“ALARMS” TABLE
CODE
NAME
DEFINITION
A01
BYP BADSHAPE
Bypass mains voltage is different than the Inverter reference signal (e.g. its
frequency is beyond synchronization limits or it has a Total Harmonic Distortion >
%10).
A02
BYP VOL HIGH
Bypass mains voltage is higher than its upper limit.
A03
BYP VOL LOW
Bypass mains voltage is lower higher than its lower limit.
A06
BYP SYN FAIL
Frequency of Bypass mains voltage is beyond the frequency range for Bypass
operation or Bypass mains voltage is very low.
A07
BYP SEQ FAIL
Phase sequence of Bypass mains voltages is not OK.
A08
MNBYP SW ON
Manual Bypass breaker is “ON”/“1”.
A09
INV TMP HIGH
Inverter block temperature is very high.
A10
OUT OVERLOAD
RMS current drawn from any of the output lines exceeds its nominal value.
A11
BYP ACT
Bypass mode is activated.
A12
INV NOT ACT
Inverter is not started due to a fault.
A13
INV BLCK
Inverter operation is automatically stopped due to a fault.
A14
VSEC NOT OK
Output voltage is beyond its limits.
A17
INP VOL HIGH
Input line/neutral voltage is higher than its upper limit.
A18
INP VOL LOW
Input line/neutral voltage is lower than its lower limit.
A21
INP SYN FAIL
Frequency of mains voltage is beyond the frequency range for Normal operation
or mains voltage is very low.
A22
INP SEQ FAIL
Phase sequence of input mains voltages is not OK.
A23
REC TMP HIGH
Rectifier block temperature is very high.
A24
REC OVERLOAD
RMS current drawn from any of the input lines exceeds its nominal value.
A25
VDC HIGH
DC bus voltages is higher than its upper limit
A26
VDC LOW
DC bus voltages is lower than its lower limit.
may mean that the battery is empty during Battery mode.
A27
REC NOT ACT
Rectifier is not started due to a fault.
A28
REC BLCK
Rectifier operation is automatically stopped due to a fault.
A30
TESTING BATT
The Battery Test is being performed.
A31
REDUND. LOST
Redundancy lost condition in Parallel System
A33
REC OFF
Rectifier is inactive.
A34
INV OFF
Inverter is inactive.
A35
BYP OFF
Bypass mode is inactive.
A36
BYP PRI HIGH
Priority is Bypass.
A37
BATT DISCHAR
Batteries are discharging after a mains failure.
A38
VDC NOT OK
DC bus voltage is out of its normal range.
A39
T-AMP HIGH
Ambient temperature exceeds its upper limit.
A40
GENSET ON
“Generator Friendly” operation is activated.
A41
EMG STOP ON
Emergency stop is activated.
A42
MINOR ALR
Minor priority alarm.
A43
MAJOR ALR
Major priority alarm.
A44
BATT TS FAIL
Batteries failed in the Battery Test.
A45
BATT CR OPEN
Battery circuit breaker is open.
A47
INV RX T-OUT
Communication between the Inverter and the front panel is lost.
A48
REC RX T-OUT
Communication between the Rectifier and the front panel is lost.