Tecnologic THP 96 Operating Instructions Manual Download Page 6

5 - Led OUT2 

: Signalize when the output OUT2 is on (on) or off (off) and

signalize the set point 2 programming mode (flashing)

6 - Led - Shift index:

 

Signalize Process value lower than 5 units of Set

Point value (flashing) or Process value lower within 5 units in respect of
Set Point value (on)

7 - Led = Shift index:

 

Signalize Process value equal to  Set Point value

8 - Led + Shift index:

 

Signalize Process value upper than 5 units of Set

Point value (flashing) or Process value upper within 5 units in respect of
Set Point value (on)

1.2 - INSTRUMENT CODE
THP 96  a b c d ee
a = SUPPLY

Y : 24 VDC (V1)
O : 24 (V1) 

,

 48 (V2) VAC

N : 110 (V1) 

,

 230 (V2) VAC

b = INPUT

C : Termocouples (J, K, S)
D : Termoresistances (Pt100, Ni100 IEC)
E : Termistors PTC (KTY 81)
F : Normalized signals 4..20 mA
A : Normalized signals 0..20 mA
V : Normalized signals 0..10 V

c = OUTPUT OUT1

R :  Relay
O : Voltage output 12 VDC for SSR

d = OUTPUT OUT2

R :  Relay
O : Voltage output 12 VDC for SSR
- : Output not present

ee = SPECIAL CODES

2 - TECHNICAL DATA
ELECTRICAL DATA

Supply: 24 VDC (V1), 24(V1)

48(V2), 110(V1)

230(V2)  VAC +/- 10%

Frequency AC: 50/60 Hz
Power consumption: 4 VA approx.
Input/s: 1 input. For temperature probes tc  J, K, S or RTD Pt 100 IEC, Ni
100 or PTC (KTY 81-121 990 

 at 25 °C) or for normalized signals 4..20

mA, 0..20 mA o 0..10 V
Output/s: Up to 2 outputs. Relay (8A-AC1, 3A-AC3 250 VAC) ; or voltage
for SSR drive (12 VDC/15 mA)
Auxiliary supply output: 10 VDC / 20 mA Max (only for norm. sign..)
Electrical life for relay output: 100000 operat.
Protection class against electric shock:  Class II for Front panel
Insulation:

 

Reinforced insulation between the low voltage section (supply

and relay outputs) and the front panel; Reinforced insulation between the
low voltage section (supply and relay outputs) and the extra low voltage
section (input and output for SSR); No insulation between input and output
for SSR driving

MECHANICAL DATA

Housing: Self-extinguishing plastic, UL 94 V0
Dimensions: 96 x 96 mm DIN, depht 73 mm
Weight: 330 g approx.
Mounting: Flush in panel in 90 x 90  mm hole
Connections:  extractable 2,5 mm

2

 screw terminal block

Degree of protection of front panel : IP 54 mounted in panel with gasket
Pollution situation: Normal
Operating temperature:  0 ... 55 °C
Operating humidity: 30 ... 95 RH% without condesation
Storage temperature: -10 ... +60 °C

FUNCTIONAL DATA

Control: ON/OFF, NEUTRAL ZONE, PID
Measurement range: according to the used probe (see table range)
Display resolution: according to the probe used  1/0,1/5/0,5
Overall accuracy: +/- 0,5 % fs
Sampling rate: 1 sample per second
Action: 1C type according to EN 60730-1
Compliance: ECC directive EMC 89/336 (EN 50081-1, EN 50082-1), ECC
directive LV 73/23 and 93/68 (EN 60730-1)

MEASUREMENT RANGE TABLE

-99.9 ... 700.0

- 999 ... 7000

4..20 mA, 0..20 mA,

0..10 V

 

(gener.)

---

0 ... +1600 °C

+32 ... +2912 °F

tc S (rh)

---

0 ... +1200 °C

+32 ... +2192 °F

tc K (Cr)

---

0 ... +800 °C

+32 ... 1472 °F

tc J (FE)

-50.0 ... +150.0 °C

-58.0 ... +302.0 °F

-50 ... +150 °C

-58 ... +302 °F

Ni 100 (ni)

-99.9 ... +600.0 °C

-99.9 ... +999.9 °F

-100 ... +600 °C

-148 ... +1112 °F

Pt 100 (Pt)

-50.0 ... +150.0 °C

-58.0 ... +302.0 °F

-50 ... +150 °C

-58 ... +302 °F

PTC

4 DIGIT with D.P.

4 DIGIT 

PROBE

3 - INSTALLATION
MECHANICAL MOUNTING

:

  The instrument, in  DIN case 96 x 96 mm,

is designed for panel mounting. Make an hole 90 x 90 mm and insert the
instrument, fixing  it with the provided special brackets . We recommend to
mount the  gasket to obtain an IP 54 front protection. Avoid to place the
instrument in areas with  humidity or dirt. Connect the instrument as far as
possible from source of electromagnetic disturbances so as motors, power
relays, relays, electrovalves,etc. 

ELECTRICAL  CONNECTIONS

: Carry out the electrical wiring

connecting only one wire for each terminal , according to the following
diagram, check that the power supply is the same as indicated on the
instrument and the loads current is not upper than the maximum current
admitted. The instrument, being a built in equipment with permanent
connection into a cabinet, is not furnished with internal device protecting  
from  overcurrent : it's recommended , therefore, to properly protect all the
electric circuits connected to the instrument, with devices (ex. fuses)
proportionate to the circulating currents. It's strongly recommended to use
cables with proper insulation, according to the working voltages and  
temperatures. Furthermore, the input cable of the probe has to be kept
separate from line voltage wiring. If the input cable of the probe is
screened, it has to be connected on the ground with only one side. It is
advisable to check that the parameters are those desired before connecting
the outputs to the actuators so as to avoid malfunctioning . Whenever a
failure of the instrument could cause dangerous or damaging situations, it
should be kept in mind that the plant has to be provided with additional
devices to ensure the safety.

4 - OPERATING MODE

4.1 - ON/OFF CONTROL

The control mode of the instrument by ON/OFF mode occours on  the
outputs according to the Sets point fixed, to the differential switching
points (par. "d1", "d2") and to operating modes (par. "HC1", "HC2")
programmed. For a correct functioning it is necessary to set a negative
differential switching point for reverse controls (ex.Heating processes) and

TECNOLOGIC - THP 96

 

 USER MANUAL (I - GB) - Vr. 02   - ISTR 00997  - PAG. 6

Summary of Contents for THP 96

Page 1: ... exclusive property of TECNOLOGIC S p A which forbids any reproduction and divulgation although partial if not expressly authorised TECNOLOGIC S p A reserves the right to execute aesthetically and functional modifications at any moment and without any notice INDICE PROBLEMI MANUTENZIONE E GARANZIA 7 TABELLA PARAMETRI 6 1 DESCRIZIONE DEI PARAMETRI 6 IMPOSTAZIONE DEI LIMITI DI INGRESSO 5 3 PROGRAMMA...

Page 2: ...5 C Umidità ambiente di funzionamento 30 95 RH senza condensazione Temperatura di trasporto e immagazzinaggio 10 60 C CARATTERISTICHE FUNZIONALI Regolazione ON OFF ZONA NEUTRA PID Range di misura Secondo la sonda utilizzata vedi tabella Risoluzione visualizzazione Secondo la sonda utilizzata 1 0 1 5 0 5 Precisione totale 0 5 fs Velocità di acquisizione 1 acquisizione al secondo Azione tipo 1C seco...

Page 3: ...di ciclo dell uscita Per il termine INTEGRALE It Tempo Integrale Per il termine DERIVATIVO dt Tempo derivativo Lo strumento è impostato in fabbrica con i parametri relativi alla regolazione PID su valori standard Qualora questi non dovessero risultare ottimali per la regolazione si consiglia di attivare la funzione di AUTOTUNING che permette la sintonizzazione dello strumento per la regolazione PI...

Page 4: ...INIMO 2 Valore minimo impostabile come Set2 o limite inferiore del Set2 HS1 SET MASSIMO 1 Valore massimo impostabile come Set1 o limite superiore del Set1 HS2 SET MASSIMO 2 Valore massimo impostabile come Set2 o limite superiore del Set2 Pb BANDA PROPORZIONALE Ampiezza della banda intorno al Set1 nella quale interviene la regolazione proporzionale It TEMPO INTEGRALE Tempo integrale da impostare ne...

Page 5: ...messaggi di errore sonda EEEE in caso la sonda sia interrotta o in overrange oppure nel caso la sonda PTC RTD o per segnali normalizzati sia in cortocircuito o in underrange in tal caso verificare la corretta connessione della sonda con lo strumento e successivamente procedere alla verifica della stessa Nelle condizioni di errore tutte le uscite sono disattivate PULIZIA Si raccomanda di evitare l ...

Page 6: ...e per second Action 1C type according to EN 60730 1 Compliance ECC directive EMC 89 336 EN 50081 1 EN 50082 1 ECC directive LV 73 23 and 93 68 EN 60730 1 MEASUREMENT RANGE TABLE 99 9 700 0 999 7000 4 20 mA 0 20 mA 0 10 V gener 0 1600 C 32 2912 F tc S rh 0 1200 C 32 2192 F tc K Cr 0 800 C 32 1472 F tc J FE 50 0 150 0 C 58 0 302 0 F 50 150 C 58 302 F Ni 100 ni 99 9 600 0 C 99 9 999 9 F 100 600 C 148...

Page 7: ...of 4 hours after this time if the Autotuning is not completed the instrument automatically get out from the procedure showing constantly on the display the EEE indication To stop the Autotuning cycle or re establish the normal functioning after an error switch off and on the instrument The calculated values will be automatically memorised by the instrument at the end of the Autotuning cycle in the...

Page 8: ... selection of one of possible control modes that the instrument offers ON OFF on PID Pi or Neutral Zone nr PSE INPUT PROBE Allows selecting if the instrument type is for thermocouples or for thermoresistances various types of probe J FE K Cr S rh for thermocouples and Pt100 Pt Ni100 ni for thermoresistances On changing this parameter it is to be remember that the exit programming phase is to be ca...

Page 9: ...ivated HOW TO CLEAN We recommend to avoid abrasive cleaners or containing solvents which could damage the instrument WARRANTY AND REPAIRS The instrument is under warranty against construction vices or defected material noticed within 12 months from delivery date The warranty is limited to the repairs or to the substitution of the instrument The eventual opening of the housing the violation of the ...