After the password ‘PA2’ has been putted in, press the 

 and 

 keys to scroll through to the required function (e.g. UL). Press the 

 key to 

execute the upload. If the operation is successful, the display will show ‘

y

’, if not it will show ‘

n

’.

Upload (UL)

 This function uploads the programming parameters from the device. 

 

  UPLOAD: device 

 Copy Card

Format (Fr)

 This command is used to format the copy card, an operation which is necessary when using the card for the first time. 

Important

when the copy card has been programmed, the parameter ‘

Fr

’ will delete all data that have been entered. This operation cannot be cancelled. 

Download from reset:

Connect the copy card when the device is switched off. When

the device is switched on, the download from the copy card will

begin automatically. At the end of the lamp test, the display will

show ‘

dLy

’ if the operation was successful and ‘

dLn

’ if not.

  

 DOWNLOAD: Copy Card 

 device

NOTES:

- after the parameters have been downloaded, the device uses the downloaded parameter map settings.

MAX AND MIN TEMPERATURE ALARM

LAL

AFd

HAL

AFd

Setpoint - LAL 

AFd 

Off

Se HAL 

AFd

1

Setpoint - LAL + AFd

Setpoint  + HAL - AFd

Setpoint

LAL + AFd

HAL - AFd

LAL

AFd

HAL

AFd

Setpoint - LAL 

AFd 

Off

Se HAL 

AFd

1

Setpoint - LAL + AFd

Setpoint  + HAL - AFd

Setpoint

LAL + AFd

HAL - AFd

Relative Temperature

Value to setpoint (Att=1)

Absolute Temperature

Value (Att=0)

 Temp. ≤ 

Set + LAL 

(only with 

LAL<0

*)

 Temp. ≥ 

Set + HAL 

(only with 

HAL>0*

*)

 Temp. ≥ 

Set + LAL + AFd 

o

  

≥ 

Set - 

I

LAL

I

 + AFd 

(LAL < 0*)

 Temp. ≤ 

Set + HAL - AFd 

(HAL > 0**)

 Temp. ≤ 

LAL 

(

LAL

 with sign)

 Temp. ≥ 

HAL 

(

HAL

 with sign)

 Temp. ≥ 

LAL + AFd

 Temp. ≤ 

HAL - AFd

Minimum temperature alarm

Maximum temperature alarm

Returning from minimum 

temp. alarm

Returning from maximum 

temp. alarm

*  if LAL is negative, Set + LAL < Set

**  if HAL is negative, Set + HAL > Set

ELECTRICAL WIRING

Attention! Never work on electrical connections when the machine is switched on.

The device is equipped with screw or removable terminals for connecting electric cables with a diameter of 2.5mm

2

 (one wire per terminal for power 

connections). For the capacity of the terminals, see the label on the instrument. Do not exceed the maximum current allowed; in case of higher loads, 

use an appropriate contactor. Make sure the power supply voltage complies with the one required by the instrument. Probes have no connection 

polarity and can be extended using a regular bipolar cable (note that the extension of the probes affects the EMC electromagnetic compatibility of 

the instrument: pay extreme attention to wiring). Probe cables, power supply cables and the TTL serial cables should be distant from power cables.

RESPONSIBILITY AND RESIDUAL RISKS

ELIWELL CONTROLS SRL shall not be liable for any damages deriving from:

 - installation/use other than that prescribed and, in particular, that which does not comply with safety standards anticipated by regulations and/or those given herein;

 - use on boards which do not guarantee adequate protection against electric shock, water or dust under the conditions of assembly applied;

 - use on boards which allow access to dangerous parts without the use of tools;

 - tampering with and/or alteration of the products;

 - installation/use on boards that do not comply with the standards and regulations in force.

DISCLAIMER

This manual and its contents remain the sole property of ELIWELL CONTROLS SRL, and shall not be reproduced or distributed without authorization 

by ELIWELL CONTROLS SRL. Although great care has been exercised in the preparation of this document, ELIWELL CONTROLS SRL, its employees or 

its vendors, cannot accept any liability whatsoever connected with its use. The same applies to any person or company involved in preparing and 

editing this document. ELIWELL CONTROLS SRL reserves the right to make any changes or improvements without prior notice.

Summary of Contents for M 1000 VC

Page 1: ...018 Vetrine refrigerate Refrigerated serve over displays Refrig ere mueble Kuehl vitrinen MANUALE D USO E MANUTENZIONE USER AND MAINTENANCE MANUAL MANUEL D INSTALLATION E DE FONCTIONNEMENT BEDIENUNGS...

Page 2: ...uttore oppure da persone esperte Se il cavo di alimentazione danneggiato esso deve essere sostituito dal costruttore o dal suo servizio assistenza tecnica o comunque da una persona con qualifica simil...

Page 3: ...SOSTITUZIONEVETRO FRONTALE LATERALE MENSOLE Pag 15 6 3 SOSTITUZIONE ILLUMINAZIONE Pag 15 6 4 SOSTITUZIONE MOTOVENTILATORE Pag 16 6 5 SOSTITUZIONE COMPRESSORE GAS REFRIGERANTE Pag 16 6 6 MOBILE CON SBR...

Page 4: ...to e o manutentore per compie re in modo corretto e sicuro tutte le operazioni di installazione messa in funzione smontaggio e smaltimento dell apparecchio Questo manuale d uso e manutenzione contiene...

Page 5: ...sono disponibili con 2 finiture differenti VERSIONE BASSO Fiancate coibentate basse fino a terra spessore 40 mm e frontale basso fino a terra VERSIONE ALTO Fiancate coibentate alte da terra spessore...

Page 6: ...ati nella tabella lunghezza peso APPENDICE 5 pag 58 Il produttore declina ogni responsabilit per operazioni logistiche svolte senza ll rispetto delle norme di sicurezza 1 3 IMBALLO Alla consegna verif...

Page 7: ...amento dell unit refrigerante Prestare attenzione in presenza di una pedana posizionata posteriormente al mobile frigorifero verificarne la sua altezza in modo che questa non ostruisca le prese d aria...

Page 8: ...essere collocato al riparo degli agenti atmosferici evitando di utilizzare il sito come deposito di materiali A seconda delle caratteristiche del modello dell unita condensatrice remota si devono ris...

Page 9: ...a del mobile ad una prolunga e o riduttore 2 2 MESSA IN FUNZIONE ED UTILIZZO ATTENZIONE Attenzione prima di effettuare l avviamento accertarsi che non vengano eseguite le operazioni con mani umide o b...

Page 10: ...orcizia Fare attenzione durante le operazioni di pulizia della vasca del mobile frigorifero bisogna porre attenzione a non ferirsi con le alette dell evaporatore che visto il loro spessore ridotto son...

Page 11: ...di sistema automatico per lo sbrinamento periodico giornaliero gi impostato in fabbrica e modificabile in numero durata ed intervallo agendo sul pannello di controllo tale operazione deve essere esegu...

Page 12: ...strettamente necessario al carico dei prodotti Caricando eccessivamente il mobile di prodotto da raffreddare si peggiorano tutte le condizioni di funzionamento rischiando di danneggiare i prodotti gi...

Page 13: ...fero in posizione perfettamente orizzon tale agendo se necessario sulla regolazione dei piedini a vite sulle gambe del banco per regolarne il livello e verificare la planarit con una bolla 1 4 POSIZIO...

Page 14: ...2 sezioni con le viti da A alla C nelle apposite predisposi zioni al fissaggio Unire le plafoniere porta luce rivettando le 2 estremit in lamiera predisposte E Una volta unite le 2 sezioni Rimuovere...

Page 15: ...mobili dotati di pistoni 6 2 SOSTITUZIONEVETRO FRONTALE LATERALE MENSOLE Nel caso di danneggiamento e o sostituzione del vetro frontale vetro laterale lato spalla della vetrina recuperare i frammenti...

Page 16: ...inamento elettrico attenzione a non scottarsi sulla resistenza elettrica che potrebbe risultare ancora calda Aspettare quindi il suo raffreddamento e successivamente iniziare le operazioni di manutenz...

Page 17: ...are dell EUT possibili opzioni C con unit compressore S senza unit compressore N senza unit compressore and without other electric components appliance provide only with internai light expositor unit...

Page 18: ...rilasciare Scorre le voci del menu Decrementa i valori Premere per almeno 5 sec Funzione configurabile dall utente par H32 SET ENTER Premere e rilasciare Visualizza eventuali allarmi se presenti Acce...

Page 19: ...cedura usata per il blocco MENU DI PROGRAMMAZIONE Per entrare nel menu Programmazione premere per oltre 5 secondi il tasto Se previsto verr richiesta una PASSWORD di accesso PA1 vedi paragrafo PASSWOR...

Page 20: ...tempo maggiore di tdO Registrazione label Opd nella cartella AL Icona Allarme fissa Blocco del regolatore chiudere la porta funzione ritardo definita da OAO Ad2 Sbrinamento per time out fine sbriname...

Page 21: ...one eseguita e dLn per operazione fallita DOWNLOAD Copy Card strumento NOTE dopo le operazioni di Download lo strumento funzioner con le impostazioni della nuova mappa appena caricata ALLARME DI TEMPE...

Page 22: ...tronico da incorporare secondo le caratteristiche del funzionamento automatico come dispositivo di comando ad azione di tipo 1 B come dispositivo di classe A in relazione alla classe e struttura del s...

Page 23: ...2 sbrinamento con la modalit Free sbrinamento indipendente dal compressore dit 1 2 defrost interval time Tempo di intervallo fra l inizio di due sbrinamenti successivi dCt 2 defrost Counting type Sele...

Page 24: ...e fino al successivo raggiungimento del valore di Setpoint 2 visualizza la label dEF durante lo sbrinamento e fino al successivo raggiungimento del valore di Setpoint dro 2 display read out Seleziona...

Page 25: ...250 30 min 1 2 dSt 50 0 150 8 0 C F 1 2 dPO n y n n y n flag 2 FPt 0 1 0 flag 2 FSt 50 0 150 50 0 C F 1 2 FAd 1 0 50 0 2 0 C F 2 Fdt 0 250 0 min 1 2 dt 0 250 0 min 1 2 dFd n y y flag 1 2 FCO n y y fl...

Page 26: ...e service When parts are being replaced and when removal of the plug is foreseen and removal of the plug is clearly indicated it must be such that an operator may check from any point to which he has...

Page 27: ...CHECKS Pag 39 6 2 GLASS REPLACEMENT Pag 39 6 3 TOP CANOPY AND SHELVES LIGHTINGS REPLACEMENT Pag 39 6 4 MOTOR FAN REPLACEMENT Pag 40 6 5 COMPRESSOR REFRIGERANT GAS REPLACEMENT Pag 40 6 6 UNIT FITTED W...

Page 28: ...staff so that the same can carry out correctly and securely all the operations of installation implementation commissioning dismantling and disposal of the appliance This user and maintenance manual...

Page 29: ...o the floor 40 mm thick and short front panel down to the floor TALLVERSION Tall insulated side panels from the floor 40 mm thick and tall front panel from the floor The model SERIES M 1000 includes M...

Page 30: ...he unloading positioning and installation procedures of the Re frigerated Serve over Display inside the shop kitchen according to the model of the Refrigerated Serve over Display please read carefully...

Page 31: ...rectly exposed to air from fans vents or fan coil unit air conditioner Do not block or obstruct the air inlets of the built in refrigeration unit Do not place any objects on the unit including boxes o...

Page 32: ...ter energy consumption If the Refrigerated Serve over Display that is fitted with built in condenser is tilted make sure to wait at least eight hours before starting the unit this time will allow the...

Page 33: ...l assistance service or however by a person with similar qualifications so as to avoid all risks No liability whatsoever can be accepted if the above instructions in not complied with 8 In order to pr...

Page 34: ...mpletely powered off Never use high pressure water jet to wash internal parts of the Refrigerated Serve over Display as electrical parts could be damaged Only use warm water with non aggressive deterg...

Page 35: ...ording to local legislation provided that they are under strict supervision by a tutor and are adults as mentioned above In other words trainees must be in normal physical and psychological condition...

Page 36: ...he following when the doors are opened cold air is released and therefore it is advisable to limit opening the doors and only do so for the time required to load products Storing non frozen products w...

Page 37: ...frigorifero in posizione perfettamente orizzon tale agendo se necessario sulla regolazione dei piedini a vite sulle gambe del banco per regolarne il livello e verificare la planarit con una bolla 1 4...

Page 38: ...e cabinet closer together fix the 2 sections with the screws from A to C in the appropriate fixing positions Join the canopy lights by riveting the presetted joints on it E Once the 2 sections have be...

Page 39: ...rectly clean the condenser of the refrigeration unit 6 2 GLASS REPLACEMENT In case of replacement or damage of the front of glass side glass shelf glass do not dissipate them on the environment Glass...

Page 40: ...open the circuit breaker upstream of the connection of the Refrigerator unit Then replace ATTENTION In the equipments with electric defrosting system pay attention to the electrical heating element t...

Page 41: ...0140 length 140 cm 0150 length 150 cm 0180 length 180 cm 0182 length 182 cm 0200 length 200 cm 0240 length 240 cm 0250 length 250 cm 0262 length 262 cm 0280 length 280 cm 0300 length 300 cm 0350 lengt...

Page 42: ...d release Displays alarms if active Opens the Machine Status menu Press for at least 5 secs Opens the Programming menu Confirms commands SET Reduced SET LED Flashing reduced set active Quick flashing...

Page 43: ...To access the Programming menu press for at least 5 secs the key If specified the PA1 access PASSWORD will be requested see PASSWORD paragraph At the access the display will show the first parameter d...

Page 44: ...eachingthedefrostendtemperature detectedbythePb2probe RegistrationAd2labelintheALfolder AlarmiconpermanentlyON waituntilthenextdefrostforautomaticreturn MANUAL DEFROST CYCLE ACTIVATION To manually act...

Page 45: ...ention Never work on electrical connections when the machine is switched on The device is equipped with screw or removable terminals for connecting electric cables with a diameter of 2 5mm2 one wire p...

Page 46: ...meter of 2 5mm2 Connectors TTL for connection to Copy Card Temperature Operating 5 55 C Storage 30 85 C Humidity Operating Storage 10 90 RH not condensing Electrical Caracteristics Power Supply 230Vac...

Page 47: ...s on and start everytime the instrument switch on 2 compressor stop Each time the compressor stops a defrosting cycle is performed according to parameter dtY dOH 2 defrost Offset Hour Start of defrost...

Page 48: ...TE the switch between C and F DO NOT modify setpoint differential etc for example set 10 C become 10 F ddd 2 Selection of type of value to be displayed 0 Setpoint 1 cold room probe Pb1 2 evaporator pr...

Page 49: ...0 30 min 1 2 dSt 50 0 150 8 0 C F 1 2 dPO n y n n y n flag 2 FPt 0 1 0 flag 2 FSt 50 0 150 50 0 C F 1 2 FAd 1 0 50 0 2 0 C F 2 Fdt 0 250 0 min 1 2 dt 0 250 0 min 1 2 dFd n y y flag 1 2 FCO n y y flag...

Page 50: ...CONFORMITY DECLARATION DE CONFORMIT KONFORMIT TSERKL RUNG FARE RIFERIMENTO ALLA DICHIARAZIONE CE CHE ACCOMPAGNA IL PRODOTTO REFERTO CE DECLARATION ACCOMPANYINGTHE PRODUCT REPORTEZ VOUS LA D CLARATION...

Page 51: ...CARICA GAS GAS LOAD kg CARICA GAS GAS LOAD kg GWP 3 985 GWP 2 141 CO2 CO2 x x APPENDICE 2 ATTREZZATURA CON GAS FLUORURATI AD EFFETTO SERRA EQUIPMENT WITH FLUORINATED GREENHOUSE GASES QUIPEMENT AVEC GA...

Page 52: ...nella prossima pagina The plate defines all the technical data of the Refrigerated Serve over Display as showed on the table in the next page L tiquette d finit toutes les donnes techniques sur le pro...

Page 53: ...Kosten Cantidad de refrigerante 10 Pot elettrica illuminazione Watt top lighting total Electrical power Puissance total de la lumi re Elektrische Leistung von licht Potencia electrica de iluminacion...

Page 54: ...e manutenzione 54 9 10 11 1 1 7 6 5 8 2 2 3 3 3 3 4 SERIE M 800 900 1000 APPENDICE 4 DESCRIZIONE PARTI DEL MOBILE FRIGORIFERO CLOSE MULTIDECK DISPLAY PARTS DESCRIPTION DESCRIPTION DU MEUBLE FRIGO BES...

Page 55: ...terung Soporte delantero 6 Vetro frontale Front glass Fa ade en verre Frontscheibe Vidrio frontal 7 Mensola in vetro Intermediary glass shelf Tablette en verre Glasboden Estante de cristal 8 Plafonier...

Page 56: ...e manutenzione 56 9 12 12 10 11 5 1 7 6 5 5 8 2 2 3 3 3 4 APPENDICE 4 DESCRIZIONE PARTI DEL MOBILE FRIGORIFERO CLOSE MULTIDECK DISPLAY PARTS DESCRIPTION DESCRIPTION DU MEUBLE FRIGO BESCHREIBUNG DERTEI...

Page 57: ...avant Vordere Halterung Soporte delantero 6 Vetro frontale Front glass Fa ade en verre Frontscheibe Vidrio frontal 7 Mensola in vetro Intermediary glass shelf Tablette en verre Glasboden Estante de cr...

Page 58: ...at In der Phase von Auftauen W A 1050 4 4 1320 5 5 1610 6 7 2060 8 5 2190 9 1 2800 11 6 2800 11 6 3340 13 9 4120 17 2 Potenza assorbita dall illuminazione dotazione standard Power absorbed by lighting...

Page 59: ...rage Erforderliche Gesamtleistung Standardausstattung ohne aggregat In der Phase von Auftauen W A 1050 4 4 1320 5 5 1610 6 7 2060 8 5 2190 9 1 2800 11 6 2800 11 6 3340 13 9 4120 17 2 Potenza assorbita...

Page 60: ...d givrage Erforderliche Gesamtleistung Standardausstattung ohne aggregat In der Phase von Auftauen W A 1050 4 4 1320 5 5 1610 6 7 2060 8 5 2190 9 1 2800 11 6 2800 11 6 3340 13 9 4120 17 2 Potenza asso...

Page 61: ...age Erforderliche Gesamtleistung Standardausstattung ohne aggregat In der Phase von Auftauen W A 1050 4 4 1320 5 5 1610 6 7 2060 8 5 2190 9 1 2800 11 6 2800 11 6 3340 13 9 4120 17 2 Potenza assorbita...

Page 62: ...porato dotazione standard In fase di sbrinamento Total absorbed power built in unit standard version In defrosting phase Puissance absorb e totale groupe log quipement standard en phase ded givrage Er...

Page 63: ...porato dotazione standard In fase di sbrinamento Total absorbed power built in unit standard version In defrosting phase Puissance absorb e totale groupe log quipement standard en phase ded givrage Er...

Page 64: ...3 502 FAX 39 0 049 8873 665 Tipologia Tipology SIMPLE DEFROSTING www dgdsrl it info dgdsrl it 11 4 12 Prodotto Product Pasticceria Pastry SCHEMA ELETTRICO ELECTRICAL DIAGRAM ELECTRIQUE SCHEMA 230V 1P...

Page 65: ...NTOLE BANCO FANS CABINET 8 RESISTENZA ANTIAPPANNANTE ANTIDEMISTER HEATER SONDA TEMPERATURA TEMPERATURE PROBE 1 ALIMENTAZIONE ELETTRICA 230V ELECTRICAL POWER SUPPLY 230V Legenda Legend 5A REATTORI LAMP...

Page 66: ...IT EN F DE ARABIC Manuale d uso e manutenzione 66 Note...

Page 67: ...Manuale d uso e manutenzione IT EN F DE ARABIC 67 Note...

Page 68: ...o not commit the Manufacturer Only the information indicated on the order confirmation are binding and counts as a proof Les images du produit ont t r alis e au moment de l impression du catalogue et...

Reviews: