IST-2293.PX03.01

 

Istruzione / User’s Manual / Manuel d’utilisation 

Pag.5/12

 

 

 

 

TECNOCONTROL S.r.l. Via Miglioli 47 SEGRATE ( MI ) 

 Tel: 02/26 92 28 90   Fax: 02/21 33 734

 

 

disconnect and connect the unit, finally try to replace a new 

“Cartridge Sensor

”. If the condition is not change, it will 

be necessary to replace the unit and/or send it back to the supplier to repair. 

All LED activate (

>24mA output signal

): 

this happens when the “

Cartridge Sensor

” is not working or gas concentra-

tion is out of scale (higher than 100% LEL) If there are not any gas leaks and the condition is not change, it will be 
necessary to replace the unit and/or send it back to the supplier to repair. 

INSTALLATION 

The detector must be accurately installed and testing according to the national dispositions in force on the safety of 
the plants and installation of electric devices in areas with danger of explosion. 

Mounting

: The 

Fig. 2

 shows the instrument size. The unit must be positioned vertically with the sensor downwards. 

Models TS293PE should be fixed at 20-30 cm from the ceiling (Acetylene is lighter than air). 
Models TS293PS should be fixed at 20-30 cm from the floor (Stirene vapours are heavier than air). 
Model TS293PX-S and TS293PX-H should be fixed in high position with a gas Vapour Density less than 1 (

the gas is 

lighter than air

) or in bottom position with a density greater than 1, (

the gas is heavier than air

(

see Table 3, 4 and  5 column n.4

). 

Electrical Connection (

see Fig.2

)

: the maximum distance to install each detector from the Gas Central Unit is show 

in 

table 1

. Normally use a tree wire shielded cable. 

The terminals (+

 - S

), are plug-in type, it is necessary to extract them to make the connection. Pay attention when 

you insert them again, being polarized. With the Dip-Switches the Alarm Red Led activation is determined. 

Note:

 Dip-Switch should be set with instrument powered off. Dip-Switch 1 settled ON activates ALARM Led indica-

tion (

see Table 2

). 

Important:

 Once installation is completed,

 it is necessary to adjust the sensor to the environment conditions,

 con-

nect the unit, wait about 20÷30 minutes and then carry out the 

”Zero Adjust” 

(see ‘

Test and Calibration >

). 

COMPATIBILITY WITH OTHER CENTRAL UNITS: In case of a central unit other then Tecnocontrol, 

please 

verify the max load resistor as shown in 

Fig. 4

. We suggest using 24Vdc power supply. 

WARNING 

Average life

: The sensitive element used in this detector has an excellent stability in time. In fresh air and in nor-

mal working condition the sensor's life is about 5 years from the date of installation. After this period the yellow LED 

FAULT

” flashes every 4 seconds, is necessary replacing the “

Cartridge Sensor

”. 

Periodical testing

: we advise to carry out working tests every 12 months. Tests, Zero Adjust and Calibration with 

Gas/Air mixture as explained in chapter “

Tests and Calibration

”. 

Note:

 the detector is not able to detect gas leaks occurring outside the room where it is installed, neither inside 

walls nor under the floor. 

Important:

 

The catalytic Pellistor sensor operates only in presence of Oxygen. Do not use pure gases or a lighter 

directly on the sensor since they could damage it irremediably. 

Warning:

 

some substances cause a permanent reduction in sensitivity. Avoid contacts of the sensor with vapours 

of Silicone compounds, Tetra-ethyl Lead (petrol antiknock additive) and Phosphate esters, since they can reduce 
irremediably its sensitivity. Some substances produce a temporary loss of sensitivity. This “inhibitors” include Hy-
drogen sulphides, Chlorine, Chlorinated hydrocarbons and halogenated compounds. The sensitivity is recovered 
after a short period of running in clear air. 

TEST and CALIBRATION 

PAY ATTENTION

: This procedure has to be made with extreme attention and by authorized and trained people; 

because starting this procedure it will start both Outputs (relays) causing the activation of connected alarm devices. 
The instrument has three different code protected functions: 

Operation Check, Zero Adjust and Calibration

.  

