background image

28 

   NT311 ETH

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

MENU MODIFICATION PROCEDURE 1) IP parameters:  

 

enter the command: 1

 

 

 

IP Address: 

 

 

 

1) Enter the desired new IP address, if you wish to keep the set address press ENTER 4 times.

 

 

 

 

At the end of the operation, the system will ask if you wish to modify the Gateway IP:  

 

 

 

 

Type in:  

Y

 to modify the Gateway IP.  

 

               N

 not to modify the Gateway IP and go to the following step.

 

 

 

2) Enter the desired new Gateway IP address, press ENTER; if you wish to keep the set address 
press ENTER 4 times.

 

 

 

 

 

 

 

At the end of the operation, the system will ask if you wish to modify Netmask:  
 

 

 

 

Type in:  

Y

 to modify the Netmask.  

 

               N

 not to modify Netmask and go to the following step. 

 

 

3) Enter the new Netmask, press ENTER; if you wish to keep the set address press ENTER 4 times.

 

 

 

 

 

 

 

At the end of the operation, the system will ask if you wish to modify the Telnet Password:  
 

 

 

 

 

Type in:  

Y

  to modify the Telnet Password.  

 

               N

 not to modify the Telnet Password and go to the following step.

 

 

 

Summary of Contents for NT311 ETH

Page 1: ...with ISO9001 certified quality system http www tecsystem it R 1 1 26 11 2020 Translations of the original instructions ENGLISH TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 NT311...

Page 2: ...MANAGEMENT 18 TABLE OF CONTENTS INTRODUCTION Firstly we would like to thank you for choosing to use a TECSYSTEM product and we strongly suggest that you read this instruction manual carefully It will...

Page 3: ...L CONNECTIONS FUNCTION CODE CODE 3 10 CODE 16 10 NOTES FOR REMOTE PROGRAMMING 20 ERROR CODES ILLEGAL DATA MODBUS MAPPING TABLE 21 10 ETHERNET MODULE PARAMETER PROGRAMMING 25 ETH0 CONNECTIONS TELNET EN...

Page 4: ...eeding 90 and never touch with wet or damp hands If any liquid penetrates the control unit disconnect it immediately and contact technical assistance CLEANING Disconnect the power cable before cleanin...

Page 5: ...24 1 terminal 11 poles pitch 5 relays Code 2PL0528 1 Terminal 4 poles pitch 3 81 TPU input Code 2PL0527 1 Terminal 3 poles pitch 3 81 doors input Code 2PL0523 ACCESSORIES ATTENTION always install the...

Page 6: ...ting management relay Output relays with 10A 250Vca res COS 1 contacts TCP IP Modbus Ethernet output DIMENSIONS 106 60x122x53 50mm DIN rail TESTS AND PERFORMANCE Construction in compliance with the EC...

Page 7: ...memory diagnostics Ech Access to programming through front keyboard Automatic exit from programming display and relay test after 1 minute of inactivity Selection of display mode for scanning or manual...

Page 8: ...o not cover the P1 2 3 dust detection sensors Never block the TU sensor input Do not place near strong magnetic fields or excessive heat sources higher than the product specifications Remove the dust...

Page 9: ...ellow LED 8 UP key 16 Scan mode selection yellow LED FRONT PANEL 1 2 3 4 5 6 7 8 9 10 11 12 14 13 15 16 1MN0199 REV 0 TPU SENSOR CONNECTION NOTES The TPU sensor must be connected to the control unit u...

Page 10: ...operation of the NT311 can be displayed 1 RUN cPU This message appears when the unit is operating regularly without any system error 2 cPU Err This message appears when the device detects an operating...

Page 11: ...proximately 5 seconds the TST indication appears for 2 seconds confirming entry into the Relays Test mode The lit LED indicates the relay to be tested use the cursors to select the desired relay Press...

Page 12: ...Ethernet port 3 Door contact input Door1 and Door2 Note image of relay contacts in non alarm condition except for the FAULT relay which switches contacts 9 11 closed NO contacts 10 11 open NC Read the...

Page 13: ...does not detect anomalies and keeps the switching until when one of the following events occurs Data memory fault Ech message TEC sensor fault C dSt rH Insufficient supply voltage During the power on...

