UPS EXA 1.1-1.5-2.2-2.6-3.2 Rack Mount 

 

10

 

Troubleshooting 

Alarms  and  problems  you may encounter during operating the UPS are given in the table below. 

Apply 

the suggestions corresponding to each anomaly as described into the table.  

If  your  anomaly  is  excluded  or  the  suggested  actions  do  not  solve  your  problem,  consult  the  Technical  Service. 
Please give the following information to the Technical Service: 

 

Model and serial number of the UPS, which can be found on the nameplate on the rear of the UPS.  

 

Description of anomaly. 

 

 

Risk of electric shock: do not remove the cover. The UPS contains internal parts that are 
at  a  high  Voltage  and  are  potentially  dangerous,  capable  of  causing  injury  or  death  by 
electric shock. 

There  are  no  internal  parts  in  the  UPS  that  are  user  serviceable.  Any  repair  or 
maintenance  work  must  be  performed  exclusively  by  qualified  technical  personnel 
authorized by TECNOWARE.  

TECNOWARE declines any responsibility if this warning is disregarded. 

Warning  to  the  technical  personnel  authorized  for  service:  since  internal  components 
are  connected  to  the  batteries,  they  will  remain  powered,  and  therefore  dangerous, 
even  after  the  UPS  has  been  disconnected  from  AC  power  mains.  Before  any  repair or 
maintenance work, disconnect the batteries, by removing the positive cable (red colour) 
from the positive pole of the battery.

 

 

ANOMALY 

POSSIBLE CAUSE 

ACTION TO SOLVE 

The UPS does not 
turn on 

ON/OFF button 

Press the ON/OFF button. 

Batteries are flat 

Recharge the batteries for at least 4 hours. 

Electronic board failure 

Refer to Technical Service. 

The UPS always 
function in Battery 
mode 

Input mains power cable is 
disconnected. 

Check the input mains power cable. 

Check the presence of the electrical mains. 

ON/OFF switch 

Check if the rear ON/OFF switch is in ON position 

Input mains fuse is burnt 

Replace the fuse with another of the same type. 

Black-out conditions / surge/ 
Over-Voltage or Low-Voltage 

Wait until the AC Input Line returns to normal conditions. 

Electronic board failure 

Refer to Technical Service. 

Battery Autonomy is 
too short 

Battery is not fully charged. 

Recharge the battery for at least 6 hours. 

Electronic board failure 

Refer to Technical Service. 

“OVERLOAD” alarm 

“OVERLOAD” condition 

Disconnect all devices that cause the overload condition. 

“FAULT” alarm 

“FAULT” condition 

Check if UPS is in OVERLOAD condition. 

Refer to Technical Service. 

The UPS does not 
communicate with 
the Computer  

The UPS Management 
Software sends a 
communication error 

Check that the USB (or RS232) cable is correctly connected 
between the UPS and the Computer.  

The Software is not correctly 
installed 

Install correctly the specific Software for your Computer’s 
Operative System. 

 

If the described anomalies should continue despite the advised troubleshooting, or should they 

manifest in any other form, please contact: 

TECNOWARE SERVICE 

www.tecnoware.com

 

Summary of Contents for EXA 1.1

Page 1: ...Uninterruptible Power Supply EXA 1 1 Rack Mount EXA 1 5 Rack Mount EXA 2 2 Rack Mount EXA 2 6 Rack Mount EXA 3 2 Rack Mount User s manual Manuale utente...

Page 2: ......

Page 3: ...acteristics 10 9 Maintenance 11 9 1 UPS Cleaning 11 9 2 Battery 11 9 3 Operator Safety 11 10 Troubleshooting 12 Conformity to the European Directives 13 Product Disposal 13 Lead Batteries 13 Copyright...

Page 4: ...Funzionamento 21 6 1 Modo Normale 21 6 2 Modo Batteria 21 6 3 Fine Autonomia e Riaccensione Automatica 21 6 4 Controllo del Carico 21 6 5 Segnalazioni di Guasto 22 7 Interfacce di Comunicazione 22 8...

Page 5: ...ponents are connected to the batteries they will remain powered and therefore dangerous even after the UPS has been disconnected from AC power mains Before any repair or maintenance work disconnect th...

Page 6: ...condition directly to a computer this makes it possible to automatically save your data during an extended black out with the most widespread operating systems Windows Linux etc Read this manual caref...

Page 7: ...pable battery High efficiency Maximum reliability Smart design and easy to use 3 Receipt and site selection Carefully remove the UPS from its packaging and carry out a meticulous inspection We recomme...

Page 8: ...itions and measurements Front panel shown below consists of two parts 1 LCD display provides information about input only in line mode and output voltage output frequency only in battery mode battery...

Page 9: ...voltage 3 BATTERY LEVEL 3 digits indicate the battery charging percentage 4 LOAD LEVEL 3 digits indicate the output load percentage 5 FREQUENCY the 3 digits indicate the output frequency only visualiz...

Page 10: ...colour to supply critical loads 3 Telephone protection RJ11 IN OUT connectors to protect and filter a phone line TNV 3 type connections 4 Computer Interface DB9 female connector it is the communicatio...

Page 11: ...onnected to the UPS outputs are working correctly By LCD display check if the Output load percentage is less than 100 otherwise it is necessary to remove part of the Output load 7 Simulate a black out...

Page 12: ...by an acoustic signal every 10 seconds 6 3 Low Battery and Automatic Restart In Battery mode EXA Rack Mount indicates the Low Battery condition whenever the battery reaches a charge level allowing con...

Page 13: ...Technical Characteristics as this may damage the unit In this case the warranty is void 6 5 Fault Condition The UPS indicates the Fault condition by LCD display by emitting a continuous acoustic alarm...

Page 14: ...C Directive Efficiency 96 Battery Type Lead acid sealed free maintenance Number of batteries 2 3 Nominal Battery Voltage 24 Vdc 36 Vdc Battery Specifications 12 Vdc 7 Ah 6 cells 12 Vdc 7 Ah 6 cells 12...

Page 15: ...procedure described in the chapter 5 before using it again Please keep in mind that the batteries must be recharged at least once a month Take in mind that batteries are recharged automatically if th...

Page 16: ...positive pole of the battery ANOMALY POSSIBLE CAUSE ACTION TO SOLVE The UPS does not turn on ON OFF button Press the ON OFF button Batteries are flat Recharge the batteries for at least 4 hours Electr...

Page 17: ...isposed as an urban waste but must be treated as a separate waste Any violation is indictable with financial sanctions as per in force regulations An incorrect waste disposal or an improper use of the...

Page 18: ...ento l UPS e scollegato dalla rete elettrica le parti interne sono ancora in tensione essendo collegate alle batterie e quindi pericolose Prima di effettuare qualsiasi tipo di riparazione o manutenzio...

Page 19: ...EXA Rack Mount perch contiene importanti avvisi di sicurezza per l operatore ed utili consigli per un corretto impiego Questo manuale una guida per installare e utilizzare correttamente l UPS Nel man...

Page 20: ...o stato dell UPS In caso di danni dovuti al trasporto annotarli sulla bolla di accompagnamento merce e contattare subito il fornitore Si consiglia di conservare l imballo originale in luogo sicuro nel...

Page 21: ...ale mostrato nella figura 1 costituito da 2 parti 1 Un display LCD che fornisce i valori della tensione d ingresso solo in modalit rete e d uscita la frequenza d uscita solo in modalit batteria la per...

Page 22: ...lla tensione d uscita in volt 3 BATTERY LEVEL i 3 digit indicano la percentuale di carica delle batterie 4 LOAD LEVEL i 3 digit indicano la percentuale di potenza erogata in uscita 5 FREQUENCY i 3 dig...

Page 23: ...tipo IEC C13 colore nero da utilizzare per alimentare carichi critici 3 Protezione Telefonica connettori RJ11 IN OUT per proteggere e filtrare una linea telefonica connessioni di tipo TNV 3 4 Interfac...

Page 24: ...iano accesi regolarmente Inoltre controllare la percentuale di carico in Uscita indicata sul display LCD e assicurandosi che il valore sia inferiore al 100 altrimenti necessario rimuovere parte del ca...

Page 25: ...le batterie sono scariche al punto da garantire soltanto alcuni minuti di autonomia L UPS avvisa l utente della condizione di Fine Autonomia emettendo un segnale acustico ogni secondo Se la linea ele...

Page 26: ...ivi alimentati 7 Interfacce di Comunicazione L UPS dotato delle Interfacce RS232 e USB utilizzabili come porte di comunicazione con un Personal Computer Infatti sul retro sono presenti i connettori de...

Page 27: ...iva Bassa Tensione CEI EN 62040 2 2006 Direttiva EMC Rendimento 96 Tipo Batterie Piombo acido sigillate senza manutenzione Numero di Batterie 2 3 Tensione Nominale Batterie 24 Vdc 36 Vdc Specifiche Ba...

Page 28: ...a di riutilizzarlo normalmente svolgere la procedura di Prima Accensione descritta nell omonimo capitolo di questo manuale Tenere comunque presente che le batterie vanno ricaricate almeno 1 volta al m...

Page 29: ...ANOMALIA POSSIBILE CAUSA AZIONI PER RISOLVERE L UPS non si accende Pulsante ON OFF Premere il pulsante ON OFF Batterie scariche Ricaricare le batterie per almeno 6 ore Guasto scheda elettronica Rivol...

Page 30: ...ssere smaltito come rifiuto urbano ma deve esserlo tramite raccolta separata qualsiasi violazione punita con sanzioni pecuniarie ai sensi delle vigenti norme Lo smaltimento non corretto del prodotto o...

Page 31: ......

Page 32: ...TECNOWARE s r l www tecnoware com...

Reviews: