1. DESCRIPTION AND PARAMETERS
The CP-1004 module is a part of an assortment of Tecomat Foxtrot series modular pro-
grammable controller basic modules. It differs from other basic modules by the number of inputs
and outputs.
The CP-1004 basic module is equipped with 8 digital inputs 24 V, four of which can be used
as an analog inputs with a range 1÷10 V and four as a special function inputs (fast counter, in-
cremental encoder connection etc.). Then, the module is equipped with 6 relay outputs.
The CP-1004 module contains a central unit (CPU) of series K designed for applications
where a higher power is required. It contains CMOS RAM memory for user programs, data and
tables, user registers, RTC, Ethernet interface, two serial channels (one with a fixed RS-232 in-
terface and the second with a position for optional submodules), one communication channel
with CIB interface for the connection of external peripheries and a system TCL2 interface de-
signed for the connection of expansion modules which increase system I/O number.
1.1 BASIC PARAMETERS
Product standard
Č
SN EN 61131-2:2005 (idt IEC 61131-2:2003)
Protection class of electrical object
Č
SN EN 61140:2003 (idt IEC 61140:2001)
I
Connection
screwless terminals, max. 2.5 mm
2
conductor per
terminal, RJ-45 (ETHERNET TP)
Type of equipment
built in
Power supply (SELV)
24 VDC, +25 %, - 15 %
Module power input
max. 8 W
Coverage
Č
SN EN 60529:1993 (idt IEC 529:1989)
IP10B
Dimensions
90 × 105 × 65 mm
1.2 OPERATIONAL CONDITIONS
Class of ambient influence -
Č
SN 33 2000-3:1995 (mod IEC 364-3:1993)
normal
Operating temperature range
0 °C to +55 °C
Permissible temperatures during trans-
port
–25 °C to +70 °C
Relative humidity
10 % to 95 % without condensation
Atmospheric pressure
min. 70 kPa (< 3000 m over the sea level)
Degree of pollution -
Č
SN EN 61131-2
1
Overvoltage category of installation -
Č
SN 33 0420-1
II
Working position
vertical
Type of operation
continuous
Electromagnetic compatibility
Emissions -
Č
SN EN 55022:1999 (mod CISPR22:1997)
class A
Immunity
min. according to requirements
Č
SN EN 61131-2:2005
Sinusoidal vibration resistance **
10 Hz to 57 Hz, amplitude 0.075 mm,
57 Hz to 150 Hz, acceleration 1G
* In indoor conditions (i.e. such conditions, where using of radio and TV sets can be supposed
in a distance of 10 m from the mentioned equipment), the product can cause radio distur-
Summary of Contents for CP-1004