Page 14: ...ay FAN FAN LED flashes 8 Select YES or NO Default YES 9 Enabling of alr alarm relay ALARM LED flashes 10 Select YES or NO Default YES 11 Low ambient temperature management Tlo Default YES 12 Select YE...

Page 15: ...g of alr alarm relay ALARM LED flashes 32 Select YES or NO Default YES 33 Enabling of input door 1 D1 34 Select YES or NO Default YES 35 Enabling of alr alarm relay ALARM LED flashes 36 Select YES or...

Page 16: ...ve indication of the faulty dust deposit sensor FLT dSt NOTE the TPU sensor diagnostics is reported in the modbus register 14 CPU ERROR Furthermore by pressing the MODE key and selecting the MAN mode...

Page 17: ...with TLo 5 C Humidity RH The alarms relating to the humidity parameter rH can be programmed with a range between 10 90 RH with steps of 1 The rH parameter can be enabled YES or disabled NO With NO pr...

Page 18: ...y switches HEATER When the temperature exceeds 1 C the programmed Tlo threshold example 6 C the relative relay switches and the HEATER LED turns off The high flexibility of the NT311 control unit allo...

Page 19: ...odbus TCP slave The unit can be used for remote configuration monitoring in real time or problem solving The Windows based Telnet system allows configuring the NT311 ETH easily into a sub network with...

Page 20: ...e is carried out a check of compatibility data 1 If you have a non compatibility exception for an answer and the data packet is rejected in its entirety The code of the first erroneous data can be obt...

Page 21: ...e 20H Vers Fw MSD ASCII R 4 Vers Fw 2 Digit ASCII Vers Fw LSD ASCII R 5 00 00 6 00 00 7 00 Incorrect datum received R see tab 8 00 Info various causes R see tab 9 00 Controls W see tab SYSTEM Setting...

Page 22: ...ess Modbus address 1255 R 18 00 Bdr Modbus baud rate 0 2400 1 4800 2 9600 3 19200 4 38400 R 19 00 Parity Modbus parity bit Stop 0 No 1stop 1 Even 2 Odd 3 No 2stop R 20 00 00 21 00 00 22 00 Sensor stat...

Page 23: ...n RW 37 00 2 compl temper 2 measured min historic from E2PROM MSB Sign ModBus only R 38 00 Measured humidity value MSB Sign R 39 00 Max humidity Set point See Progr Humid rH RW 40 00 Humidity controls...

Page 24: ...Tecsybus Error TEC Sens Dust Error dSt Sens Humid Error rH Temp Sens Error C ECH error SENSOR STATUS BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 In P D2 All In P D1 All Dust All Humidity All Temp...

Page 25: ...C TELNET ENABLING Use the Telnet program to set the Ethernet IP parameters 1 START menu Windows If already enabled the program appears 2 Start the search with the Telnet program Press ENTER to launch...

Page 26: ...restart the PC if required 9 START menu Windows 10 Search for the Telnet program 15 Enter 192 168 10 120 9999 16 Press ENTER 12 TELNET SCREEN 11 Press ENTER to launch the program 13 Enter OPEN 14 Pre...

Page 27: ...cation parameters between the ETH0 port and the control unit 3 Communication configuration between the ETH0 port and the control unit 4 Communication advanced settings between the ETH0 port and the co...

Page 28: ...Enter the desired new Gateway IP address press ENTER if you wish to keep the set address press ENTER 4 times At the end of the operation the system will ask if you wish to modify Netmask Type in Y to...

Page 29: ...page 27 Indications of LEDs 1 2 of the Ethernet port LED 1 Link Off No link Amber 10 Mbps Green 100 Mbps 1 2 LED 2 Activity Off No Activity Amber Half Duplex Green Full Duplex 4 Enter the new Telnet P...

Page 30: ...bove instructions restore the voltage Fault with indication ECH A strong disturbance has damaged the memory data See the paragraph for programmed data diagnostics on page 16 Fault with TEC indication...

Page 31: ...suant to European directive 2012 19 EU on electrical and electronic waste WEEE Any electrical or electronic equipment marked with this symbol must be disposed of separately from normal domestic waste...

Reviews: