TFA1-298
41
-
+
L1B
L1A
-
+
TFA1-298
Warning:
the outputs OUT1 (terminal 11), OUT2 (terminal 12) and the alarm relay output ALL (terminals 3, 4, 5) are not
supervised (type C, E, J according to EN 54-1 nomenclature) and therefore, in accordance with EN 54-2, may not be used to control
fi
re alarm devices or transmission devices for
fi
re or failure alarm.
The failure relay output FAULT (terminals 6, 7, 8) is not supervised (type J according to EN 54-1 nomenclature) and therefore,
in accordance with EN 54-2, may not be used to control transmission devices for failure alarm.
9 - ELECTRONIC BOARDS
The control panel electronics are divided into two parts, the CPU board and the terminal board.
JP1 BATT
F1 3.15A - F
9-1 - Terminal board
PROTECTION AGAINST DEEP DISCHARGE
JP1 BATT
Automatic battery disconnection for Vbat <18V DC
Protection against deep discharge disabled
Fuse F1
Protection against battery reverse polarity (type 3.15A - F 5x20)
CPU board
connector
Power supply
connector
Battery connection