Basic manual for CP-1004 module
TXV 110 04
14
Delay from log. 0 to log. 1
5 µs (DI0 - DI3)
5 ms (DI4 - DI7)
Delay from log. 1 to log. 0
5 µs (DI0 - DI3)
5 ms (DI4 - DI7)
Minimal size of captured pulse
50 µs
Input pulse overloading
max. 250 V (t < 10 ms)
* DI0 to DI3 inputs can be used as a special inputs (see chapter 2) and DI4 to DI7 inputs as an
analog inputs (see table below).
Note! It is necessary to be aware of GND terminals in groups 24 V DC and DIGITAL / SPECIAL
INPUTS are galvanically connected inside the system. It is not wantable to connect GND
terminal in DIGITAL / SPECIAL INPUTS group with a minus pole of power supply supplying
both the system and inputs, because the loop would be closed through the second GND ter-
minal and would cause possible disturbing signal inducing.
Analog input parameters (optional function of DI4 to DI7 function)
Number of inputs
4 (DI4 - DI7 optional function)
Number of inputs in a group
4 (common with DI0 - DI3 inputs)
Galvanic isolation from internal circuits
no
Diagnostics
overload indication in a status word
Common pole
minus
External power supply
no
Converter type
sigma-delta
Conversion time
350 µs
Numerical resolution
10 bits
Input resistance
approx. 6 k
Ω
Measure range / resolution (1 LSB)
0 to +10 V / 11,36 mV
Permitted continuous overload
max. +10,5 V, min. 0 V
Error of analog input
< 3 %
Max. error at 25 °C
± 3 % of full range
Temperature coefficient
± 0,1 % of full range / K
Linearity
± 0,2 % of full range
Repeatability under steady conditions
0,5 % of full range
Detection of open input
no