Adjustment of Settings 

• If the outdoor temperature is cold and the rooms are cold, increase the 

Curve setting by 0.1 per day.

• If the outdoor temperature is near the WWSD temperature and the rooms are cold, increase the 

Starting Temp. setting.

• If the boiler is cycling too often, increase the 

Differential setting or set control to Ad (Auto Differential).

STEP NINE 

 BEFORE YOU LEAVE 

• Install the wiring cover over the wiring chamber and secure it with the screw provided.

• Place the front cover on the control and snap it into place.

• Place this brochure, and all other brochures relating to the installation, in the protective plastic bag supplied with the control.

• Place the bag in a conspicuous location near the control for future reference.

• It is important to explain the operation of this control within the system to the end user, and to anyone else who may be operating

the system.

Error Messages

Whenever a fault is detected, an error message will be displayed to indicate the location of the problem. For detailed sensor testing
instructions see Data Brochure D 070.

Refer to the troubleshooting section above for operation details

WWSD

Boiler Supply

    Target Boiler
       Starting Temp.

Minimum Boiler

Differential

Curve

OUTDOOR

H. Dem

Boiler

Outdoor Sensor

Open Circuit

WWSD

Boiler Supply

    Target Boiler
       Starting Temp.

Minimum Boiler

Differential

Curve

OUTDOOR

H. Dem

Boiler

WWSD

Boiler Supply

    Target Boiler
       Starting Temp.

Minimum Boiler

Differential

Curve

OUTDOOR

H. Dem

Boiler

WWSD

Boiler Supply

    Target Boiler
       Starting Temp.

Minimum Boiler

Differential

Curve

H. Dem

Boiler

Outdoor Sensor

Short Circuit

OUTDOOR

WWSD

Boiler Supply

    Target Boiler
       Starting Temp.

Minimum Boiler

Differential

Curve

H. Dem

Boiler

WWSD

Boiler Supply

    Target Boiler
       Starting Temp.

Minimum Boiler

Differential

Curve

H. Dem

Boiler

Internal

Fault

WWSD

Boiler Supply

    Target Boiler
       Starting Temp.

Minimum Boiler

Differential

Curve

H. Dem

Boiler

WWSD

Boiler Supply

    Target Boiler
       Starting Temp.

Minimum Boiler

Differential

Curve

H. Dem

Boiler

Boiler Sensor

Short Circuit

WWSD

Boiler Supply

    Target Boiler
       Starting Temp.

Minimum Boiler

Differential

Curve

H. Dem

Boiler

Boiler Sensor

Open Circuit

WWSD

Boiler Supply

    Target Boiler
       Starting Temp.

Minimum Boiler

Differential

Curve

H. Dem

Boiler

flashes

between

flashes

between

flashes

between

flashes

between

flashes

between

Notes

Summary of Contents for One Stage Boiler Control 253

Page 1: ... Mar 97 31000265 displays control settings displays hundreds of hours of use displays hours of use Press Hold Item One Stage Boiler Control 253 2 3 Com Sen Boil Sen Out Sen No power 7 8 Power R C NRTL C LR 58223 R USE hours Minimum Boiler Differential Curve Boiler Supply Target Boiler Starting Temp H Dem Boiler OUTDOOR Signal wiring must be rated at least 300V Input Heat Demand Made in Canada Cont...

Page 2: ...s possible for maximum efficiency Differential An on off boiler must be operated with a differential in order to prevent short cycling When the supply water temperature drops below the bottom rail of the differential the boiler is turned on The boiler is then kept on until the supply water temperature rises above the top rail of the differential If the differential is too wide there can be large s...

Page 3: ...ur responsibility to ensure that this control is safely installed according to all applicable codes and standards This electronic control is not intended for use as a primary limit control Other controls that are intended and certified as safety limits must be part of the control circuit STEP ONE GETTING READY Check the contents of this package If any of the contents listed are missing or damaged ...

Page 4: ...d Connect the C side of the transformer to terminal T 6 through a switching device This provides a heat demand to the control Caution The C of the same transformer used to power up the control must be used to provide the heat demand Sensor and Unpowered Input Connections Do not apply power to these terminals as this will damage the control Outdoor Sensor Connect the two wires from the Outdoor Sens...

Page 5: ... in outdoor temperature The Curve setting can be calculated from the following formula design supply temperature Starting water temperature Heating Curve WWSD design outdoor temperature Curve Heating Curve Setting Examples Example 1 Example 2 Example 3 Design Supply Water Temperature 180 F 82 C 180 F 82 C 180 F 82 C Starting Water Temperature 70 F 21 C 150 F 66 C 160 F 71 C Design Outdoor Temperat...

Page 6: ...pply pointer WWSD Boiler Supply Target Boiler Starting Temp Minimum Boiler Differential Curve F H Dem Boiler WWSD Boiler Supply Target Boiler Starting Temp Minimum Boiler Differential Curve PRGM F C When the control is powered up a version number followed by all display elements are turned on After approximately 5 seconds the control automatically goes into operating mode OUTDOOR H Dem Boiler WWSD...

Page 7: ...70 Refer to the troubleshooting section above for operation details WWSD Boiler Supply Target Boiler Starting Temp Minimum Boiler Differential Curve OUTDOOR H Dem Boiler Outdoor Sensor Open Circuit WWSD Boiler Supply Target Boiler Starting Temp Minimum Boiler Differential Curve OUTDOOR H Dem Boiler WWSD Boiler Supply Target Boiler Starting Temp Minimum Boiler Differential Curve OUTDOOR H Dem Boile...

Page 8: ...n compliance with the local codes and ordinances or if due to defective installation of the product The warranty applicable to a product is as set out in the statement of warranty policy the Warranty above receipt of which is hereby acknowledged The liability of tekmar is limited to those obligations identified in the warranty as obligations of tekmar The warranty is understood to be in substituti...

Reviews: