START-UP PROCEDURES

Following installation and checking of all electri-
cal and hydraulic connections, the unit may be
turned ON by pressing the green switch posi-
tioned below the control panel.
The display will automatically position a triangu-
lar cursor at the indicator for electric current.
Simultaneously, the relative values of the afore-
mentioned parameters will be displayed.
When humidification is requested, the LED 7)
HUMIDIFY ON is turned ON and the control unit
fills the cylinder with water: the fill led (4) is also
turned on at this point. The operation proceeds
until the correct current value is reached. This
value dependes not only on the steam produc-
tion  imposed but on the conductivity of the feed
water measured by the two small electrodes
positioned on the filling cup as well.
Steam production is factory-set at 70% of maxi-
mum production capacity.

START-UP WITH CONDUCTIVITY OF FEED
WATER SUPERIOR TO 1000 MICROSIEMENS

The humidifier reaches full efficiency immediate-
ly, adjusting water flow to the cylinder to provide
the value of current necessary to produce the
required steam quantity.

START-UP WITH CONDUCTIVITY OF FEED
WATER INFERIOR TO 1000 MICROSIEMENS

The humidifier reaches full efficiency slowly
because it begins on “soft” cycle. This cycle
may last one hour dependent upon the conduc-
tivity; it will proceed until the conductivity reach-
es the projected value. If the scarcely con-
ductible water reaches the top level electrodes
during the filling phase a prealar m (E05)
appears. It is followed by another prealarm
(E02) signalling reduced functionality if the con-
ductibility remains low during successive fill-
ings.
This pre-alarm may persist for a prolonged time
period in cases where conductivity is very low.
The aforementioned pre-alarms do not block the
functioning of the unit and they are turned off
automatically as soon as the conductivity within
the cylinder reaches projected values.
If the situation persist after numerous fillings
(particularly when the humidifier has been in
use for some time) it means that the cylinder
needs cleaning or replacement and on addition-
al alarm (E08) will appear blocking the function-
ing of the unit.

SETTING OF PARAMETERS

As already mentioned, some of the indicators
are only displayed values while others may be

modified by the user:
2) maximum steam production
3) drainage with electrodes whether under cur-
rent or not.
Respositioning of the triangular cursor by using
the pushbutton 12) SEL, the indicators are dis-
played in a clockwise manner in the following
order:
1) - 2) -3) - 4) - 5) - 1)
visualisation lasts for 30 seconds afterwich the
display returns automatically to the initial start
configuration, that is, either current or relative
humidity depending on the model.
In cases of modification of parameters, the
memorization of the new value must be made
within 30 seconds by pressing push-button 12)
SEL.

MAXIMUM STEAM PRODUCTION

Using push-button 12) SEL, position the cursor
at the indicator for max production. The value of
maximum steam production which had been
previously set is visualized and with pushbutton
13) and 14) this value may be either increased
or decreased.
Pressing pushbutton SEL a second time the
new value is memorized and the cursor is posi-
tioned at the indicator 3) CONFIGURATION.

IMPORTANT:

SWITCH TO CHOOSE HUMIDIFICATION
POWER

In “AUT” position the system supplies 30% of
max water vapour delivery which is preset in
phases Iª and IIª of LevControl 1; Iª, IIª, IIIª of
LevControl 2. It supplies the max. water vapour
delivery in phase IIIª of LevControl 1 and in
phase IVª of LevControl 2.
In “MAX” position it always supplied the max.
water vapour delivery.

Note: The “MAX” position must be used only
during the manual leavening phase.

Summary of Contents for T 98 E H4

Page 1: ...Cod 71503313 0 10 2000 OUR SYSTEMS COMPLY WITH EEC DIRECTIVE 73 23 89 336 INSTRUCTION MANUAL S T E A M H U M I D I F I E R S T 98 E H4 GB ...

Page 2: ...ACHINE AND OR COMPONENTS 7 ADJUSTMENT AND SETTING PROCEDURES 8 MACHINE CLEANING AND MAINTENANCE RELATIVE TO THE FOLLOWING PARTS AND COMPONENTS ELECTRICAL ELECTRONIC MECHANICAL COOLING SYSTEM W W W WA A A AR R R RN N N NI I I IN N N NG G G G MACHINE USER IS SEVERELY PROHIBITED FROM CARRYING OUT THE FOLLOWING OPERATIONS AS WELL AS THOSE MARKED WITH THIS SYMBOL ...

Page 3: ... ABSORPTION TYPE OF CONTROL AMPEROMETRIC TRANSFORMER TAM THREE PHASE 1 E400TA 1 24 V50 60 Hz 30 VA CDP 100 Kg h I W Kg h I W Kg h I W K I W 220 V 240 V 380 V 415 V POWER SUPPLY VOLTAGE 8 8 8 5800 8 8 5800 OPERATING TEMPERATURE RANGE C FEED WATER PRESSURE AIR DUCT PRESSURE RESISTANCE CONDUCTIVITY OF FEED WATER 0 40 C 1 10 bar 200 mm H20 800 800Ω 125 1250 µS cm ...

Page 4: ...d allowing water to fill the feed tank from which it descends by the force of gravity to the inside of the cylinder The two small top level electrodes positioned at the top of the cylinder control that the water level does not supersede the maximum value Beyond this maximum value water is dis charged through the overflow pipe of the feed tank The other two electrodes positioned on the feed tank me...

Page 5: ... as shown in figure Some of the indicators are simply displayd val ues while others blink on and off when dis played and are parameters that may be modi fied by the user see section on modifiable functional Iparameters A great number indicators are shown 1 absorbed current 2 desired production Kg h 3 unit configuration visualisation of humidifi er model power supply voltage number of phases nomina...

Page 6: ...ntioned pre alarms do not block the functioning of the unit and they are turned off automatically as soon as the conductivity within the cylinder reaches projected values If the situation persist after numerous fillings particularly when the humidifier has been in use for some time it means that the cylinder needs cleaning or replacement and on addition al alarm E08 will appear blocking the functi...

Page 7: ...n already signalled by a prealarm which does not allow the continua tion of regular steam production eg cylinder exhausted It may appear following a temporary situation voltage excess lack of water etc which requires intervention of personnel The alarm consist of visualisation on the display or eventual trans mission via serial line on the relative code blocking of the humidifying function reset i...

Page 8: ...om filter Remove scale and calcareous deposits under a jet of water and clean grids mechanically or chem ically with a commercially available cleaner When electrode wear is such that regenera tion is insufficient the boiler must be replaced Exchange only involves the body of the boiler and the gasket The ring nut connection piece and filer do not deteriorate with use Reassemble the boiler in reser...

Reviews: