ENGLISH
User’s manual
10
UPS EXA 1.1-1.5-2.2-2.6-3.2 Rack Mount
8
Technical Characteristics
UPS EXA Rack Mount Model
1.1
1.5
2.2
2.6
3.2
Power
1100 VA
(550 W)
1500 VA
(750 W)
2200 VA
(1100 W)
2600 VA
(1300 W)
3200 VA
(1600 W)
Technology
Line Interactive Pure Sinewave with Stabilizer
Nominal Input Voltage
Single-phase 230 Vac
Input Voltage Range
+20% / -25%
Input/Output Frequency
50/60 Hz (automatic selection)
Input Frequency Range
+/- 10%
Nominal Output Voltage
Single-phase 230 Vac
Output Voltage Regulation
(Normal mode)
Through AVR (Automatic Voltage Regulation)
Output Voltage Regulation
(Battery mode)
+/- 5%
Output Inverter Waveform
Sinewave
Accepted Overload
110%-60sec / 120%-30sec / >120%-20msec
Certifications
CE
Standards: CEI EN 62040-1: 2008 (Low Voltage Directive) –
CEI EN 62040-2: 2006 (EMC Directive)
Efficiency
96%
Battery Type
Lead acid, sealed, free maintenance
Number of batteries
2
3
Nominal Battery Voltage
24 Vdc
36 Vdc
Battery Specifications
12 Vdc – 7 Ah
6 cells
12 Vdc – 7 Ah
6 cells
12 Vdc – 8 Ah
6 cells
12 Vdc – 8 Ah
6 cells
12 Vdc – 8 Ah
6 cells
Backup Time (typical)
12 min
10 min
8 min
8 min
6 min
Battery Charge Time (typical)
4 hours
Audible Noise (at 1 meter)
< 45 dBA
Environmental Operative Specification
Temperature: 0-40 °C - Humidity 0-95% (without condensation)
Altitude: max 3.000 mt
Computer Interface
1 RS232 port and 1 USB port
UPS Management Software
Included Software UPSilon 2000,
downloadable free of charge from
www.tecnoware.com
SNMP Interface
Optional
Telephone and Modem protection
RJ11 plugs included
Output sockets
4 UPS Output sockets (IEC type)
6 UPS Output sockets (IEC type)
Dimension (W x H x D)
30,9 x 8,8 x 43,8 cm (2U)
36 x 13,2 x 43,8 cm (3U)
Net Weight
14,5 Kg
15,5 Kg
16,5 Kg
18,5 Kg
19.5 Kg
Technical data may change without prior notice