THE USER MUST NOT INTERVENE SHOULD ANY OF THE FOLLOWING
MACHINE MALFUNCTIONS OCCUR.
IT IS OBLIGATORY TO CONTACT AN AUTHORIZED TECNOMAC
TECHNICIAN.
1. THE CONTROL PANEL IS NOT WORKING
2. THE HEATING SYSTEM IS NOT WORKING
3.
IN ANY OTHER CASE OF IRREGULAR FUNCTIONING
5. ALARMS AND PRE-ALARMS
PRE-ALARM
Functions to advise the user via display or seri-
al line, of particular situations regarding unit
functioning. The control continues to regulate
the production on steam compatible with the
newly signalled situation (alarm level, reduced
functionality, etc.) and verifies whether or not
the cuse of the prealarm has disappeared
and/or the production of steam may be allowed
the return gradually to the required value. On
the contrary, after a certain time an alarm is
signalled.
The pre-alarm consists of:
– visualisation on the display or eventual trans-
mission via serial line of the relative alarm
code.
ALARM
The alarm is activated following the duration of
a particularity of function, already signalled by
a prealarm, which does not allow the continua-
tion of regular steam production (eg, cylinder
exhausted).
It may appear following a temporary situation
(voltage excess, lack of water, etc.) which
requires intervention of personnel.
The alarm consist of:
– visualisation on the display or eventual trans-
mission via serial line on the relative code;
– blocking of the humidifying function (reset is
automatic for E11 and E12 when relative
humidity returns within set limits);
– activation of alarm relay;
– lighting of alarm led 9)
– total draining of water (with the exception of
alarms E31, E32, E11, E12).
ALARMS - TROUBLE SHOOTING
The purpose of the following table is to help the
user to identify the cause of eventual malfunc-
tions and to indicate the necessary procedure
in case of block in humidifier function.
By pressing the pushbutton 10) RESET follow-
ing an alarm, the humidifier resumes activity. If
the cause of the alarm persists however, within
a short time the humidifier will stop again.
In any case it is advisable, before re-starting
the humidifier by pressing the 10) RESET but-
ton, to consult the possible remedies suggest-
ed in the following table in order to avoid
unnecessary loss of time or actions that may
damage the unit.