’ is displayed in the Mode status field while 
doing floor cooling.

Enable Floor Cooling

For floor cooling to occur, a compatible tekmarNet

® 

thermostat 

must have floor cooling turned on. Use the FLOOR COOL (or 
F C) setting in the thermostat to turn floor cooling ON.

Pre-Heat or Pre-Cool

Once the purging has completed, the heat pump is allowed 
to preheat or precool the tank. All zones are prevented from 
calling for 30 minutes or until the tank temperature reaches 
within 10°F (5.5°C) of its new target. This allows time for the 
heat pump to switch the tank temperature to its new target 
before turning on zones again. 

Switchover from 

Heat to Cool Mode

Switchover from 

Cool to Heat Mode

Status Field

Status Field

HEAT

While in heat mode, the heat pump will  satisfy any heating 
calls from the zones on the Tank and Mix bus. The backup 
will operate automatically to satisfy DHW, Setpoint, Tank, Mix 
and Boil calls for heat. “Heat” is displayed in the Mode status 
field while in heat mode.

BKUP (Backup)

While in backup mode, the heat pump is disabled. The backup 
will operate automatically to satisfy DHW, Setpoint, Tank, Mix 
and Boil calls for heat. “Backup” is displayed in the Mode status 
field while in backup mode.

OFF

While in off mode, the heat pump and backup are disabled. 

Mode

 --------------------------------------------

 --------------------------------------------

There are five different modes that the heat pump and backup 
can operate in. Use the MODE setting in the Adjust Menu to 
select one of the following modes:

AUTO

The heat pump and backup will automatically switchover 
between heat and cool mode. 

COOL

While in cool mode, the heat pump will satisfy any cooling 
calls from the zones on the Tank and Mix bus. The backup  
will operate automatically to satisfy DHW and Setpoint calls 
for heat on the Boil bus. “Cool” is displayed in the Mode status 
field while in cool mode.

Heat Cool Operation

Section C

Status Field

the words “PURGING HEAT” or “PURGING COOL” will be 
displayed in the view menu depending if the tank is currently 
in the heat or cool mode.

Note:

 For hydronic cooling with a fancoil, use tekmarNet® 2 

thermostat 530 or tekmarNet® 4 thermostat 540 with a date 
code of 

December 2011

 or newer.

Summary of Contents for tekmarNet 2 House Control 406

Page 1: ...rts CSA C US Certified for use in USA and Canada Introduction The tN2 House Control 406 is designed to operate the equipment in a 2 pipe single tank hydronic heating and cooling system It operates two...

Page 2: ...tended for use as a primary limit control Other controls that are intended and certified as safety limits must be placed into the control circuit Do not attempt to service the control Refer to qualifi...

Page 3: ...llow proper wiring practices building and electrical codes for your jurisdiction Each cable must be pulled from the equipment to the electrical junction box It is recommended to label each cable for e...

Page 4: ...ix System P DHW Pump Transfer Pum Variable Speed Pump Boil System Pump Figure 1 Connect Ground Wires Figure 2 Connect Neutral Wires for Power Source 1 Pull two conductor 18 AWG LVT cable up to 500 fee...

Page 5: ...ly tucked inside the electrical box Using 2 of the 4 holes in the back of the enclosure securely fasten it to the junction box extension ring with 2 10 screws as shown in Figure 7 Install The Enclosur...

Page 6: ...add additional Boil or Mix water temperature zones to the system install a tekmarNet Wiring Center Connect the Boil Mix terminals tN4 and C on the 406 to the corresponding tN4 and C Expansion termina...

Page 7: ...heat pump Connect the Rc2 and Y2 terminals on the 406 to the R and Y2 terminals on the heat pump Connect the Rc1 and O B terminal on the 406 to the R and O or B terminal on the heat pump Wiring the A...

Page 8: ...vided in the enclosure The other side of the terminal block is used to connect wires from the control A good quality test meter capable of measuring up to 5 000 k 1 k 1000 is required to measure the s...

Page 9: ...peed setting Step 7 The mix system pump turns on for 10 seconds Step 8 The tank system pump turns on for 10 seconds Step 9 The O B contacts are closed for 10 seconds Step 10 The HP loop pump turns on...

Page 10: ...easure between 103 5 V ac and 126 5 V ac Testing the Boiler Modulating Output This test applies for modulating boilers only Active the User Test sequence and pause at Step 18 by pressing the Item butt...

Page 11: ...Menu An electric element in the system storage tank is switched on through an isolation relay with the backup relay on the 406 to provide backup heat to maintain the Tank Sensor S4 at its target temp...

Page 12: ...Com Boil HPRt Out Com Zone 1 H8009B Zone 2 Zone 3 Zone 4 tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Rc1 Y1 O B Sensors No Power No Power Call Call Mix DHW tN4 tN4 C C Mod dc mA Boil Mix Tank Rc2 Y2 Setpoint DHW...

Page 13: ...nter 314 An electric boiler supplies backup heat using the Backup relay and the Transfer Pump P7 By setting HP LOOP to ON the HP Loop Pump P2 will operate whenever there is a call on the tank or mix b...

Page 14: ...N 3 4 6 5 7 2 1 8 O C Y R O C Y R Transfer 314 Menu House Control 406 Item Tank Com Boil HPRt Out Com Zone 1 H8009B Zone 2 Zone 3 Zone 4 tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Rc1 Y1 O B Sensors No Power No...

Page 15: ...pump starts adding heat to the storage tank use the backup delay setting in the adjust menu This ensures the heat pump is being used to its full potential before backup is allowed Placing the Transfer...

Page 16: ...ack red black black black 313 Menu House Control 406 Item Tank Com Boil HPRt Out Com Zone 1 H8009B Zone 2 Zone 3 Zone 4 tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Rc1 Y1 O B Sensors No Power No Power Call Call M...

Page 17: ...sed to its full potential before backup is allowed A non condensing boiler may be used since P1 provides boiler return protection preventing flue gas condensation Tank zones can have fan coils air han...

Page 18: ...lack black black Variable Speed 314 T T Menu House Control 406 Item Tank Com Boil HPRt Out Com Zone 1 H8009B Zone 2 Zone 3 Zone 4 tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Rc1 Y1 O B Sensors No Power No Power C...

Page 19: ...or heating or mix the water temperature up above the dewpoint for floor cooling Expansion Tank Mechanical A406 5 S1 S2 S5 P3 tekmarNet 2 Thermostats tekmarNet 2 Thermostats P2 Z1 Z2 Z3 Z4 P5 Z9 Z10 Z1...

Page 20: ...black black 3 4 6 5 7 2 1 8 314 313 Menu House Control 406 Item Tank Com Boil HPRt Out Com Zone 1 H8009B Zone 2 Zone 3 Zone 4 tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Rc1 Y1 O B Sensors No Power No Power Call...

Page 21: ...CONDS Units of measurement for current number WARNING Displays if an error exists on the system Symbols Display User Interface Aux Setpoint Xfr Var Item Field Displays the name of the selected item Nu...

Page 22: ...sing the up or down button This will permit setting changes to the control Programming and Settings The 406 settings can be found in the Adjust menu When changing the items value the setting is saved...

Page 23: ...re the control is currently trying to maintain at the tank sensor The tank target is calculated based on the outdoor design and tank design settings is displayed when no heat is required for tank zone...

Page 24: ...ith TANK links zones 1 4 to the tank loop BOIL links zones 1 4 to the boiler loop MIX links zones 1 4 to the mixing loop Note This item is only available when either mix or boil water temperatures hav...

Page 25: ...SECTION D The outdoor air temperature used in the heating curves that determine the tank mix and boiler target temperatures Typically set to the temperature of the coldest day of the year 70 to 200 F...

Page 26: ...g device does not provide boiler protection when Boiler Type is set to EMS1 or EMS2 10 to 230 seconds Default 30 seconds Access Installer Set to BOILER MOTOR SPEED SECTION G Time in seconds from full...

Page 27: ...HOVER SECTION E O Close O B contacts to operate heat pump in cool mode B Close O B contacts to operate heat pump in heat mode 2 to 20 F 1 to 11 C Default 4 F Access Installer Set to HEAT PUMP DIFFEREN...

Page 28: ...CTION E Minimum compressor off time for the heat pump 10 to 180 minutes OVR Default 60 minutes Access Installer Set to BACKUP DELAY SECTION E The time that heat pump s have to run at full output befor...

Page 29: ...only available when HP TYPE 2STG or ROT 0 to 9999 Hours Default 0 hr Access User RUN TIME BOILER The total on time of the backup relay since the item was last reset Press and hold the Up and Down butt...

Page 30: ...Hours Default 0 hr Access Installer RUN TIME MIX SYSTEM PUMP The total running time of the Mix System Pump since this item was last reset Press and hold the Up and Down buttons while viewing to reset...

Page 31: ...ble items When set to USER all thermostats are locked and the number of thermostat settings available are reduced OFF SEL Default Off Access Installer FACTORY DEFAULTS Loads the factory default settin...

Page 32: ...ATERTEMP setting in the Adjust Menu to configure the proper water temperatures for the application The following table references application drawings with different water temperatures selected Applic...

Page 33: ...so used to give a boiler enable to allow the modulating boiler to go through the ignition sequence The Backup relay may not be required on all modulating boilers EMS1 The Mod dc mA output uses 0 10 V...

Page 34: ...ots of glass and high solar gains by extracting heat away from the slab before it is able to heat the room Floor is displayed in the Mode status field while doing floor cooling Enable Floor Cooling Fo...

Page 35: ...utdoor design These two parameters set the upper point for each heating curve Adjust the BOIL DSGN MIX DSGN and TANK DSGN settings in the Adjust Menu Boiler and Tank Minimum The BOIL MIN and TANK MIN...

Page 36: ...naturally recover better since there are longer periods of time between the heat pump transferring heat to or from the ground source GEO Source Staging Longer times between cycles Stage 2 ON Y2 Stage...

Page 37: ...ontrol shuts down the heat pump when the outdoor temperature falls below an adjustable temperature to prevent energy waste from unnecessary heat pump operation during cooling Use the Y COOLING CWSD se...

Page 38: ...Adjust Menu to adjust the preheat tank target The heat pump will target a water temperature 20 F 11 C higher than the preheat tank target at the return sensor The heat pump target is limited by the H...

Page 39: ...here are four items that determine the boiler target temperature 1 2 Differential 1 2 Differential Boiler Target Boiler On Boiler Off Boiler Differential Both on off and modulating boilers are operate...

Page 40: ...ings for House Control 406 with Common Modulating Boilers Modulating Boiler Operation The 406 can operate a single hot water modulating boiler using the Mod dc mA output and the Backup contact Not all...

Page 41: ...setting Note Setpoint operation has no priority Boiler System Pump Setpoint Pump Setpoint ON ON or OFF Zone Pump ON or OFF Setpoint Operation The control can operate to satisfy the requirements of a...

Page 42: ...g set to On The control is not in Warm Weather Shut Down Xfr The House Control 406 operates six different pump outputs on the back side of the enclosure The Pumps box in the status field indicates whi...

Page 43: ...supply sensor As a result the control operates the variable speed pump at a fixed output as long as there is a Mix Call Locate and repair the problem as described in the Test the Sensor Wiring sectio...

Page 44: ...me once the sensor problem is corrected The error message self clears once the error condition is corrected DOMESTIC HOT WATER CALL ERROR A DHW sensor and a DHW call have been applied at the same time...

Page 45: ...cking for the flashing Warning symbol Once the error on the device is corrected the error message will clear DEVICE ERROR AT ADDRESS M 01 to M 24 Each tekmarNet device thermostat setpoint control time...

Page 46: ...tem in AWAY During AWAY the thermostats operate at a lower temperature Locate a User Switch and set to Normal to resume heating MODE setting The mode of the 406 can be set to Auto Cool Heat Backup or...

Page 47: ...TANK DSGN TANK MIN MIX DSGN BOIL DSGN BOIL MIN BOIL MOTR MIN MOD MOD DELAY WWSD OCC WWSD UNOCC INTERLOCK COOL SETP Item Setting DEW POINT COOL MIN SWITCHOVER HP DIFF HP2 DELAY HP LOOP HP RETURN MAX H...

Page 48: ...sponsibility and obligation Pur chaser shall indemnify and hold tekmar harmless from and against any and all claims liabilities and damages of any kind or nature which arise out of or are related to a...

Reviews: