UPS EVO DSP TT
15
User’s Manual
4.1.2 Mimic Panel
Mimic panel is a diagram, which shows the path of energy flow in the UPS by means of several LED’s.
Definitions of LED status are shown below:
LED's
ID
COLOR
DEFINITION
STATE
Line 1
Green
Input mains voltage is OK and Rectifier is active.
Steady
Input mains voltage is OK and Rectifier is inactive.
Flashing
Input mains voltage is very close to its upper/lower limit and Rectifier
is active.
Input mains voltage is not OK.
Off
Line 2
Green
Bypass voltage is OK.
Steady
Bypass voltage is not OK and output voltage is synchronized to the
Bypass voltage.
Flashing
Bypass mains voltage is not OK and output voltage is not synchronized
to the Bypass voltage.
Off
Battery Red
Battery mode is active and battery voltage is OK.
Steady
UPS is performing Battery Test and battery voltage is OK.
Battery mode is active and battery voltage is close to its lower limit
(energy available in the battery is about to be depleted).
Flashing
Battery Test is active and battery voltage is close to its lower limit
(energy available in the battery is about to be depleted).
Rectifier is active and able to supply whole power required by the
Inverter.
Off
Inverter Green
Load is fed via Inverter.
Steady
Inverter is not active.
Off
Load
Green
Load is powered.
Steady
Load is powered but UPS is overloaded.
Flashing
Output voltage is not OK.
Off
Bypass
Yellow
Load is fed via static Bypass line.
Steady
Bypass is not active.
Off
Fault
Red
No alarms.
Off
A minor priority alarm is present.
Flashing
A major priority alarm is present.
Steady
Summary of Contents for EVO DSP TM