Operation Check, Zero Adjust and Calibration:

 are different code protected functions. To access these functions is 

necessary to insert the relevant “

Code

" through the keys F1s and F2. To have the key pressure recognized, hold 

pressing it for around a second (

until the Green Led doesn't switch off for a moment

). Then the next key can be pressed. In 

case of error all it takes is waiting around 10 seconds and the sequence is automatically erased. 

Calibration Kit, Sample Gas Bottles

 (

for Calibration Check and Calibration

please, only

 

using a mixture 20%LEL 

(0.88%v/v)

 

Methane in Air (

20.9% Oxygen

).

 

Catalytic sensors cannot work without Oxygen

. It is possible to use 

either the disposable one litre cylinders with adjust valve or the high pressure ones with reduction gear. Is also 
necessary the Tecnocontrol Calibration Kit model TC011. 

“INSTRUMENT OPERATION CHECK” (

Check Code

: F2, F2, F1, F1)

this function allows to effect a functional test 

of the equipment. After having put the system in safety and inserted the "

Code Test

", all Led are switched off. Then 

they will switch on in sequence, the Led, from the yellow up to the red. At the end all the Led will remain lighted for 
around 5 seconds, then the central returns at the conditions of normal operation. It is advisable to perform this op-
eration every 6-12 months according to the use. 

Note: this function is not working if the red Led is already switched on  

 “ZERO ADJUST” (

Zero Code

: F2, F1, F1, F2)

this function is to adjust the Zero sensor and can be done in clean 

air only (environment without the presence of gas or other pollutants). Immediately after having inserted the "

Zero 

Code

", as a confirmation of the operation carried out there will be 

1

 flash of the red Led and the output will become 

4,0 mA. We suggest performing this operation after the installation or after the change of the cartridge and every 6-
12 months based on the environmental conditions. 

NoteThis function is not working if mA output is more than 5,6mA (10% LEL) and/or red Led is already 

been switched on. In this case, it will be necessary to recalibrate the unit and/or replacing the “Cartridge” 

Summary of Contents for TS293P Series

Page 1: ...placeable échangeable Uscita in Corrente Current Output Sortie en mA 4 20 mA lineare Linear linéaire Resistenza di carico load resistor résistance de charge 50 ohm 12Vdc 10 500 ohm 24Vdc 10 Campo di misura Standard Range Champ de mesure 0 100 LIE LEL Limite Scala Limits Limite échelle 100 LIE LEL Vita media in aria pulita Average Life in fresh air Vie moyenne en air pur 5 anni years ans Tempo di r...

Page 2: ...ormale deve essere acceso il solo Led Verde ON Il Led Rosso ALARM si accende se è stato abilitato se la concentrazione di Gas supera il 20 LIE I Guasti possibili sotto elencati sono indicati dall accensione del Led giallo FAULT e portando l uscita S a 0mA Il Led Giallo si accende ogni 4 secondi con il Led Verde acceso per avvisare che la Cartuccia Sensore ha su perato il suo limite di vita circa 5...

Page 3: ... e Bombole con Miscela Aria Gas per Calibrazione e Verifica la miscela da utilizzare è Gas Meta no al 20 LIE 0 88 v v in aria 20 9 Ossigeno circa in quanto i sensori catalitici Pellistor non possono assoluta mente funzionare in assenza d ossigeno È possibile usare sia bombole monouso con valvola d erogazione sia ri caricabili ad alta pressione con riduttore di pressione Inoltre è necessario il kit...

Page 4: ...s value is on compliance with EN61779 1 TS293PE is calibrated to detect Acetilene C2H2 It is a colorless gas lighter than air highly infiammable With the air easily form explosive mixtures Its density as to air is 0 9 and its LEL Lower Explosive Limit is 2 3 v v volume TS293PX S can be calibrated to detect the gases listed in Table 3 and is used in low polluted environments If other gases not list...

Page 5: ... nor under the floor Important The catalytic Pellistor sensor operates only in presence of Oxygen Do not use pure gases or a lighter directly on the sensor since they could damage it irremediably Warning some substances cause a permanent reduction in sensitivity Avoid contacts of the sensor with vapours of Silicone compounds Tetra ethyl Lead petrol antiknock additive and Phosphate esters since the...

Page 6: ... shown in Table 3 4 and 5 on column 6 corresponding to mA output value 0 2mA as indicated in column 7 The central unit should be display about the LEL value 2 as indicated in column 8 If the result is different is necessary to recalibrate the sensor see Calibration Then close the gas bottle remove TC011 Then the mA out put will slowly decrease up to 4mA Using a cylinder with the specific gas Air m...

Page 7: ...Capteur ou une concentra tion de gaz supérieur au fond d échelle 100 LIE S il n est pas constaté de fuite de gaz et que la condition perdure après la substitution de la Cartouche il sera nécessaire d envoyer le détecteur au fournisseur pour réparation INSTALLATION Les détecteurs doivent être installés positionnés et vérifiès en suivant toutes les règles nationales en vigueur pour les installations...

Page 8: ...nction des conditions ambiantes Remarque Il n est pas possible d exécuter l opération si la LED Rouge est allumée ou si la sortie en mA est supè riere a 10 de la LIE 5 6 mA Dans le cas il nécessaire de procéder a la calibration ou bien de substituer la cartouche ETALONNAGE Code de Etalonnage F2 F2 F2 F1 F2 F1 cette fonction permet l étalonnage du capteur Le mélange à utiliser est le mélange méthan...

Page 9: ...lcool isopropilico 2 Propanolo iso Propil alcool IPA 2 30 2 2 1 0 40 110 5 11 0 44 Alcool propilico 1 Propanolo n Propyl alcohol Propan 1 ol 1 69 2 2 2 1 0 44 94 5 9 45 34 Ammoniaca Ammonia 0 70 15 0 59 3 00 62 5 6 25 14 Benzina Verde Petrol unlead 2 20 2 8 1 2 0 56 110 5 11 05 44 Butano Butane 1 92 1 4 2 05 0 28 99 9 9 37 Butene 2 trans trans Butene 2 trans but2ene 1 66 1 8 1 93 0 36 94 5 9 45 34...

Page 10: ... 1 93 0 36 94 4 9 44 34 Butene 2 cis Butene 2 cis Butene 2 cis but2ene 1 95 1 60 1 93 0 32 104 0 10 40 40 Cianogeno Cyanogen Ethanedinitrile 0 93 6 00 1 80 1 2 72 0 7 20 20 Cicloesano Cyclohexane 2 19 1 20 2 90 0 24 110 4 11 04 44 Ciclopropano Cyclopropane 1 34 2 40 1 45 0 48 81 6 8 16 26 Clorobenzene Chlorobenzene 2 62 1 40 3 88 0 28 120 0 12 00 50 Cloruro di etile Chloroethane Ethyl chloride 1 5...

Page 11: ...110 4 11 04 44 Ottoano n n Octane 3 14 0 80 3 93 0 16 144 0 14 40 65 Pentano Pentane 1 94 1 40 2 48 0 28 104 0 10 40 40 Pentene 1 1 Pentene 2 07 1 40 2 40 0 28 104 0 10 40 40 Propano Propane 1 95 1 70 1 56 0 34 104 0 10 40 40 Propilamina n Propylamina 1 82 2 00 2 04 0 4 99 2 9 92 37 Propina Propyne 2 03 1 70 1 38 0 34 104 0 10 40 40 Toluene Toluolo Toluene 2 37 1 10 3 20 0 22 120 0 12 00 50 Trieti...

Page 12: ... Centrale de détection RL S Dip Switch Test Uscita Output Test Sortie Test 40 200mV TP1 TP2 S Uscita 4 20 mA 4 20 mA Output Sortie en 4 20 mA Fig 2 Schema di collegamento Wiring diagram Schéma F2 F1 mV 0 3 L min Fig 3 Tester di calibrazione Calibration Tester Kit de Calibration Alimentazione Power Supply Alimentation 100 300 400 500 50 0 5 200 Vdc RL Resistenza di carico Load resistor Resistance d...

Reviews: