15
2-2 Installation of Grid-tied Wind Power Inverter
※
Installation Procedure of Inverter
:
Conditions
Do not operate the Inverter in an environment where the ambient temperature is outside the limits given in
the specifications of this manual. These inverter units are in-tended for use in a temperature-controlled,
indoor area free of conductive contaminants. Select a location that will provide good air circulation for
inverter at all times.
◇
Placement
Mounting the Grid-tied Inverter on the wall
(1)
The mounting background must be firm.
(2)
The ambient temperature must be between -20°C and +40°C.
(3)
Install at a shading roof, do not expose the inverter to direct sunlight.
(4)
Keep it in good ventilated situation; a minimum distance of 10 inch (254 mm) must be clear
around the inverter.
(5)
The heat sink can reach a temperature of more than +80°C. The air circulation must be sufficient
for heat dissipation.
(6)
Provide a correct position of the inverter for mounting.
(7)
The inverter is mounted on the back side with the metal strap.(as Figure 7)
(8)
Check mounting is firm.
(9)
Please ensure to install the grid-tied wind power inverter in a ventilated location. There should be no any
stack around one meter of its surrounding.