THIS PROCEDURE MAY ONLY BE DONE

BY AN AUTHORISED TECNOMAC

INSTALLATION TECHNICIAN

WIRING

GENERAL RULES

– Check that supply voltage corresponds to

rated voltage of humidifier;

– when wiring, respect minimum values for

supply cable section as suggested in the
table below;

– Protect equipment with fuses or automatic

switches, preferably according to values
shown in table below.

MODEL

T98 EH4

Instant max. capacity of intake water I./min.

Feed water attachment

Instant max. capacity of discharge water I./min.

Discharge water attachment (mm.)

Min. diam. of discharge piping

2,5

3/4” M

1,6

30

3/4”

4. START-UP

CONTROL PANEL

The control panel with the functions of humidity
regulation incorporated, offers additional func-
tions and indicators as shown in figure:
Some of the indicators are simply displayd val-
ues while others blink on and off when dis-

played and are parameters that may be modi-
fied by the user (see section on modifiable
functional Iparameters).
A great number indicators are shown: 

1) absorbed current
2) desired production Kg/h
3) unit configuration: visualisation of humidifi-

er model, power supply voltage, number
of phases, nominal current, amperometric
transformer, control model, drainage under
tension or timed

4) alarms, pre-alarms
5) conductivity relative to feed water (*)

INDICATING LED

6) indicating led of water charge
7) indicating led of humidification ON
8) indicating led of water drainage
9) indicating led of alarm

BUTTONS
10) reset button
11) manual drainage button
12) button for selection of parameter to be dis-

played

13) button for increase of displayed value
14) button for decrease of displayed value.
(*) The conductivity value display is a relative
value as it depends on temperature.

4

3

1

2

13

6

8

11

14

5

7

9

10

12

Summary of Contents for T 98 E H4

Page 1: ...Cod 71503313 0 10 2000 OUR SYSTEMS COMPLY WITH EEC DIRECTIVE 73 23 89 336 INSTRUCTION MANUAL S T E A M H U M I D I F I E R S T 98 E H4 GB ...

Page 2: ...ACHINE AND OR COMPONENTS 7 ADJUSTMENT AND SETTING PROCEDURES 8 MACHINE CLEANING AND MAINTENANCE RELATIVE TO THE FOLLOWING PARTS AND COMPONENTS ELECTRICAL ELECTRONIC MECHANICAL COOLING SYSTEM W W W WA A A AR R R RN N N NI I I IN N N NG G G G MACHINE USER IS SEVERELY PROHIBITED FROM CARRYING OUT THE FOLLOWING OPERATIONS AS WELL AS THOSE MARKED WITH THIS SYMBOL ...

Page 3: ... ABSORPTION TYPE OF CONTROL AMPEROMETRIC TRANSFORMER TAM THREE PHASE 1 E400TA 1 24 V50 60 Hz 30 VA CDP 100 Kg h I W Kg h I W Kg h I W K I W 220 V 240 V 380 V 415 V POWER SUPPLY VOLTAGE 8 8 8 5800 8 8 5800 OPERATING TEMPERATURE RANGE C FEED WATER PRESSURE AIR DUCT PRESSURE RESISTANCE CONDUCTIVITY OF FEED WATER 0 40 C 1 10 bar 200 mm H20 800 800Ω 125 1250 µS cm ...

Page 4: ...d allowing water to fill the feed tank from which it descends by the force of gravity to the inside of the cylinder The two small top level electrodes positioned at the top of the cylinder control that the water level does not supersede the maximum value Beyond this maximum value water is dis charged through the overflow pipe of the feed tank The other two electrodes positioned on the feed tank me...

Page 5: ... as shown in figure Some of the indicators are simply displayd val ues while others blink on and off when dis played and are parameters that may be modi fied by the user see section on modifiable functional Iparameters A great number indicators are shown 1 absorbed current 2 desired production Kg h 3 unit configuration visualisation of humidifi er model power supply voltage number of phases nomina...

Page 6: ...ntioned pre alarms do not block the functioning of the unit and they are turned off automatically as soon as the conductivity within the cylinder reaches projected values If the situation persist after numerous fillings particularly when the humidifier has been in use for some time it means that the cylinder needs cleaning or replacement and on addition al alarm E08 will appear blocking the functi...

Page 7: ...n already signalled by a prealarm which does not allow the continua tion of regular steam production eg cylinder exhausted It may appear following a temporary situation voltage excess lack of water etc which requires intervention of personnel The alarm consist of visualisation on the display or eventual trans mission via serial line on the relative code blocking of the humidifying function reset i...

Page 8: ...om filter Remove scale and calcareous deposits under a jet of water and clean grids mechanically or chem ically with a commercially available cleaner When electrode wear is such that regenera tion is insufficient the boiler must be replaced Exchange only involves the body of the boiler and the gasket The ring nut connection piece and filer do not deteriorate with use Reassemble the boiler in reser...

Reviews: