![background image](http://html1.mh-extra.com/html/tekmar/tekmarnet-2-house-control-406/tekmarnet-2-house-control-406_installation-and-operation-manual_1076504030.webp)
© 2011
D 406 - 12/11
30 of 48
Item Field
Range
Description
Aux
0 to 9999 Hours
Default = 0 hr
Access:
Installer
RUN TIME (AUXILIARY)
The total ‘on’ time of the Backup relay since the item was last reset. Press and
hold the Up and Down buttons while viewing to reset.
Note:
Item is only available when BACKUP = AUX.
Xfr
0 to 9999 Hours
Default = 0 hr
Access:
Installer
RUN TIME (TRANSFER PUMP)
The total running time of the Transfer Pump since the item was last reset. Press
and hold the Up and Down buttons while viewing to reset.
Note:
Item is only available when BACKUP = XFER
Var
0 to 9999 Hours
Default = 0 hr
Access:
Installer
RUN TIME (VARIABLE SPEED PUMP)
The total running time of the Variable Speed Pump since the item was last reset.
Press and hold the Up and Down buttons while viewing to reset.
Note:
Item is only available when BACKUP = VAR.
0 to 9999 Hours
Default = 0 hr
Access:
Installer
RUN TIME (HP LOOP PUMP)
The total running time of the HP Loop Pump since the item was last reset. Press
and hold the Up and Down buttons while viewing to reset.
0 to 9999 Hours
Default = 0 hr
Access:
Installer
RUN TIME (TANK PUMP)
The total running time of the Tank System Pump since this item was last reset.
Press and hold the Up and Down buttons while viewing to reset.
0 to 9999 Hours
Default = 0 hr
Access:
Installer
RUN TIME (MIX SYSTEM PUMP)
The total running time of the Mix System Pump since this item was last reset.
Press and hold the Up and Down buttons while viewing to reset.
Note:
Item is only available when WATERTEMP = T + M or T + MB.
0 to 9999 Hours
Default = 0 hr
Access:
Installer
RUN TIME (BOIL SYSTEM PUMP)
The total running time of the Boil System Pump since this item was last reset.
Press and hold the Up and Down buttons while viewing to reset.
Note:
Item is only available when WATERTEMP = T + B or T + MB.
0 to 9999 Hours
Default = 0 hr
Access:
Installer
RUN TIME (DHW PUMP)
The total running time of the DHW Pump since this item was last reset. Press
and hold the Up and Down buttons while viewing to reset.
Note:
Item is only available when DHW MODE ≠ OFF.
– – –, -35 to 273°F
(-37 to 134°C)
Access:
Installer
DEW POINT MIX
Highest dewpoint of all humidity sensors on the mix loop.
Note:
Item is only available when WATERTEMP = T + M or T + MB and a
humidity sensor has been detected on the mix bus.
– – –, -35 to 273°F
(-37 to 134°C)
Access:
Installer
DEW POINT TANK
Highest dewpoint of all humidity sensors on the tank loop.
Note:
Item is only available when a humidity sensor has been detected on
the tank bus.
– – –, -35 to 273°F
(-37 to 134°C)
Access:
Installer
DEW POINT BOIL
Highest dewpoint of all humidity sensors on the boiler loop.
Note:
Item is only available when WATERTEMP = T + B or T + MB and a
humidity sensor has been detected on the boiler bus.
Monitor Menu (2 of 2)