Single-knock
fi
re zone
The alarm of a single device (single-knock) is suf
fi
cient to generate the alarm of the zone and initiate the alarm procedure
programmed for the zone and the evacuation siren. If a device generates a prealarm, the zone will switch to prealarm state.
8-2 - Fire zones
Double-knock
fi
re zone
The prealarm or alarm of a single device generates a prealarm in the zone, the intervention of a second device causes an alarm in
the zone. However, if the
fi
rst device is a manual call point, the double-knock zone immediately issues an alarm.
Double-knock zone prealarm timeout
It is possible to set the maximum prealarm time for the double-knock zones.
If a zone in prealarm state at the end of the set timeout has switched to stand-by state, the prealarm is automatically cleared.
If, however, the prealarm condition persists, the zone remains in prealarm state until the detector switches to stand-by or another
detector of the zone switches to alarm. The timeout can be set by steps of 5 minutes from 0 (in
fi
nite) to 60 minutes.
N.B.
The
Behavior after prealarm
setting can have an effect on the alarm release.
SINGLE-KNOCK FIRE ZONE - ALARM TRIGGERING
The zone is in stand-by state
With one device in alarm state
the zone switches to alarm
One more device in alarm state triggers another alarm noti
fi
cation
SINGLE-KNOCK FIRE ZONE - PREALARM TRIGGERING
The zone is in stand-by state
With one device in prealarm state
the zone switches to prealarm
One more device in prealarm state
switches the zone to alarm and
triggers the alarm noti
fi
cations
DOUBLE-KNOCK FIRE ZONE - PREALARM TRIGGERING
The zone is in stand-by state
With one device in prealarm state
the zone switches to prealarm
One more device in prealarm state
switches the zone to alarm and
triggers the alarm noti
fi
cations
DOUBLE-KNOCK FIRE ZONE - ALARM TRIGGERING
The zone is in stand-by state
With one device in alarm state
the zone switches to prealarm
One more device in alarm state switches the zone to alarm
and triggers the alarm noti
fi
cations
Prealarm
Alarm
No alarm
Alarm
Alarm
No alarm
Prealarm
Alarm
No alarm
Prealarm
Alarm
No alarm
Summary of Contents for Tecnofire TF-A1-298-DE
Page 2: ...TFA1 298 2 ...
Page 4: ...TFA1 298 4 ...
Page 10: ...TFA1 298 10 ...
Page 14: ...TFA1 298 14 ...
Page 28: ...TFA1 298 28 ...
Page 32: ...TFA1 298 32 ...
Page 40: ...TFA1 298 40 ...
Page 46: ...TFA1 298 46 ...
Page 55: ...TFA1 298 55 NOTES ...