background image

IST-2136.IC01.01

 

Istruzione / User’s Manual / Manuel d’utilisation 

Pag.5/10

 

 

 

TECNOCONTROL S.r.l. Via Miglioli 47 SEGRATE ( MI ) ITALY 

Tel. +39 02 26922890 - Fax +39 02 2133734

 

 

 

"zero" value. The difference signal between the two detectors provides the value of the gas concentration. The ad-
vantage of this technique is that it is selective for gases such as carbon dioxide, which is difficult to measure with 
other methods, and also has the advantage of compensating, in time, the changes of detector sensitivity. The only 
interference, may be given from presence of water vapour, which absorbs infrared. 

Preheating

: when powered, the sensor needs a time of preliminary heating of about 60 seconds. During this peri-

od the yellow LED “

FAULT

” flashes. After this period, the yellow LED light off, the green LED “

ON

” illuminates to in-

dicate normal functioning. After this period the unit is able to detect gas even if it attains the optimum stability con-
ditions after about 10÷30 minutes continual functioning (

only after this time, can be made the calibration check

). 

Normal operation

: the green LED “

ON

” should be light on. 

ALARMS:

  three  alarm  levels,  can  be  set  by  Dip-Switch  (

see  tables  2

). There  are  two  different  alarm methods,  the 

normal  one,  will  activate  the  corresponding  relays  after  a  fixed  delay,  the  advanced  one,  operate  with  TLV-TWA, 
STEL and C value, will activate the relays without delay. 

The 1st  red Led

 (

ALARM 1

) illuminates  when the  gas  concentration attains 1st  alarm level. Under  normal alarm 

method, after about 12 seconds the “

ALARM 1

" relay will activate, while under advanced one, with TLV-TWA level 

selected, the relay will activate without delay. 

The  2nd  red  Led

  (

ALARM  2

)  illuminates  when  the  gas  concentration  attains  2nd  alarm  level  and  after  about  30 

seconds, the “

ALARM 2

" relay will activate or without delay when TLV-STEL level is selected. 

The  3rd  red  Led

  (

ALARM  3

)  illuminates  when  the  gas  concentration  attains  3rd  alarm  level  and  after  about  60 

seconds, the “

ALARM 3

" relay will activate or without delay when TLV-C level is selected. 

TLV (

T

hreshold 

L

imit 

V

alues

)

 are defined as an exposure limit to which it is believed nearly all workers can be exposed 

day after day for a working lifetime without ill effect. 

TLV-TWA (

T

hreshold 

L

imit 

V

alue–

T

ime-

W

eighted 

A

verage

)

 is the time-weighted average concentration for a conventional 

8-hour workday and a 40-hour workweek, to which it is believed that nearly all workers may be repeatedly exposed, 
day after day, without adverse effect. 

TLV-STEL

 

(

T

hreshold 

L

imit 

V

alue–

S

hort-

T

erm 

E

xposure Limit

)

 is the concentration to which it is believed that workers can 

be  exposed  continuously  for  a  short  period  of  time  without  suffering  from  irritation,  chronic  or  irreversible  tissue 
damage, or narcosis. STEL is defined as a 15-minute TWA exposure, which should not be exceeded at any time 
during a workday. 

TLV-C (

T

hreshold 

L

imit 

V

alue-

C

eiling

)

 is the concentration that should not be exceeded during any part of the working exposure. 

The  values  are  recommending  exposure  levels  that  are  protective  to  workers,  OSHA  (

O

ccupational 

S

afety  and 

H

ealth 

A

dministration

, of the U.S. Department of Labour) and COSHH 

(

C

ontrol Of 

S

ubstances 

H

azardous to 

H

ealth in Europe

).

 

FAULTS

the Yellow LED (

FAULT

) illuminates, the "

S

" output falls down to 0mA (

The different faults are listed below

) and 

the “

FAULT

 normally activated relay (NC contact), will deactivate. The "

FAULT

" relay, if necessary, can be used both 

to signal remotely an occurred damage and to signal the absence of power to the instrument. 

Yellow LED illuminates each 3 seconds (

with green LED activate

):

 

this happens when the “

Sensor

” has overcome 

its period of life (about 5 years) and its correct operation is not longer guaranteed. The detector keeps on operating 
normally but it is necessary, as soon as possible,

 

replace and / or send it back to the supplier to replace the “

Sensor

” 

with a new one. 

Yellow LED activate, green LED off (

FAULT relay activates and 0 mA output signal

):

 

this signal different kind of faults. 

1)

  The  Dip  Switch  set  up  is  wrong,  please  verify  (

see  Table  2

). 

2)

  The  “

Sensor

”  is  not  working,  (fault  sensor  or  no 

communication or uncorrected). Performed the checks turn off then on the device. If the condition persists, please 
replace the unit and/or send it back to the supplier for repair. 

Yellow and green LED activates (

FAULT relay activates and 0mA output signal

):

 

this happens when the “

Sensor

” is not 

working. First try to turn off then on the device. If the condition persists, please replace the unit and/or send it back 
to the supplier for repair. 

INSTALLATION 

The detectors must be installed, positioned and carried out maintenance, following all the applicable national regu-

lations for electrical installations and safety standards of the plant. 

Mounting

: The 

Fig. 1

 shows the instrument size. The unit must be positioned vertically. The unit must be positioned 

vertically with the sensor downwards. 

SE136 IC2

 positioning

:

 s

hould be fixed at 20-30 cm from the floor (CO

2

 gas is heavier than air). 

Electrical Connection (

see Fig.2

)

: the maximum distance to install each detector from the from the power supply is 

show in 

table 1

. If more than one detector is to be powered in parallel, it is necessary to consider the voltage drop 

across the supply cable. Normally use a two wire cable (

not shielded

) for power  the wire for output relays. 

NOTE

:  If  is  also  used  the  mA  output  signal,  please  use  3  wire  shielded  cable  +  conductors  for  relay  output.  The 

max load resistor is 50 ohm with 12Vdc power supply, while is 400 ohm with 24Vdc power supply (

see fig.4

). 

Power Supply terminals, on the main board, are plug-in type, it is necessary to extract them to make the connec-
tion, pay attention when you insert them again, being polarized. The relays terminals, on outputs board, are fixed.

 

The sealed relays are

 

tension free 

SPST (

S

ingle 

P

ole 

S

ingle 

T

hrow)

 

contacts and should be set NO (Normally Open) or 

NC (Normally Closed) by positioning the 4st Dip-Switch (

see Table 3

). With the

 

Dip-Switches from 1 to 3 the concen-

tration for alarm activations is determined. Alarms can be set with TLV-TWA and STEL functioning (

see Table 2

). 

NOTE: Dip-Switch should be set with instrument powered off. Dip-Switch settled in reserved positions ac-

tivates FAULT Led indication (see “Operational Description > Faults”). 

Summary of Contents for SE136IC2

Page 1: ...empo di risposta Response Time Temps de réponse 60s T90 105s dipendente dal valore misurato depend ing on the measured value dépend de la valeur mesurée Ripetibilità di zero Zero Repeatability Zéro répétitivité 1 FS Fondo Scala Full Scale fond d échelle Precisione Accuracy Précision 0 02 vol 200ppm 5 del valore misurato of measuring value de la valeur mesurée Tempo di Preriscaldo Warm up time Temp...

Page 2: ...e e arriva al rivelatore Il rivelatore è doppio il primo definito attivo ha un filtro ottico per il gas da misurare mentre il secondo chiamato riferimento ha un filtro con una lunghezza d onda diffe rente Il rilevatore attivo viene usato per rilevare il gas mentre il rivelatore di riferimento fornisce il valore di zero La differenza di segnale tra i due rivelatori fornisce il valore di concentrazi...

Page 3: ...ssima con alimentazione 12Vcc 10 è 50ohm mentre a 24Vcc 10 è 500ohm vedi Fig 4 Il morsetto d alimentazione sulla scheda principale è ad innesto e va sfilato per collegare i cavi Prestare atten zione nel reinserirlo dato che è polarizzato Invece quelli dei Relè d allarme posti sulla scheda uscite sono fissi I relè di tipo sigillato hanno un contatto libero da tensione SPST 1 Singolo Contatto Single...

Page 4: ...la con CO2 a 1 vol 10 000ppm in Azoto l uscita in mA dovrà essere circa 12 mA 0 56mA cioè 114 126mV su TESTmV EN DESCRIPTION The SE136 IC2 series are gas detectors able to detect CO2 Carbon Dioxide by employing a NDIR Non dis persive Infrared Sensor and find their best application in centralized alarm systems for laboratories food indus tries Wineries Breweries or environments Greenhouses where mo...

Page 5: ...e to workers OSHA Occupational Safety and Health Administration of the U S Department of Labour and COSHH Control Of Substances Hazardous to Health in Europe FAULTS the Yellow LED FAULT illuminates the S output falls down to 0mA The different faults are listed below and the FAULT normally activated relay NC contact will deactivate The FAULT relay if necessary can be used both to signal remotely an...

Page 6: ...ith the yellow Led relay ALARM1 with the 1st red Led relay ALARM2 with the 2nd red Led relay ALARM3 with the 3rd red Led At the end all the Led will remain lighted for around 5 seconds then the detector returns at the conditions of normal operation It is advisable to perform this operation every 12 months according to the use Note this function is not working if the 1 st and or the 2 nd and or the...

Page 7: ...utre dite de référence comporte un filtre de longueur d onde différente et servant de référence La différence entre ces deux signaux permet de mesurer la concentration de gaz L unique cause d interférence peut être donnée par la présence de vapeur d eau qui absorbe l infrarouge Préchauffage à partir du moment où la sonde est alimentée commence le préchauffage du capteur signalé par le clignotement...

Page 8: ...contre ceux des relais d alarmes montés sur la carte de sortie sont fixes Les relais de type solide state possèdent un contact libre de tension SPST 1 Unique Contact Single Pole Single Throw qui peut être paramétré NA NO Normalement Ouvert ou NC NF Normalement Fermé selon position du Dip Switch n 4 Tableau 3 Les Dip Switch de 1 à 3 servent à déterminer les seuils d alarmes en fonction des concen t...

Page 9: ...V TP1 et TP2 voir Fig 2 on obtient la valeur en mV indiquée au Tableau 4 Colonne 6 ou bien que la sortie en mA augmente jusqu à la valeur indiquée dans la Colonne 7 0 56mA et que la centrale à laquelle est raccordée la sonde indique la valeur contenue en Colonne 8 Si le résultat est très différent contactez notre ser vice Une fois la Vérification terminée fermer la bouteille et enlever le kit TC01...

Page 10: ...a Gas heavier than air gaz plus lourd que l air Fig 1 Dimensioni Size Dimensions Fig 2 Schema di collegamento Wiring diagram Schéma S 12 24V mA 1 2 3 4 ON OFF SET ALARM 1 ALARM 2 ALARM 3 FAULT Scheda Uscite Relé Relays Output Board Sortie sur Realis TESTmA 12 24Vdc Alimentazione Power Supply Alimentation Centrale rivelazione gas Gas Central Unit Centrale de détection RL Uscita in 4 20 mA 4 20 mA O...

Reviews: